Samsung DH094EAM Installation Manual Download Page 1

E§§HNIKA

ENGLISH

INSTALLATION MANUAL
MANUAL DE INSTALACIÓN
MANUEL D’INSTALLATION
MANUALE D’INSTALLZIONE
MANUAL DE INSTALAÇÃO
INSTALLATIONS-HANDBUCH

E°XEIPI¢IO E°KATA™TA™H™

àçëíêìäñàü èé ìëíÄçéÇäÖ

ESP

A

Ñ

OL

FRAN

Ç

AIS

IT

ALIANO

POR

TUGU

Ê

S

DEUTSCH

E S F I P D G R DB98-20396A(1)

DH094EAM

Duct-type Air Conditioner 

(Cool and Heat)

Aire acondicionador Tipo Canal 

(Refrigeración y Calefacción)

Climatiseur de type Conduit 

(Refroidissement et Chauffage)

Condizionatore d’aria Tipo Conduttura 

(Raffreddamento e Riscaldamento)

Ar Condicionado Tipo Conduto 

(Refrigeração e Aquecimento)

Ventiltype Klimaanlage 

(Kühlen und Wärmen)

K

ÏÈÌ·ÙÈÛÙÈÎfi T‡Ô˘ AÂÚ·ÁˆÁÔ‡ 

(æ‡Í˘ Î·È £¤ÚÌ·ÓÛ˘)

ÇÓÁ‰Û¯Ì˚È äÓ̉ˈËÓÌÂ íÛ·ÌÓ„Ó íËÔ‡ 

(éı·ʉÂÌË ˠé·Ó„‚) 

RUSSIAN

Summary of Contents for DH094EAM

Page 1: ...G R DB98 20396A 1 DH094EAM Duct type Air Conditioner Cool and Heat Aire acondicionador Tipo Canal Refrigeración y Calefacción Climatiseur de type Conduit Refroidissement et Chauffage Condizionatore d aria Tipo Conduttura Raffreddamento e Riscaldamento Ar Condicionado Tipo Conduto Refrigeração e Aquecimento Ventiltype Klimaanlage Kühlen und Wärmen KÏÈÌ ÙÈÛÙÈÎfi T Ô AÂÚ ÁˆÁÔ æ ÍË Î È ÚÌ ÓÛË ÇÓÁ Û Ì È...

Page 2: ... pipe 9 Cutting Flaring the pipes 10 Performing leak test insulation 11 Drain hose installation 12 Connecting the connection cord 14 Increasing fan speed 16 Assigning address to indoor unit 17 Additional functions 18 Air filter installation Optional 19 Drain pump installation Optional 20 Troubleshooting 21 D D D DU U U UC C C CT T T T L L L LO O O OW W W W S S S SI I I IL L L LH H H HO O O OU U U ...

Page 3: ...llation 12 Connecting the connection cord 14 Increasing fan speed 16 Assigning address to indoor unit 17 Additional functions 18 Air filter installation Optional 19 Drain pump installation Optional 20 Troubleshooting 21 D D D DU U U UC C C CT T T T L L L LO O O OW W W W S S S SII IIL L L LH H H HO O O OU U U UE E E ET T T TT T T TE E E E II IIN N N NS S S ST T T TA A A AL L L LL L L LA A A AT T T ...

Page 4: ...INSTRUCTIO NS MANUAL DE INSTRUCCIO NES ISTRUZIONI PER L USO MANUAL DE INSTRU ES MANUEL D UTILISATION GEBRAUCHSANWEISUN G Splut type Room Air Conditioner Aire acondicionado dom stico sistema Split Condizionatore d aria per ambienti ad unit Separate Aparelho de ar condicionado tipo Split Climatiseur de type s par Geteilte raumklimaanlage Insulation Drain Insulation Cover Pipe Insulation pipe Insulat...

Page 5: ...t of public access Not touchable by the users After connecting a chamber insulate the connection part between the indoor unit and the chamber with t10 or thicker insulation Otherwise there can be air leak or dew from the connection part Space Requirements for Indoor Unit You must have 5mm or more space between the ceiling and the bottom of indoor unit Otherwise the noise from the vibration of indo...

Page 6: ...Deciding on where to install the indoor unit Continued 1 2 Liquid pipe connection Gas pipe connection No Name Remark Drawing of the indoor unit Unit mm E 6 ø9 52 ø15 88 ...

Page 7: ...nstruct a suitable support as shown in figure 3 Install the suspension bolts depending on the ceiling type 4 Screw eight nuts to the suspension bolts making space for hanging the indoor unit 5 Hang the indoor unit to the suspension bolts between two nuts 6 Screw the nuts to suspend the unit 7 Adjust level of the unit by using measurement plate for all 4 sides 8 Since the diagram is made of paper i...

Page 8: ... are ready to connect the piping N N N No o o ot t t te e e e On delivery the indoor unit is loaded with refrigerant gas All this gas must therefore be purged before connecting the assembly piping To purge the inert gas proceed as follows Unscrew the pinch pipe at the end of each refrigerant pipe Result All inert gas escapes from the indoor unit E 8 ...

Page 9: ... applying the following torque 1 Must use insulator which is thick enough to cover the refrigerant tube to protect the condensate water on the outside of pipe falling onto the floor and the efficiency of the unit will be better 2 Cut off any excess foam insulation 3 Be sure that there must be no crack or wave on the bended area 4 It would be necessary to double the insulation thickness 10mm or mor...

Page 10: ... 2 To prevent any gas from leaking out remove all burrs at the cut edge of the pipe using a reamer 3 Slide a flare nut on to the pipe and modify the flare 4 Check that the flaring is correct referring to the illustrations below for examples of incorrect flaring 5 Align the pipes and tighten the flare nuts first manually and then with a torque wrench applying the following torque 6 Outer Diameter D...

Page 11: ... Acrylonitrile Butadien Rubber separately around each refrigerant pipe 1 Wind insulating tape around the pipes 2 Finish wrapping insulating tape around the rest of the pipes leading to the outdoor unit 3 Always make the seam of pipes face upwards N N N No o o ot t t te e e e Leak Test Insulation Insulation cover pipe Be sure to overlap the insulation Indoor Unit C C C CA A A AU U U UT T T TI I I I...

Page 12: ...ose for the indoor unit to ensure that any condensate water is correctly drained outside The drain hose can be installed to the right or left side of the base pan Remove the rubber cap located on the side of the base pan depending on the situation 1 Install the drain hose so that its length can be as short as possible Internal diameter of the drain hose should be the same or slightly bigger than t...

Page 13: ...Prepare a little water about 5 liter Pour water into the base pan in the indoor unit as shown in figure 1 Confirm that the water flows out through the drain hose 2 Testing the drainage E 13 ENGLISH ...

Page 14: ...through the ceiling the hole on the wall 3 Reassemble the electrical component box cover carefully tightening the screw 4 Between Indoor and Outdoor Connection Cord Specifications 220 240V 50Hz 10 2 0mm2 H07RN F 3G Ø 1 6mm 2 wires 0 75 1 25mm2 H07RN F 2 wires 0 75 1 25mm2 2 wires Power Supply Single Phase Power Supply Max Min V ConnectionWire Earth Cable Communication Cable Home server C C C CA A ...

Page 15: ...nit Wiring and Communication Cable Connection Connect the power cable which is connected with the outdoor unit and supplied by another source making sure that the power cable terminal should not be changed Since the communication cable has the polarities be careful to connect the terminal of F1 F2 and F3 F4 rightly E 15 ENGLISH Between Indoor and Outdoor Communication Terminal Indoor Power Termina...

Page 16: ...Switch OFF position High speed H At shipment Normal speed N N N No o o ot t t te e e e External static pressure mmAq Min 0 Normal 4 Max 8 Range of static pressure SW03 K1 K2 K3 K4 K3 ON OFF Normal speed High speed Switch No If external static pressure is too great due to long extension of ducts for example the air flow volume may drop too low at each air outlet This problem can be solved by increa...

Page 17: ...ntralized controller 4 If you install optional accessories such as the wired remote controller centralized controller etc see an appropriate installation manual 5 If an optional accessory is not installed you do not have to set the RMC address However adjust K1 and K2 switches of the SW03 DIP switch to ON position in this case 6 Set the MAIN address by adjusting the rotary switch SW02 from 0 to F ...

Page 18: ...tch No Switch ON Switch OFF K6 1000 hours 2000 hours Switch No Switch ON Switch OFF Hot water heater You must adjust the K7 when you install the hot water heater K7 No use of hot water heater Use of hot water heater Switch No Switch ON Switch OFF Additional functions E 18 SW04 K5 K6 K7 K8 SW04 K5 K6 K7 K8 SW04 K5 K6 K7 K8 External Control You must adjust the K11 when you use external control K11 N...

Page 19: ...event inserting the air filter 3 Insert the air filter into the indoor unit 4 Turn the levers to the original position to fix the air filter securely 5 C C C CA A A AU U U UT T T TI I I IO O O ON N N N The optional kits must be installed by an installation specialist Before installing the optional kits ensure that you have turned off the main power The optional air filter has to be cleaned only by...

Page 20: ...ng materials N N N No o o ot t t te e e e When installing the drain pump leave a 7mm space between the bottom of the drain pan and the drain pump N N N No o o ot t t te e e e Connect the drain pump cable to yellow terminal CN74 and the float switch to black terminal CN51 N N N No o o ot t t te e e e Switch No K4 Switch Position ON OFF Using Drain Pump X O K1 K2 K3 K4 SW03 Drain pump 7mm Bottom of ...

Page 21: ...door temperature sensor Error of the condensor temperature sensor Error of the discharge temperature sensor 1 No communication for 2 minutes between indoor units Communication error for more than 2 minutes 2 Indoor unit receiving the communication error from outdoor unit 3 Outdoor unit tracking 3 minutes error 4 When sending the communication error from the outdoor unit the mismatching of the comm...

Page 22: ...n of high temperature discharge 5 Error of reverse phase 6 Compressor down due to 6 th detection of freezing Communication error between indoor units X X X X X X X X On Flickering X Off If you turn off the air conditioner when the LED is flickering the LED is also turned off LED Display Detection of the float switch X X EEPROM error X X EEPROM option error Remarks Abnormal conditions Indicators Bl...

Page 23: ...aster wired remote controller Slave wired remote controller COM1 COM2 Cross installed error Error of setting option for wired remote controller COM2 Error of discharge temperature sensor Open Short System down caused by communication error after completion of tracking Mismatching of the indoor unit numbers set with those communication after completion of 5 times tracking Error of electronic expans...

Page 24: ...E 24 Parts list 25 O O O OP P P PT T T TI I I IO O O ON N N NA A A AL L L L A A A AC C C CC C C CE E E ES S S SS S S SO O O OR R R RI I I IE E E ES S S S Chapter ...

Page 25: ...rew 7 Cable tie 2 Cable clamp 5 Wireless remote controller 1 Battery 2 Remote control holder 1 STS 2S 2x10 tapped screw 2 Owner s instructions 1 Installation manual 1 Owner s instructions 1 Installation manual 1 Owner s instructions 1 Installation manual 1 Wireless Remote Controller Accessories Wire kit length 10m 1 Wire kit length 10m 1 Receiver display unit Wire kit Receiver display unit Wire ki...

Page 26: ...ed Remote Controller Accessories Owner s instructions 1 Installation manual 1 Parts list continued Wired remote controller 1 Cable tie 2 Cable clamp 5 M4x16 tapped screw 7 Indoor unit power drawing cable 1 Wire joint 1 Communication cable of the wired remote controller 1 Owner s instructions 1 Installation manual 1 ...

Page 27: ...e 1 Installation manual 1 Function controller 1 Cable tie 2 Cable clamp 6 M4x16 tapped screw 7 Function Controller Accessories Owner s instructions 1 Installation manual 1 If you would like to install the centralized controller you must install the transmitter in the outdoor unit N N N No o o ot t t te e e e ...