background image

14

       Carbon  

       plastic       

Steel core

PVC-insulated green

/yellow wire, 2mm

²

 x 3.5 m

To earthing 

screw

50 cm

30

 cm

1. Select an earthing electrode that complies with the specifications 

given in the illustration opposite.

2. Determine a suitable location for the earthing electrode :

 

  

In damp hard soil rather than loose sandy or gravel soil that has a

        higher earthing resistance.
   

Away from underground structures or facilities, such as gas pipes,

        water pipes, telephone lines and underground cables.
   

At least two meters away from a lightening conductor earthing 

        electrode and its cable.

≫ 

The earthing wire for the telephone line cannot be used to earth the    

       air conditioner.

3. Dig a hole of the size indicated in the illustration opposite, drive the 

earthing electrode into position and cover the top of the electrode with 

the excavated soil.

4. Install a green/yellow insulated earthing wire (Ø1.6 mm, section 2 mm

²

 or 

greater) :

   

If the earthing wire is too short, connect an extension lead, soldering   

        the connection and wrapping it with insulating tape (Do not bury the  

        soldered connection.)
   

Secure the earthing wire in position with staples. If the earthing 

        electrode is installed in an area of heavy traffic, its wire must be  

        connected securely.j

5. Carefully check the installation, by measuring the earthing resistance 

with an earthing resistance tester. If the resistance is above the required 

level(Example:100Ω), drive the earthing electrode deeper into the ground

or increase the number of earthing electrodes.

6. Connect the earthing wire to the earthing screw on the air conditioner.

If the power distribution circuit does not have an earth or the earth does not comply with specifications, an 

earthing electrode must be installed. The corresponding accessories are not supplied with the air conditioner.

Method for connecting wires

Checking correct earthing

Tightening power terminal

≫  

Connect the cables to the terminal board using the compressed ring terminal.

≫  

Use rated cables only.

≫  

Connect the cables with driver and wrench that can apply the rated torque to the screws.

≫  

Make sure that appropriate tightening torque is applied for cable connection. If the terminal is loose, arc heat may 

 

occur and cause fire and if the terminal is connected too firmly, terminal may get damaged.

Screw

Tighten Torque(kgf • cm)

Position

M4

12.0~15.0

1(L), 2(N), L, N, F1, F2

RJ100F5HXEA_IM_E_32978A(4).indd   14

2012-10-25   오후 5:22:45

www.keveklima.hu

Summary of Contents for DB98032978A

Page 1: ...hank you for purchasing this Samsung product To receive more complete service please register your product at www samsung com register DB98 32978A 4 S E F I P D G RJ100F5HX AJ100FCJ5 RJ100F5HXEA_IM_E_...

Page 2: ...always carefully read the following warnings Store the operation and installation manual in a safe location and remember to hand it over to the new owner if the air conditioner is sold or transferred...

Page 3: ...substances or close to equipment that release free flames to avoid the occurrence of fires explosions or injuries To prevent injury when accidentally touching the indoor unit fan install the indoor un...

Page 4: ...are not supplied use the standard cable approved by IEC standard Please check Method for connecting wires section 3 wire Power Cable option 2 wire Assembly Cable option Drain Plug Installation Manual...

Page 5: ...tdoor unit so that the air flow is directed towards the outside as indicated by the arrows on the top of the unit Maintain sufficient clearance around the outdoor unit as indicated in page 8 Make sure...

Page 6: ...or more 2000 or more The upper part of the outdoor unit and the air outlet is towards the wall 1500 or more 600 or more 300 or more The upper part of the outdoor unit and the air outlet is opposite th...

Page 7: ...e in the noise level and vibration particularly if the outdoor unit is to be installed close to a neighbour If it is to be installed in a location exposed to strong winds or at a height the unit must...

Page 8: ...and vibration Indoor unit Outdoor unit Power supply V Hz 020 023 026 030 035 052 07 09 12 18 24 RJ100F5HX AJ100FCJ5 1 220 240 50 60 Unit Outside diameter Liquid Gas 020 023 026 030 035 07 09 12 1 4 3...

Page 9: ...ct up to the outdoor unit and purge the circuit refer to page 10 While heating ice may accumulate During the process of defrosting check if condensation draining is adequate For adequate draining do t...

Page 10: ...4 Purge the air from the system using vacuum pump for about 30 minutes Close the valve of the low pressure side of manifold gauge clockwise Make sure that pressure gauge show 0 1MPa 76cmHg after abou...

Page 11: ...echeckedforleakageatleastonceevery12months ac cordingtoregulationN 842 2006 Thisactivityhastobecoveredbyqualified personnelonly Incasesituationabove 3kgormoreofR 410A installer orrecognisedperson whic...

Page 12: ...system on in cooling with fan operating at high velocity Compressor will immediately start provided 3 minutes have elapsed since the last stop 3 After 2 minutes of operation shut off the suction valv...

Page 13: ...munication Cable Specification 2G 0 75mm2 or more Abbreviations MCA Min Circuit Amps A MFA Max Fuse Amps A 1 L 2 N 1 L 2 N A B 1 L 2 N F1 F2 1 L 2 N F1 1 L 2 N F1 1 L 2 N F1 F2 1 2 F1 F2 F1 F2 1 2 2 1...

Page 14: ...ith staples If the earthing electrode is installed in an area of heavy traffic its wire must be connected securely j 5 Carefully check the installation by measuring the earthing resistance with an ear...

Page 15: ...it connected to refrigerant pipe A The outdoor unit is communicating correctly with the indoor unit connected to refrigerant pipe B The outdoor unit is communicating correctly with the indoor unit con...

Page 16: ...ftdisplayofoutdoorunitdisplayPCB DIS01 willcountfrom00 01 02to15 Estabilishedcommunicationtheleftdisplaywillcountsequentially 00 communicationwithindoorunitA 01 communicationwithindoorunitB 02 communi...

Page 17: ...TO SET ADDRESSING MANUALLY BY ROTARY SWITCH SW02 RAC MH020FV N A MH023FB MH026FB V N A MH035FB V N A MH052FB V N A IT S HERE sw02 MAIN PCB SLIM 1 WAY CASSETTE MH026FS MH035FS sw02 MINI 4 WAY CASSETTE...

Page 18: ...by 1 4 You press button to move to the next setteing page 5 After setting option press button to check whether the option code you input is correct or not 6 Press operation button with the direction o...

Page 19: ...tton to enter SEG12value Step 7 Press Mode button to be changed to AUTO mode in the OFF status 1 Press Fan button to enter SEG14 value 2 Press High Fan button to enter SEG15 value Step 8 Press Mode bu...

Page 20: ...it address 10 digit of indoor unit A single digit of indoor unit Remote Controller Display Indication andDetails Indication Details Indication Details Indication Details Indication Details Indication...

Page 21: ...t the option value of SEG4 6 If you set the SEG 9 as 0 the indoor unit will maintain previous RMC ADDRESS even if you input the option value of SEG11 12 5 The MAIN address is for commnication between...

Page 22: ...umber of electric and electronics loads consumption and use Ampere limits switch DIP Switch just as emergency solution or in case the system is anyway oversized compared to real thermal load needed Am...

Page 23: ...Explanation Push Display Explanation 0 Present Compressor Frequency 8 Discharge temperature 1 Target Compressor Frequency 9 OLP temperature 2 EEV0 current step 10 Condenser temperature 3 EEV1 current...

Page 24: ...units refer to page 26 5 Assemble a cover of the outdoor unit and turn the power on 6 Check the communication status 7 If you install a transmitter to the outdoor unit every indoor unit which is conn...

Page 25: ...PCB as seen in the picture 5 Connect the wire remote controller central remote controller etc to the sub PCB 6 Assemble the panel frame and the front panel The product and accessories may look differ...

Page 26: ...lave Indication andDetails Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 1 0 0 0 0 0 Slave 1 Master Option SEG13 SEG14 SEG15 SEG16 S...

Page 27: ...fan motor can remain off to avoid cold air blown into conditioned space Before leaving the premises on which you have installed the air conditioner you should explain the following operations to the o...

Page 28: ...installationthroughautoaddressingmodewithoutpipecheckoperation Check setting The number of Indoor unit mismatched Check electrical connection and setting Communication error between the outdoor and in...

Page 29: ...lf diagnosis Outdoor unit EEV open operating indoor unit s Self diagnosis High temperature over 30 C of outdoor as heating mode Low temperature under 10 C of outdoor as cooling mode Outdoor Fan Error...

Page 30: ...EEE Y netmeli ine Uygundur This EEE is compliant with RoHS RJ100F5HXEA_IM_E_32978A 4 indd 30 2012 10 25 5 22 55 w w w k e v e k l i m a h u...

Page 31: ...conditions kW 3 0 3 0 3 7 R Assumed backup heating capacity kW 0 0 0 1 Refrigerant leakage contributes to climate change Refrigerant with lower global warming potential GWP would contribute less to g...

Page 32: ...kW 4 3 5 5 5 8 R Assumed backup heating capacity kW 0 0 0 1 Refrigerant leakage contributes to climate change Refrigerant with lower global warming potential GWP would contribute less to global warmin...

Page 33: ...ons kW 5 8 7 7 7 7 R Assumed backup heating capacity kW 0 0 0 1 Refrigerant leakage contributes to climate change Refrigerant with lower global warming potential GWP would contribute less to global wa...

Page 34: ...at reference design conditions kW 3 7 5 8 4 3 R Assumed backup heating capacity kW 0 0 0 1 Refrigerant leakage contributes to climate change Refrigerant with lower global warming potential GWP would c...

Page 35: ...n conditions kW 5 8 7 7 5 8 R Assumed backup heating capacity kW 0 0 0 1 Refrigerant leakage contributes to climate change Refrigerant with lower global warming potential GWP would contribute less to...

Page 36: ...sign conditions kW 5 8 7 7 3 0 R Assumed backup heating capacity kW 0 0 0 1 Refrigerant leakage contributes to climate change Refrigerant with lower global warming potential GWP would contribute less...

Page 37: ...at reference design conditions kW 3 7 5 8 3 7 R Assumed backup heating capacity kW 0 0 0 1 Refrigerant leakage contributes to climate change Refrigerant with lower global warming potential GWP would c...

Page 38: ...ference design conditions kW 3 7 5 8 3 7 R Assumed backup heating capacity kW 0 0 0 1 Refrigerant leakage contributes to climate change Refrigerant with lower global warming potential GWP would contri...

Page 39: ...kW 0 0 1 Refrigerant leakage contributes to climate change Refrigerant with lower global warming potential GWP would contribute less to global warming than a refrigerant with higher GWP if leaked to...

Page 40: ...acit nerg tique SCOP K Classe di efficienza energetica SCOP L QHE 3 temporada calefacci n L QHE 3 saison chaude L QHE 3 stagione di riscaldamento M Otras temporadas de calefacci n declaradas aptas par...

Page 41: ...etrieb SCOP J SCOP K Classe de efici ncia energ tica SCOP K Energieeffizienzklasse SCOP K SCOP L QHE 3 esta o de aquecimento L QHE 3 Heizperiode L QHE 3 M Outras esta es de aquecimento utiliz veis M W...

Page 42: ...jamais d interf rer avec le circuit de fluide frigorig ne ou de d monter le produit vous m me et demandez toujours conseil un professionnel 2 Consommation nerg tique XYZ kWh par an bas e sur des r sul...

Page 43: ...e da sua localiza o DEUTSCH 1 K ltemittelverlust tr gt zum Klimawandel bei K ltemittel mit niedrigeremTreibhauspotenzial GWP tragen im Falle eines Entweichens in die Atmosph re in geringerem Ma e zur...

Page 44: ...14 Memo RJ100F5HXEA_IM_Product fiche_32978A 4 indd 14 2012 11 12 3 59 56 w w w k e v e k l i m a h u...

Reviews: