Thank you for purchasing this Samsung product.

NASA_Big Duct_AM@@@FNHDEH@_IM_EN_03653A-06.indd   1

2016-12-01   오후 3:06:48

Summary of Contents for AM280FNHDEH

Page 1: ...onditioner installation manual Duct Type Series BIG duct AM FNHDEH imagine the possibilities Thank you for purchasing this Samsung product NASA_Big Duct_AM FNHDEH _IM_EN_03653A 06 indd 1 2016 12 01 3...

Page 2: ...10 Cutting Flaring the Pipes 11 Performing Leak Test Insulation 13 Drain pipe and Drain hose Installation 14 Wiring Work 18 Setting an indoor unit address and installation option 24 Setting temperatu...

Page 3: ...le to the general public This appliance should be installed according to the provided installation instruction When installing the air conditioner in a small room the measure not to exceed the dangero...

Page 4: ...sufficient or electric work is not properly completed electric shock or fire may occur Install the cables with supplied cables firmly Fix them securely so that external force is not exerted to the ter...

Page 5: ...the ballast of the lighting apparatus Do not install the air conditioner in following places Place where there is mineral oil or arsenic acid Resin parts flame and the accessories may drop or water ma...

Page 6: ...y differ depending on the specifications User s manual Installation manual Pattern sheet Insulation cover pipe out Insulation pipe A Insulation pipe B Washer Clamp hose Flexible hose Cable tie Sleeve...

Page 7: ...vice clean and repair the unit It is possible to install the unit at an height of between 2 2 2 5m from the ground if the unit has a duct with a well defined lenght 300mm or more to avoid fan motor bl...

Page 8: ...ommunication connection 6 Air discharge grille flange 7 Air suction flange 8 Hook 9 52 or M10 Selecting the Installation Location Continued 140X8 1120 1306 Suspension position 1188 Air inlet duct flan...

Page 9: ...olts between two nuts Screw the nuts to suspend the unit Adjust level of the unit by using measurement plate for all 4 sides Since the diagram is made of paper it may shrink or stretch slightly due to...

Page 10: ...frigerant pipes of differing diameters A smaller one for the liquid refrigerant A larger one for the gas refrigerant The inside of copper pipe must be clean has no dust The connection procedure for th...

Page 11: ...R410Aclutchtype Conventional flare tool Clutch type Wing nut type 6 35 0 0 5 1 0 1 5 1 5 2 0 9 52 0 0 5 1 0 1 5 1 5 2 0 12 70 0 0 5 1 0 1 5 1 5 2 0 15 88 0 0 5 1 0 1 5 1 5 2 0 5 Check if you flared t...

Page 12: ...le Butadien Rubber separately around each refrigerant pipe Note Always make the seam of pipes face upwards 2 Wind insulating tape around the pipes and drain hose avoiding to compress the insulation to...

Page 13: ...condition Restaurant ceiling sauna swimming pool etc Building construction condition The ceiling frequently exposed to moisture and cooling is not covered e g The pipe installed at a corridor of a dor...

Page 14: ...y bigger than the external diameter of the drain hose port 4 Wrap the drain hose with the insulation drain as shown in figure and secure it Fix the flexible hose to the indoor unit with the supplied c...

Page 15: ...f 1 100 or more and fix it by hanger space of 1 0 1 5m 3 Install the air vent in the horizontal drain pipe to prevent water flow back to the indoor unit You may not need to install it if there were pr...

Page 16: ...vent at the front of the farthest indoor unit from the main drain when installed indoor units are more than 3 2 You may need to install individual air vent to prevent water flow back at the top of eac...

Page 17: ...mp pumping 3 Testing the drainage Confirm that the water flows out through the drain hose 2 Reassemble the cover of water supply intake 6 Check drain water drops at the end of the drain pipe 4 Make su...

Page 18: ...en installing the wired remote control Power and communication cable connection WiringWork Connecting power for optional product When installing optional product make sure to follow below current capa...

Page 19: ...on manual about the rating current of indoor unit Decide the power cable specification and maximum length within 10 power drop among indoor units T coef 1 55 T Lk Distance among each indoor unit m Ak...

Page 20: ...6 Lk ik 10 of input voltage V 1000 Ak n k 1 h Calculation Installing with 1 sort wire 220 V 2 2 V 2 0 V 2 5 mm2 208 8 V Within 198V 242V 2 2 2 0 1 8 1 5 1 3 1 1 0 9 0 7 0 4 0 2 11 2 V it s okay 2 5 m...

Page 21: ...e auxiliary circuit breaker An all pole disconnection from the power supply must be incorporated in the fixed wiring 3mm You must keep the cable in a protection tube Keep distances of 50mm or more bet...

Page 22: ...nit mm 120 60 20 20 20 180 Power cable 20 Pre installed tube for the power cable 3 f f Method 1 Push the core wire into the sleeve from both sides Connection sleeve f f Method 2 Twist the wire cores t...

Page 23: ...th the insulation tape to finish Insulation tape Make sure that the connection parts are not exposed to outside Be sure to use insulation tape and a contraction tube made of approved reinforced insula...

Page 24: ...change Low Temp Button Low Fan Button Entering mode for option setting Option setting mode MR EC00 MR EH00 High Temp Button High Fan Button Mode change Low Temp Button Low Fan Button Entering mode for...

Page 25: ...Setting Fan mode Press Mode button to be changed to FAN mode in the ON status 7 Setting SEG9 SEG10 option Press Low Fan button to enter SEG9 value Press High Fan button to enter SEG10 value Each time...

Page 26: ...Fan button to enter SEG22 value Each time you press the button will be selected in rotation 18 Setting Heat mode Press Mode button to be change to HEAT mode in the OFF status 19 Setting SEG23 SEG24 mo...

Page 27: ...0 No Main address 0 9 100 digit 0 9 10 digit 0 9 Aunit digit 1 Main address setting mode Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE SettingRMCaddress Groupchannel 16 Groupaddress Remote...

Page 28: ...control of a remote controller Heating setting compensation Removing condensated water in heating mode EEV Step of stopped unit during oil return defrost mode Motion detect sensor 1WAY 2WAY 4WAY MODEL...

Page 29: ...tion and Details Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 1 0 Disuse 0 Disuse 0 Default value 1 Use 1 Use 2 1 Noise decreasing...

Page 30: ...ff when the hot water heater is turned on with cooling only indoor unit Cooling only indoor unit To use this option install the Mode Select switch MCM C200 on the outdoor unit and fix it as cool mode...

Page 31: ...ng WhensettingSEG3 Timerequiredformode change Compensationoptionfor Longpipeorheight differencebetweenindoor units SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 2 Control variables when using hot water external...

Page 32: ...3 C 6 3 C 6 4 C 7 3 5 C 7 3 5 C 7 4 5 C Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE WhensettingSEG3 Standardformode changing Cooling Heating mode WhensettingSEG3 Timerequiredformode chang...

Page 33: ...g thermostat is on and turned off when the heating thermostat is off e g 2 Setting 02 series SEG15 2 Setting 05 series SEG18 A Room temp set temp f heating compensation temp External heater is turned...

Page 34: ...hSEG4 C B SetwithSEG5 C C SetwithSEG6 C D SetwithSEG8 C Cooling Thermo Off Heating Thermo Off Cooling Thermo On Heating Thermo On B C D Ts A c a Temp d b Standardtemp forHeating Standardtemp forCoolin...

Page 35: ...umpmodel mixedoperationmode twoormoreindoorunitsoperatingindifferentoperationmode simultaneously isnotavailablewhentheindoorunitsareconnectedtosameoutdoorunit Ifyousetthemasterindoorunit witharemoteco...

Page 36: ...ion of the air conditioner you should explain the following to the user Refer to appropriate pages in the User s Manual 1 How to start and stop the air conditioner 2 How to select the modes and functi...

Page 37: ...ived from the outdoor unit 3 3 miniute tracking error on outdoor unit 4 Communication error after tracking due to unmatching number of installed units 5 Error due to repeated communication address 6 C...

Page 38: ...on 6 Indoor operation stop due to unconfirmed error on outdoor unit 7 Error due to reverse phase detection 8 Comp stop due to freeze detection 6th detection 9 High pressure sensor is detached 10 Low p...

Page 39: ...ion place is in When it is out of input the appropriate option code If you input the inappropriate option code error may occur or the air conditioner is out of order The option code must be inputted c...

Page 40: ...This product is RoHS compliant DB68 03653A 06 NASA_Big Duct_AM FNHDEH _IM_EN_03653A 06 indd 40 2016 12 01 3 07 02...