Troubleshooting
Samsung Electronics
95
4-3-15
MCU branch part setup error – Connect more Indoor units than what is actually set up
in MCU
1. How to check
Check the number of indoor units connected to MCU then readjust the switch for the number of units.
After completing resetting, press the outdoor unit's K3 button to reset or turn off to restart.
• Example of MCU indoor unit setting DIP switch error.
ex) Indoor unit No.5 was connected to branch part C, but DIP switch No.3 (branch part C) is off.
Outdoor Unit PBA
Quantity of
Indoor
Quantity of
MCU
Indoor Unit: 4 MCU: 1
Branch
Outdoor unit
display
Indoorunit
display
Duct, Cassette (1/2 Way),Console, Celing
Cassette (4/Mini4 Way)
Wall-mounted (NeoForte)
Operation Defrost Timer Fan Filter/
MPI Operation Defrost Timer Filter Operation Timer Turbo 24
℃
27
℃
×
×
◑
◑
×
×
◑
◑
×
×
×
◑
◑
×
※ ●
: ON
◑
: Flash ×: OFF
Judgment
Method
• Occurs when the number of indoor unit installed exceeds that setting in MCU
Cause of
problem
• Number of indoor units exceeds number of indoor units entered on MCU setting
4-3 Appropriate Measures for Different Symptom (cont.)