Page 1: ...미주향_DVMS_1Way Cassette_IM_EN_03806A 1 indd 34 2013 03 06 오후 5 58 38 ...
Page 2: ...this Samsung product To receive more complete service please register your product at www samsung com register Cassette Type Series Slim 1 Way cassette DB68 03806A 1 This manual is made with 100 recycled paper PT FR ES EN 미주향_DVMS_1Way Cassette_IM_EN_03806A 1 indd 35 2013 03 06 오후 5 58 38 ...
Page 3: ...e Refrigerant Pipe 11 Cutting Flaring the Pipes 12 Performing Leak Test Insulation 13 Drainpipe and Drain Hose Installation 15 Bushing Bracket Installation 17 Wiring Work 18 Setting an indoor unit address and installation option 21 Final Checks and User Tips 30 Troubleshooting 31 미주향_DVMS_1Way Cassette_IM_EN_03806A 1 indd 2 2013 03 06 오후 5 58 14 ...
Page 4: ...d of as special waste At the end of its life cycle the air conditioner must be disposed of in authorized centers or returned to the retailer so that it can be disposed of correctly and safely Installing the unit IMPORTANT When installing the unit always remember to connect first the refrigerant tubes then the electrical lines Always disassemble the electric lines before the refrigerant tubes Upon ...
Page 5: ...st of the lighting apparatus Do not install the air conditioner in following places Place where there is mineral oil or arsenic acid Resin parts flame and the accessories may drop or water may leak The capacity of the heat exchanger may reduce or the air conditioner may be out of order The place where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outlet The copper pi...
Page 6: ...ay correctly and safely The indoor unit must be installed in this way that they are out of public access Not touchable by the users Rigid wall without vibration Where it is not exposed to direct sunshine Where the air filter can be removed and cleaned easily Asarule theunitcannotbeinstalledataheightoflessthan2 5m 8 2ft Itispossibletoinstalltheunitataheightofbetween2 2 2 5m 7 2 8 2ft fromtheground ...
Page 7: ...g the Installation Location Continued Space Requirements for Indoor Unit 1500 59 or more 1500 59 or more 1500 59 ormore 1500 59 ormore Unit mm inch 미주향_DVMS_1Way Cassette_IM_EN_03806A 1 indd 6 2013 03 06 오후 5 58 15 ...
Page 8: ...nsion position Ceiling opening Ceiling Drain hole Ceiling opening Suspension position 1150 45 28 1035 8 40 78 249 9 80 440 17 32 21 0 83 77 3 03 52 2 05 50 1 97 85 3 35 970 38 19 135 5 31 40 1 57 25 0 98 150 5 91 410 16 14 1198 47 17 500 19 69 1150 45 28 Suspension position 1035 8 40 78 Ceiling opening 249 9 80 Ceiling opening 440 17 32 Suspension position Drain hole Ceiling 미주향_DVMS_1Way Cassette...
Page 9: ...s Note 2 Insert bolt anchors use existing ceiling supports or construct a suitable support as shown in figure 3 Install the suspension bolts depending on the ceiling type Ensure that the ceiling is strong enough to support the weight of the indoor unit Before hanging the unit test the strength of each attached suspension bolt If the length of suspension bolt is more than 1 5m 4 92 ft it is require...
Page 10: ...e indoor unit by using the gauge of dimensions You should adjust the gauge of dimensions and the pattern sheet to fit the cutting dimensions of ceiling Make sure that the indoor unit is installed at a level if the indoor unit slants too much there can be water leaks 7 Tighten the upper part nuts 8 Remove the gauge of dimensions after installing the indoor unit Level Nut Washer Rubber Fasten the nu...
Page 11: ...Therefore all insert gas must be purged before connecting the assembly piping Unscrew the pinch pipe at the end of each refrigerant pipe Result All inert gas escapes from the indoor unit Note To prevent dirt or foreign objects from getting into the pipes during installation do NOT remove the pinch pipe completely until you are ready to connect the piping 미주향_DVMS_1Way Cassette_IM_EN_03806A 1 indd ...
Page 12: ...the flaring area to prevent a leak Note 3 Be sure that there must be no crack or kink on the bended area Connecttheindoorandoutdoorunitsusingpipeswithflared connections notsupplied Forthelines useinsulated unwelded degreasedanddeoxidizedcopperpipe CuDHPtypetoISO1337 suitableforoperatingpressuresofatleast4200kPa 609 2psi andforaburst pressureofatleast20700kPa 3002 3psi Copperpipeforhydro sanitary a...
Page 13: ...nch 6 35 1 4 0 0 5 0 0 02 1 0 1 5 0 04 0 06 1 5 2 0 0 06 0 08 9 52 3 8 0 0 5 0 0 02 1 0 1 5 0 04 0 06 1 5 2 0 0 06 0 08 12 7 1 2 0 0 5 0 0 02 1 0 1 5 0 04 0 06 1 5 2 0 0 06 0 08 15 88 5 8 0 0 5 0 0 02 1 0 1 5 0 04 0 06 1 5 2 0 0 06 0 08 5 Check if you flared the pipe correctly There are some examples of incorrectly flared pipes below Inclined Correct Damaged Surface Cracked UnevenThickness 6 Align...
Page 14: ...e piping and hose 1 To avoid condensation problems place T13 0 1 2 or thicker Acrylonitrile Butadien Rubber separately around each refrigerant pipe Note Always make the seam of pipes face upwards 2 Wind insulating tape around the pipes and drain hose avoiding to compress the insulation too much 3 Finish wrapping insulating tape around the rest of the pipes leading to the outdoor unit 4 The pipes a...
Page 15: ...condition Restaurant ceiling sauna swimming pool etc Building construction condition The ceiling frequently exposed to moisture and cooling is not covered e g The pipe installed at a corridor of a dormitory and studio or near an exit that opens and closes frequently The place where the pipe is installed is highly humid due to the lack of ventilation system Refrigerant pipe before EEV kit and MCU o...
Page 16: ...connected part doesn t leak Drain pipe type VP20 2 Connect the flexible hose to the drain hose port Make sure that a rubber ring is installed on the drain hose port Drain hose port location differs depending on the unit types 3 Install the drain pipe as shortly as possible Give a slightly slant to the drainpipe for proper drainage of condensate water There must be no gap on the connected part so t...
Page 17: ... 100 3 94 ormore Ceiling Hanger Centralized Drainage 1 Install main air vent at the front of the farthest indoor unit from the main drain when installed indoor units are more than 3 2 You may need to install individual air vent to prevent water flow back at the top of each indoor unit drainpipe Hanger Main drainpipe Individual air vent Main air vent Centralized horizontal drainpipe more than 1 100...
Page 18: ... Drain water drops 5 Make sure there is no water leak at the drainage 6 When you finished the test close the coverside Whenmaintainingtheairconditioner removecondensatewater remainedinthedrainpanbyusingadrainportformaintenance Leveler Air outlet 1 If the conduit tube is used bushing bracket must be installed as shown in the picture to fix the conduit tube Bushing Bracket Installation Drain pipe an...
Page 19: ... Power and communication cable connection Norminaldimensionsforcable mm2 inch2 1 5 0 002 2 5 0 003 4 0 006 Norminaldimensionsforscrew mm inch 4 0 15 4 0 15 4 0 15 4 0 15 4 0 15 B Standard dimension mm inch 6 6 0 25 8 0 0 31 6 6 0 25 8 5 0 33 9 5 0 37 Allowance mm inch 0 2 0 007 0 2 0 007 0 2 0 007 D Standard dimension mm inch 3 4 0 13 4 2 0 16 5 6 0 22 Allowance mm inch 0 3 0 011 0 2 0 007 0 3 0 0...
Page 20: ...ower cable specification mm2 inch2 ik Running current of each unit A Coef 35 6 Lk ik 10 of input voltage V 1000 Ak n k 1 Example of Installation Total power cable length L 100m 328 08ft Running current of each units 1 A Total 10 indoor units were installed 10 A Indoor unit10 20 m 65 62 ft 10 m 32 8 ft 0 m 9 A 1 A 100 m 328 ft MCCB Indoor unit2 Indoor unit1 ELB Apply following equation Coef 35 6 Lk...
Page 21: ... the power supply must be incorporated in the fixed wiring 3mm 1 8 You must keep the cable in a protection tube Keep distances of 50mm 2 or more between power cable and communication cable Maximum length of power cables are decided within 10 of power drop If it exceeds you must consider another power supplying method The circuit breaker MCCB ELB should be considered more capacity if many indoor un...
Page 22: ...nd LowTemp button 3 Check if you have entered the option setting status Step 2 The procedure of option setting After entering the option setting status select the option as listed below HighTemp Button High Fan Button Mode change LowTemp Button Low Fan Button Entering mode for option setting Option setting mode Option setting is available from SEG1 to SEG 24 SEG1 SEG7 SEG13 SEG19 are not set as pa...
Page 23: ...ton will be selected in rotation 6 Setting Fan mode Press Mode button to be changed to FAN mode in the ON status 7 Setting SEG9 SEG10 option Press Low Fan button to enter SEG9 value Press High Fan button to enter SEG10 value Each time you press the button will be selected in rotation 8 Setting Heat mode Press Mode button to be changed to HEAT mode in the ON status 9 Setting SEG11 SEG12 option Pres...
Page 24: ...EG22 value Each time you press the button will be selected in rotation 18 Setting Heat mode Press Mode button to be change to HEAT mode in the OFF status 19 Setting SEG23 SEG24 mode Press Low Fan button to enter SEG23 value Press High Fan button to enter SEG24 value Each time you press the button will be selected in rotation SEG16 SEG18 SEG21 SEG23 SEG17 SEG20 SEG22 SEG24 Step 4 Input option Press...
Page 25: ...on Details Indication Details 0 A 0 NoMain address 0 9 100 digit 0 9 10 digit 0 9 Aunit digit 1 Main address setting mode Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE SettingRMCaddress Groupchannel 16 Groupaddress Remote Controller Display Indication andDetails Indication Details Indication Details Indication Details Indication Details 1 0 NoRMC address RMC1 0 F RMC2 0 F 1 RMC address ...
Page 26: ... Hot water heater EEV Step when heating stops Master Slave SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 2 External control External control output S Plasma ion Buzzer Number of hours using filter SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 3 Individual control of a remote controller Heating setting compensation EEVStepof stoppedunitduring oilreturn defrost mode Motiondetectsensor 1WAY 2WAY 4WAY MODEL Drain pump SE...
Page 27: ...s Master Slave Remote Controller Display Indication andDetails Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 1 0 Disuse 0 Disuse 0 Disuse 0 Default value 0 slave 1 Use 1 Use 1 Use 1 Noise decreasing setting 1 master 2 Whenan indoorunit stops drain pumpwill operate for3min Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 Explanation PAGE...
Page 28: ...ed function 2 5 C 41 F 6 Turnoutin 60min withoutmotion or advanced function 7 Turnoutin 120min withoutmotion or advanced function 4 channel4 8 Turnoutin 180min withoutmotion or advanced function SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 0 5 UseofAutoChangeOver forHRonlyinAutomode WhensettingSEG3 Standardheatingtemp Offset WhensettingSEG3 Standardcoolingtemp Offset WhensettingSEG3 Standardformodechange Heating...
Page 29: ...rdcoolingtemp Offset WhensettingSEG3 Standardformode change Heating Cooling Remote Controller Display Indication andDetails Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 0 5 0 Follow product option 0 0 0 0 0 1 1 UseAuto Change Overfor HRonly 1 0 5 1 0 5 1 1 5 2 1 2 1 2 2 3 1 5 3 1 5 3 2 5 4 2 4 2 4 3 5 2 5 5 2 5 5 3 5 6 3 6 3 6 4 ...
Page 30: ...A When changing a digit of indoor unit installation option set the SEG3 as 2 Ex When setting the buzzer control into disuse status Note ued SEG 3 4 5 6 8 9 additional information WhentheSEG3issetas 1 andfollowAutoChangeOverforHRonlyoperation itwilloperateasfollows Cooling HeatingmodecanbechangedwhenThermoOffstatusismaintainedduringthetimewithSEG9 A SetwithSEG4 C B SetwithSEG5 C C SetwithSEG6 C D S...
Page 31: ...low the steps below After finishing the installation of the air conditioner you should explain the fol lowing to the user Refer to appropriate pages in the User s Manual 1 How to start and stop the air conditioner 2 How to select the modes and functions 3 How to adjust the temperature and fan speed 4 How to adjust the airflow direction 5 How to set the timers 6 How to clean and replace the filters...
Page 32: ... error received from the outdoor unit 3 3 miniute tracking error on outdoor unit 4 Communication error after tracking due to unmatching number of installed units 5 Error due to repeated communication address 6 Communication address not confirmed Other outdoor unit communication error that is not on the above list E101 E102 E202 E201 E108 E109 Self diagnosis error display 1 Error due to opened EEV ...
Page 33: ...detection 6 Indoor operation stop due to unconfirmed error on outdoor unit 7 Error due to reverse phase detection 8 Comp stop due to freeze detection 6th detection 9 High pressure sensor is detached 10 Low pressure sensor is detached 11 Outdoor unit copression ration error 12 Outdoor sump down_1 prevetion control 13 Compressor down due to low pressure sensor prevention control_1 14 Simultaneous op...
Page 34: ...E 33 ENGLISH MEMO 미주향_DVMS_1Way Cassette_IM_EN_03806A 1 indd 33 2013 03 06 오후 5 58 38 ...