Installation Procedure
English
Instal
lation Pr
oc
edur
e
3
Finish wrapping insulating tape around the rest of the
pipes leading to the outdoor unit.
4
Install a green/yellow colored earthing wire:
• If the earthing wire is too short, connect an
extension lead in a mechanical way and wrap it with
insulating tape (do not bury the connection).
• Secure the earthing wire in position with staples.
NOTE
• If the earthing electrode is installed in an area with
heavy traffic, its wire must be connected securely.
5
Carefully check the installation by measuring the
earthing resistance with a earth resistance tester. If
the resistance is above the required level, drive the
electrode deeper into the ground or increase the
number of earthing electrodes.
6
Connect the earthing wire to the electrical component
box inside of the outdoor unit.
Step 12 Setting an indoor unit address
and installation option
Setting the indoor unit addresses manually
1
Review all the following elements in the installation:
• Installation site strength
• Piping connection tightness to detect any gas
leakage
• Connection wiring
• Heat-resistant insulation of the piping
• Drainage
• Earthing wire connection
2
Manually set options in each room’s the indoor unit by
3
Press the K3 button once or reset the outdoor unit.
NOTE
• The Display 1/2 indications are the same as in the
automatic address setting mode.
Setting Key and Display of the outdoor unit
• Key option of the outdoor unit
‐
K1: Function button
- K3: Reset button
Key
Push
K1
K3
1
Pipe Checking Operation
Reset
2
Cool Mode Try run
3
Heat Mode Try run
4
Pump Down
5
Inverter Fault Detection (Comp#1) ¹⁾
6
Auto Mode Try run
7
Finish Key Operation
¹⁾ Indication on the display and action to take when an
inverter fault is detected
SEG1
SEG2
SEG3
SEG4
Action to
take
Fault
detection is
in progress
-
OK
-
NG
PBA
defect:
Replace
the PBA
Check
Manual
inspection
is required
Going
into fault
detection
mode failed
Try fault
detection
again
※
For more information of the Cool or Heat or Auto mode
Try run test, refer to page 31.