Samsung AC048KNPPCC Service Manual Download Page 1

AIR CONDITIONER

CONTENTS

FLOOR STAND TYPE AIR CONDITIONER

Basic :  

AF55JV1MAEE

Model :  

 AC048KNPPCC / AC048KXQPCC 

AC036KNPPCC / AC036KXQPCC 

AC140KNPDEH / AC140KXADGH 

AC100KNPDEH / AC100KXADEH 

AC048KNPDEC / AC048KXADGC 

AC036KNPDEC / AC036KXADEC

Model Code :    AC048KNPPCC/MG AC048KXQPCC/MG 

AC036KNPPCC/MG AC036KXQPCC/MG 

AC140KNPDEH/EU AC140KXADGH/EU 

AC100KNPDEH/EU AC100KXADEH/EU 

AC048KNPDEC/TL  AC048KXADGC/TL 

AC036KNPDEC/TL  AC036KXADEC/TL 

AC036KNPDEC/SV AC036KXADEC/SV

1.  Precautions

2.  Product Specifications

3.  Disassembly and Reassembly

4.  Troubleshooting

5.  PCB Diagram

6.  Wiring Diagram

7.  Reference Sheet

AC048KXQPCC

AC036KXQPCC

AC140KXADGH

AC048KXADGC

AC048KNPPCC

AC036KNPPCC

AC140KNPDEH

AC100KNPDEH

AC048KNPDEC

AC036KNPDEC

AC100KXADEH

AC036KXADEC

Summary of Contents for AC048KNPPCC

Page 1: ...MG AC036KNPPCC MG AC036KXQPCC MG AC140KNPDEH EU AC140KXADGH EU AC100KNPDEH EU AC100KXADEH EU AC048KNPDEC TL AC048KXADGC TL AC036KNPDEC TL AC036KXADEC TL AC036KNPDEC SV AC036KXADEC SV 1 Precautions 2 Product Specifications 3 Disassembly and Reassembly 4 Troubleshooting 5 PCB Diagram 6 Wiring Diagram 7 Reference Sheet AC048KXQPCC AC036KXQPCC AC140KXADGH AC048KXADGC AC048KNPPCC AC036KNPPCC AC140KNPDE...

Page 2: ...ting 4 1 4 2 Outdoor Trouble shooting 4 2 4 3 Troubleshooting by symptoms 4 5 4 3 1 Communication error after finishing tracking E202 4 5 4 3 2 Outdoor s service valve Clog 4 6 4 3 3 No Power completely dead Initial diagnosis 4 7 4 3 4 E102 Communication error between indoor and outdoor unit E201 Unit quantity miss matching beween Indoor and Outdoor E202 Abnormal state no communication between Ind...

Page 3: ...voltage Low voltage error 4 21 4 3 15 Pipe Blocking Error Error Code E422 4 22 4 3 16 The others 4 23 4 3 17 Setting an indoor unit installation option 4 24 5 PCB Diagram 5 1 5 1 Indoor unit 5 1 5 1 1 Main PCB 5 1 5 1 2 Power PCB 5 3 5 1 3 Panel PCB 5 4 5 2 Outdoor unit 5 5 5 2 1 Main PCB Diagram 5 5 5 2 2 Inverter PCB 5 6 5 2 3 EMI PCB 5 10 6 Wiring Diagram 6 1 6 1 Indoor unit 6 1 6 2 Outdoor uni...

Page 4: ...case any wire or power plug has been damaged replace it to eliminate any possible danger Do not bend the power cord by force and do not put any heavy object on the power cord There is a danger of electric shock or fire Do not use multi socket There is a danger of electric shock or fire Ground the product if necessary Be sure to ground the product if there is any danger of electric leakage due to w...

Page 5: ...xurious style boasts high quality interior design that fits naturally into any place Compact Remote Controller A small hand size remote control makes it even easier to use Long Piping Length Height It can give the benefit to the installers and aries the reliability of the air conditioner Long Ambient Operation In LowTemperature It can arise the reliability and the capacity of the air conditioner e...

Page 6: ...ed part Changed item and feature Basic After changed Indoor Unit Wi Fi Function added Outdoor Unit AC048KXQPCC AC036KXQPCC AC140KXADGH AC048KXADGC Inverter controller changed Outdoor Unit AC100KXADEH AC036KXADEC 2 1 2 Changes in comparison to basic model ...

Page 7: ...xD Indoor Unit mm 610 1850 400 610 1850 400 610 1850 400 610 1850 400 610 1850 400 610 1850 400 610 1850 400 Outdoor Unit mm 940 1420 330 940 1210 330 940 1210 330 940 998 330 940 1210 330 940 998 330 940 1420 330 Shipping Dimension WxHxD Indoor Unit mm 705 1963 493 705 1963 493 705 1963 493 705 1963 493 705 1963 493 705 1963 493 705 1963 493 Outdoor Unit mm 995 1597 426 995 1388 426 995 1388 426 ...

Page 8: ...rWashing Item Descriptions Code No Q ty Remark Manual AC048 036KNPPCC DB68 04872A 1 Indoor Unit Manual AC140 100KNPDEH DB68 06271A DB68 06272A 1 Manual AC048 036KNPDEC DB68 06270A 1 Wireless Remocon DB93 15883B 1 Battery DB47 90024A 2 Holder Remocon DB61 06087A 1 Rubber Cabi Hole DB73 00195A 1 InsulationTube DB62 10944A 1 Insulation AC048 036KN DB72 50300A 1 ...

Page 9: ...6 Item Descriptions Code No Q ty Remark Insulation AC140 100KN DB72 50300C 1 Indoor Unit HolderTop DB61 40042B 1 Screw L14 6002 000538 4 Screw L12 6002 000231 4 Rubber leg DB73 20134A 4 Outdoor Unit Drain Plug DB67 00806A 1 CAP Drain DB63 10355C 3 ...

Page 10: ...Samsung Electronics 3 1 Item Remark Screw driver Monkey spanner Necessary Tools 3 Disassembly and Reassembly ...

Page 11: ...and disconnect the main power supply 2 Ass y Inlet Part 1 Open the Ass y Inlet and remove the safety clips 3 Ass y Cover Control 1 Loosen one fixing screw of Ass y Cover Control Use Screw driver and detach the cover 2 Lift up the Ass y Cover Control and detach it by pulling the bottom outward 3 1 Indoor Unit ...

Page 12: ...the connectors connected to Panel Outlet and the Motor Connector Motor In Panel Horizontal blade Vertical blade 4 Ass y Panel outlet 1 Loosen the 7 fixing screws of Ass y Panel Outlet and detach the panel outlet by pushing upwards Use Screw driver Detaching direction Detaching direction ...

Page 13: ...rews of EVA 3 Loosen the grounding screw 4 Pull out the sensor cable 5 Pull out the Bracket Pipe upward 6 Pull the upper part of the Heat Exchanger toward you and lift up the Heat Exchanger to detach 6 Ass y Control In 1 Loosen the 1 fixing screw of Ass y Control 2 Loosen the EVA grounding fixing screw 3 Detach the Ass y Control In by pushing it to the right Detaching direction ...

Page 14: ...ure Remark 7 Ass y Blower 1 Loosen the 1 fixing screw of Guard Fan Use Screw driver 2 Push the Guard Fan in the arrow direction and detach the guard 3 Loosen the Blower nut clockwise and pull the Blower toward you and detach it Use a monkey spanner Detaching direction ...

Page 15: ...d detach the case Use Screw driver 2 Loosen the 3 fixing screws of Motor and ground fixing screw Use a monkey spanner Remove the connectors before detaching the Motor 9 CoverTop 1 Loosen the 3 fixing screws of Cover Top and detach the cover Use Screw driver Screw TH type2 M4 L10 BLK 2 Lift up the rear of Cover Top and detach it Detaching direction ...

Page 16: ...Remark 10 Ass y Panel Outlet 1 Panel Outlet 2 As you push the 2 hooks on each side of Panel outward detach the bottom part of Partition by lifting it toward you 3 Detach the wire positioned with HolderWire 4 Detach the wire positioned with HolderWire Rear side Front side ...

Page 17: ...emark 11 Ass y Panel outlet Seperate Display PBA 1 Loosen the 2 fixing screws of Case Display PBA and detach the case Use Screw driver 2 Unlink the fixing hook placed in the middle of Case Display PBA 3 Loosen the 2 fixing screws of PBA and detach the PBA Use Screw driver ...

Page 18: ...9 No Parts Procedure Remark 12 Ass y Panel outlet Motor Step 1 Loosen the 8 fixing screws of Holder Blade and detach the holder Use Screw driver 2 Loosen the 2 fixing screws of Step Motor and detach the motor Use Screw driver 3 The detached Step Motor ...

Page 19: ...o mounting screw in the Cabinet Front RH Use Screw Driver 2 Cabi Top 1 Unscrew and remove 9 screws on each side of the Cabinet Top Use Screw Driver 3 Cabi Install Front 1 Unscrew and remove 1 screw in the Cabinet Install Front Use Screw Driver 4 Guard Cond 1 Pull the sensor from Guard Cond 2 Unscrew and remove 4 screws in the Guard Cond Use Screw Driver ...

Page 20: ...nd remove 4 screws on each side of the Cabinet Back RH Use Screw Driver 6 Cabi Install Back 1 Unscrew and remove 1 screw in the Cabinet Install Back Use Screw Driver 7 Cabi Front LF 1 Unscrew and remove 10 screws in the Cabinet Front LF Use Screw Driver 8 Fan 1 Turn 2 mounting nuts as shown in the picture and remove it Use Adjustable Wrench ...

Page 21: ... Motor mounting screws Use Screw Driver 3 Disconnect the Motor wire From Ass y Control Out 10 Bracket Motor 1 Unscrew and remove 2 mounting screws in Bracket Motor Use Screw Driver 11 Control Out 1 Disconnect 4 Connecters From Ass y Control Out 2 Unscrew and remove 1 mounting screw in Control Out Use Screw Driver 3 Separate Ass y Control Out ...

Page 22: ...Valve Use Screw Driver 3 Separate the pipe from the Entrance Exit using a welder When removing the compres sor Heat Exchanger and Pipe purge the Coolant inside the Compressor completely and remove the pipe with a welding flame 13 Assy EEV Valve 1 Unscrew and remove 2 mounting screws in Service Valve Use Screw Driver 2 Separate the pipe from the Entrance Exit using a welder ...

Page 23: ... Check the connection wire Change the Fan motor Change the Main PCB BLDC Motor is used as Fan Motor therefore if you connect or disconnect the connector while the power is still on it may get damaged Make sure to turn off the power before performing any operation Operation OFF Operation OFF Operation OFF EEPROM ERROR Change PCB Operation OFF Operation OFF Operation OFF EEPROM Option Setting Error ...

Page 24: ...Open Thermal Fuse Open Check of indoor unit Terminal Block 10 E201 Communication error between indoor and outdoor unit Installation number setting error repeated indoor unit address indoor unit communication cable error Check indoor quantity setting in outdoor 11 E202 Communication error between indoor and outdoor unit Communication error on all indoor unit outdoor unit communication cable error C...

Page 25: ...52 Error due to ZCP detection circuit problem or power failure 42 E453 Error due to overheated motor of outdoor unit s Fan1 FAN1 error 43 E455 Error due to overheated IPM of Fan1 FAN1 error 44 E458 Fan speed error FAN1 ERROR 45 E461 Error due to operation failure of inverter compressor 46 E462 System stop due to full current control 47 E463 Over current trip PFC over current error Check OLP sensor...

Page 26: ...r 68 E499 Heat sink temperature sensor error of Fan1 FAN1 error 69 E500 IPM over heat error on inverter 1 Check Outdoor Inverter PBA 70 E508 Smart install is not installed 71 E554 Gas leak detected Check the refrigerant 72 E556 Error due to mismatching capacity of indoor and outdoor unit Check the indoor and Outdoor unit Capacity 73 E557 Option code miss matching among the indoor units only for DP...

Page 27: ...ollowing picture 0 7V 0 7V Good Bad Check the communication cable and replace the indoor unit PCB Remove the communication cable connecting the outdoor unit to indoor unit and measure the signal on LINE 2 of the outdoor unit with a scope Reconnect the cable connecting the outdoor unit to the indoor unit and restart the unit If the communication still doesn t work e h t e c a l p e r indoor unit PC...

Page 28: ...Wire remote controller display E422 Symptom Clogging of outdoor s service valve Failure Valve clog 4 3 9 Outdoor s service valve Clog No No Yes Yes Is the outdoor service valve clogged Was lacking in refrigerant Check the normal of EVA IN TEMP SENSOR Open the outdoor s service valve Refrigerant Charge ...

Page 29: ...ut power voltage of the indoor unit 220V 5 Is the wired remote controller connected correctly 2 Check procedure Yes Turn off the main power switch circuit break of power outlet and turn on again after 30 seconds Check the input power No Is the outdoor unit power supply L N 220V Yes Check the connection of the terminal block No Is the outdoor unit power voltage L N 220V Yes Replace the inverter PBA...

Page 30: ...oting 4 8 Samsung Electronics Samsung Electronics 4 17 Yes Outdoor unit is not powered on Initial diagnosis 1phase cont Yes Connect the reactor No Is the reactor connector connected correctly Replace the PBA Cont ...

Page 31: ...he input power Check connection of the outdoor unit terminal block Check the connection wires and connectors of the indoor and outdoor units Replace the PCB of the indoor unit if the PCB Transformer fuse pcd etc fails Replace the wired remote controller Turn off the main power switch circuit break of power outlet and turn on again after 30 seconds Is the outdoor unit power supply N R N S N T 220Va...

Page 32: ...iagnosis 3phase cont Yes Yes Reconfigure the option DIP switches Check the system depending on the error display No No Are the option DIP switches inside the wired remote controller configured correctly Is there an error message displayed on the wired remote controller display Check the target temperature Cont ...

Page 33: ...or E202 Abnormal state no communication between Indoor and Outdoor Main PCB E203 1min Time out of communication error Main Inverter 1 Checklist 1 Is the communication cable between the indoor unit and outdoor unit connected correctly 2 Isn t the power cable and communication cable wiring error 2 Troubleshooting procedure Yes Restart after power off Is the communication error occurred again Isn t t...

Page 34: ...ce No Is the temperature sensor measuring resistance similar to the table on the left After confirming the state is normal end the service No Yes Replace the outdoor unit PBA Power is on After confirming the state is normal end the service Example COND sensor outdoorunittemperaturesensormeasuringresistancevaluebytemperature E231 E221 Example OLPsensor dischargetemperaturesensormeasuringresistancev...

Page 35: ...tes normally The indoor EEV operates normally The indoor heat Exchanger sensor displays the temperature ok 4 3 13 E403 Freezing control causes comp down Outdoor unit display E403 Criteria All the operating indoor machines do not reach 4 C for more than five minutes Cause of problem Check if the indoor FAN MOTOR operates normally Check if the indoor EEV operates normally Check the indoor heat Excha...

Page 36: ...ine ex filter 4 3 14 E416 Dischage temperature sensor error Outdoor unit display E416 Criteria The compressor temperature above 110 C Cause of problem Insufficient coolant Clogging in the outdoor machine s solenoid valve Clogging in the sub valve Malfunctioning exhaust gas temp sensor Clogging in the pipeline and the filter Liquid EEV damaged 1 How to check Test operation Check the amount of coola...

Page 37: ...is above 30 C operation of the indoor heater with a remocon causes this error E441 The indoor machine remocon ON signal If the outside temperature is below 10 C before the AC runs this error occurs Causeofproblem OLP SENSOR temp above Trip_Dis 1 How to check The above malfunction codes do not indicate a malfunction of the product All you have to do is change the temperature suitably for the limits...

Page 38: ...locked 2 Is the sensor placed correctly 3 Does the both terminal of sensor satisfy the resistance value in accordance with temperature 4 Is the resistance value of sensor connection pull_up correct 2 Troubleshooting procedure Isn t the Fan locked Is the connector connected correctly Is the color of Fan wire matched correctly Remove the Fan lock Connect the connector Replace the Fan Replace the PCB...

Page 39: ... 2 Is the interphase resistance of compressor normal 2 Troubleshooting procedure Yes Restart after power off Is the restart error occurred again Is the interphase resistance value of compressor u v v w w u normal Is the connection cable for the compressor and power terminal normal Replace the PCB Terminate the service Replace the compressor Is the compressor body and interphase resistance insulate...

Page 40: ...rotection control causes comp down E484 PFC overload error Outdoor unit display E462 E484 Criteria The outdoor machine input current above I_Trip Causeofproblem Check the compressor input voltage error for low voltage Check the overcurrent option setting 1 How to check Overcurrent option setting ok Compressor input voltage supplied ok Check the input power terminal Correct the overcurrent setting ...

Page 41: ...Dis Causeofproblem See if the sub valve is open Check the amount of coolant Check the OLP sensor 1 How to check No No No No No Yes Yes Yes Check the amount of coolant The sensor s resistance normal Refer to E20 The outdoor indoor EEV operates normally All the sub valves open Clogging in the pipeline ex filter Test operation Replace the OLP sensor Connect S net to vacuum forceful Open the sub valve...

Page 42: ...s Yes No No No No No No Yes Yes Yes Does the compressor wire connected to the compressor normally Yes Yes Replace the compressor Reinstall and remove the obstruction Is the installation of outdoor unit good Reinstall and remove the obstruction Is the installation of indoor unit good Open valve screw to the end Are the service valves full opened Correct the compressor wire connection Is insuration ...

Page 43: ...center bar of M C and mesure the resis tance of each contact Yes No Replace M C Check and reconnecting the AC power cable wire Is the AC Power cable connection to the outdoor unit terminal block good Check and reconnecting the reactor wire at the TAB terminal Is the connection of reactor terminal good Replace the blown FUSE Are the FUSEs on EMI PCB blown Is each contact resistance normal less than...

Page 44: ...llowing order Check whether the pipe is empty and open all the service valves on the gas and liquid pipes Change and connect the pipes immediately and empty the pipes and then open the service valves Check the replacement of the EEV body coil and the refrigerant leaking part After that recharge Check the temperature value through S NET etc and then if there is a fault replace and reconnect No No N...

Page 45: ...ule orPFCMTemperaturesensorError E500 IPMisoverheated CheckIPMiswellassembledtoheatsink Checkwhetherinletportisclogged ChangeIPMifitisdefectiveone 5 E554 Gasleakerror Checkrefrigerantcharge CheckIndoorEVAsensor CheckServicevalveisopen Checkthepipesandwirescorrectlyconnected 6 E556 Capacitymissmatchbetweenindoorandoutdoor Checkthemodelnameofindoorandoutdoorunitandsetoptioncodeonindoorunitagain 7 Ou...

Page 46: ...he installation option according to the installation condition of an air conditioner The default setting of an indoor unit installation option is 02000 100000 200000 300000 4 Set the indoor unit option by wireless remote controller Heating setting compensation SEG21 is applied to Heat pump model only SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 0 2 RESERVED RESERVED RESERVED RESERVED SEG7 SEG8 SEG9 SEG10 SEG11 S...

Page 47: ...Samsung Electronics 5 1 5 PCB Diagram 5 1 Indoor unit 5 1 1 Main PCB This Document can not be used without Samsung s authorization 1 2 3 4 5 6 7 10 9 8 ...

Page 48: ... 1 DC 12V 2 ERROR_Check 3 DC 12V 4 Comp_Chec 1 GND 2 External control 1 DC 12V 2 GND 3 PANEL_TXD 4 PANEL_RXD 5 REMOCON_RXD 6 DC 5V 7 KEY_INT 1 GND 2 GND 3 SPI_Control 4 1 F1 2 F2 3 DC 12V 4 GND 5 F3 6 F4 1 DC 12V 2 UB_12B 3 UB_12A 4 UB_12B 5 UB_12A 1 DC 12V 2 UB_12B 3 UB_12A 4 UB_12B 5 UB_12A CN02 CTRL POWER FAN CN01 AC LOAD CN41 EVA IN ROOM CN81 ERROR COMP CN83 EXT_CTRL CN61 STEP UP DOWN CN903 DI...

Page 49: ... DC5V 4 BLDC_PS 5 FAN_PWM 6 RPM_FEEDBACK 7 ZEROCROSS 8 PWR_RY_12 9 INRUSH_RY_12 10 DETECT_OV LV CN71 POWER 1 L 2 NC 3 N 4 NC 5 EARTH CN501 BLDC MOTOR 1 DC310V 2 NC 3 AGND 4 DC15V 5 Vsp 6 RPM_FEEDBACK CN02 MAIN PBA 1 FAN_TURBO_4WAWY_12 2 FAN_HIGH_FAN_12 3 FAN_LOW_COMP_12 4 HEATER_CTRL_12A 5 HEATER_ZC CN72 AC LOAD 1 N 2 NC 3 COMPRESSOR 4 OUTDOORFANMOTOR 5 OUTDOOR4WAYV V ...

Page 50: ... 5 1 3 Panel PCB This Document can not be used without Samsung s authorization 2 1 3 CN903 DISPLAY 1 DC12V 2 GND 3 PANEL_TXD 4 PANEL_RXD 5 REMOCON_RXD 6 DC5V 7 KEY_INT CN31 DOWNLOAD MICOM 1 20 Download CN01 DOWNLOAD Touch IC 1 DC5V 2 GND 3 4 I2C 5 I2C ...

Page 51: ...PCB Diagram and Parts List Samsung Electronics 5 5 5 2 OUTDOOR 5 2 1 MAIN PCB Diagram 1 2 3 4 5 6 7 8 9 10 11 ...

Page 52: ...0 DOWNLOAD 1 4 EEV SIGNAL 5 6 DC 12V 1 7 EEPROM 1 COMM SIGNAL 2 COMM SIGNAL 3 GND 4 DC 5V 5 DC 12V 6 COMM SIGNAL 1 N C 2 SENSOR SIGNAL 3 GND 4 DC 5V 1 SENSOR SIGNAL 2 N C 3 GND 4 DC 5V 1 2 COMM SIGNAL 1 EARTH CN101 POWER CN702 4WAY CN403 SENSOR CN306 DOWNLOAD CN802 EEV CN806 EEPROM CN305 COMM INV CN401 LOW PRESSURE CN402 HIGH PREWSSURE CN303 COMM INDOOR CN103 EARTH ...

Page 53: ...NV 4 TDO_INV 5 TCK_INV 6 TDI_INV 7 TMS_INV 8 nTRST 9 GND 10 11 5V 14 18 19 ENC 17 GND 20 SUB 1 DC310V 2 N C 3 GND 4 DV15V 5 FAN RPM 6 FAN RPM Feedback 1 DC310V 2 N C 3 GND 4 DV15V 5 FAN RPM 6 FAN RPM Feedback 1 COMP U phase RED 2 COMP V phase BLU 3 COMP W phase YEL 1 L phase BRN 2 N phase SKY Reactor A1 B1 Reactor A2 B2 CN351 Communication CN551 Downloader CN901 FAN1 CN911 FAN2 CN401 COMP L N 220V...

Page 54: ...O_INV 5 TCK_INV 6 TDI_INV 7 TMS_INV 8 nTRST 9 GND 10 11 5V 14 18 19 ENC 17 GND 20 SUB 1 DC310V 2 N C 3 GND 4 DV15V 5 FAN RPM 6 FAN RPM Feedback 1 DC310V 2 N C 3 GND 4 DV15V 5 FAN RPM 6 FAN RPM Feedback CN401 COMP U phase RED CN402 COMP V phase BLU CN403 COMP W phase YEL 1 L phase BRN 2 N phase SKY Reactor A1 B1 Reactor A2 B2 CN351 Communication CN551 Downloader CN901 FAN1 CN911 FAN2 CN401 402 403 ...

Page 55: ... BOOT_INV 4 TDO_INV 5 TCK_INV 6 TDI_INV 7 TMS_INV 8 nTRST 9 GND 10 11 5V 14 18 19 ENC 17 GND 20 SUB 1 DC310V 2 N C 3 GND 4 DV15V 5 FAN RPM 6 FAN RPM Feedback 1 DC310V 2 N C 3 GND 4 DV15V 5 FAN RPM 6 FAN RPM Feedback 1 COMP U phase RED 2 COMP V phase BLU 3 COMP W phase YEL 1 2 Reactor RST AC Power 3 Phase CN152 AC Power CN351 Communication CN551 Downloader CN901 FAN1 CN911 FAN2 CN400 COMP CN101 Rea...

Page 56: ... Diagram and Parts List 5 10 Samsung Electronics AC048KXQPCC AC036KXQPCC AC100KXADEH AC036KXADEC L1 BRN N1 SKY BLU 1 3 AC 220 240V L1 AC POWER L phase N1 AC POWER N phase CN01 AC POWER 3 1 2 5 2 3 EMI PCB ...

Page 57: ...PCB Diagram and Parts List Samsung Electronics 5 11 AC140KXADGH AC048KXADGC R AC 380 400V WHT S AC 380 400V BRN T AC 380 400V BLK 1 3 AC 220 240V RST AC POWER 3phase CN100 AC POWER 2 1 ...

Page 58: ...Wiring Diagram Samsung Electronics 6 1 6 Wiring Diagram 6 1 Indoor Unit ...

Page 59: ...Wiring Diagram 6 2 Samsung Electronics 6 2 Outdoor unit AC048KXQPCC AC036KXQPCC AC100KXADEH AC036KXADEC This Document can not be used without Samsung s authorization ...

Page 60: ...Wiring Diagram Samsung Electronics 6 3 AC140KXADGH AC048KXADGC This Document can not be used without Samsung s authorization ...

Page 61: ...l Temp B Non Inv Side General Temp N Non Inv Side Low Temp R Non Inv Side Tropical Temp Z Non Inv Top Tropical Temp 1 1 In out 4Way 4 MSP Duct M Ceiling C ProductType Indoor Code Type F FLAGSHIP P PREMIUM D DELUXE S STANDARD ProductType Outdoor Code Type A STANDARD GENERAL Temp MODULE B STANDARD LOW Temp MODULE C STANDARD TROPICAL MODULE D STANDARD GENERAL Temp NON MODULE S STANDARD T DELUXE TROPI...

Page 62: ...LDC Sirocco C H 510 450 390 rpm Outdoor unit Heat Exchanger FMC 16mm 1R 69S 910 2EA FP1 4 Corrugate Fan Motor BLDC Propeller RPM MAX 800 rpm Indoor unit Heat Exchanger PFE 12mm 2X63X785 6 1PASS FP1 5 Louver Fan Motor BLDC Sirocco C H 430 390 370 rpm Outdoor unit Heat Exchanger PFC 16mm 1R 69S 910 2EA FP1 4 Corrugate Fan Motor BLDC Propeller RPM MAX 800 rpm ...

Page 63: ... 430 390 rpm Outdoor unit Heat Exchanger F T Φ7W 2R 66S 950 FP1 7 Louver Fan Motor BLDC Propeller RPM MAX 800 rpm AC100KXADEH Indoor unit Heat Exchanger PFE 8mm 2X63X785 6 1PASS FP1 5 Louver Fan Motor BLDC Sirocco C H 410 370 350 rpm Outdoor unit Heat Exchanger F T Φ7W 2R 46S 950 FP1 7 Louver Fan Motor BLDC Propeller RPM MAX 830 rpm ...

Page 64: ...440 390 rpm Outdoor unit Heat Exchanger F T Φ7W 2R 66S 950 FP1 7 Louver Fan Motor BLDC Propeller RPM MAX 800 rpm AC036KXADGC Indoor unit Heat Exchanger PFE 12mm 2X63X785 6 1PASS FP1 5 Louver Fan Motor BLDC Sirocco C H 410 370 350 rpm Outdoor unit Heat Exchanger F T Φ7W 2R 46S 950 FP1 7 Louver Fan Motor BLDC Propeller RPM MAX 830 rpm ...

Page 65: ...able International and or domestic law Samsung Electronics Co Ltd December 2017 Printed in Korea Code No AC 00163E_1 GSPN GLOBAL SERVICE PARTNER NETWORK Area Web Site Europe CIS Mideast Africa gspn1 samsungcsportal com Asia gspn2 samsungcsportal com North Latin America gspn3 samsungcsportal com China china samsungportal com ...