Troubleshooting
4-36
Samsung Electronics
4-3-12 Reverse phase / Loss phase detection (3-phase outdoor unit) (Error Code : E425 )
1. When power is on, it checks the power status used for 3-phase power compressor.
When the order of 3-phase L1(R) – L2(S) – L3(T) is changed (Reverse phase) or there is a phase that does not supply power (Loss phase), it
will display
and the air conditioner will stop operating.
1) Check the voltage on L1(R) – L2(S) phase/ L1(R) – L3(T) phase/ L2(S)
– L3(T) phase.
2) When there is any terminal that does not have normal voltage,
check the external power of the air conditioner and take
appropriate measures.
3) If 3-phase power is normal check the phase of the power wire using
3-phasetester. If it shows reverse phase, change the current power
wire connection.
4) After completing above, press reset key (K3) then check the power
again.
3-phase tester
Summary of Contents for AC026RN1DKG
Page 219: ...PCB Diagram and Parts List Samsung Electronics 5 11 AC026 035 052RNJDKG ...
Page 247: ...Wiring Diagram Samsung Electronics 6 9 Indoor Unit cont AC026 035 052RNJDKG ...
Page 248: ...Wiring Diagram 6 10 Samsung Electronics Indoor Unit cont AC100 120 140RNCDKG ...
Page 251: ...Wiring Diagram Samsung Electronics 6 13 Outdoor unit cont AC100 120 140RXADKG EU ...
Page 252: ...Wiring Diagram 6 14 Samsung Electronics Outdoor unit cont AC100 120 140RXADNG EU ...