26
Installation Procedure
English
Installation Pr
oc
edur
e
2
Set the installation options of indoor units, by referring to the following table and by following the steps in
Common
steps for setting the addresses and options
on page
19
.
• The installation options of indoor units are set to
020000-100001-200000-300000
by default.
• The SEG20 option, Individual control with remote control, allows you to control multiple indoor units individually
by using the remote control.
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Function
Page
Mode
Reserved
Use of external temperature
sensor
Use of central
control
Compensation of the fan RPM
Indication
and
details
Indication Details Indication
Details
Indication
Details
Indication Details Indication
Details
0
2
0
Disuse
0
Disuse
0
Disuse
1
Use
1
Use
1
RPM compensation
Option
SEG7
Ɗkߪࠋࣕ
SEG9
SEG10
SEG11
SEG12
Function
Page
Use of drain pump
Reserved
Reserved
Reserved
Dew removal operation in Wind-Free mode
Indication
and
details
Indication Details Indication
Details
Indication
Details
1
0
Disuse
0
Maintain blade status in Wind-
Free mode
1
Use
2
Use with 3 minute
delay
1
(Default)
Cooling operation by opening the blade
Option
SEG13
SEG14
SEG15
SEG16
SEG17
Ɗkߣߪࠌࣕ
Function
Page
Use of external control
Setting the output of external
control
Ionizer
Buzzer control
Maximum filter usage
time
Indication
and
details
Indication Details Indication
Details
Indication
Details
Indication Details Indication
Details
Indication Details
0
Disuse
Existing
Control
0
Thermo on
0
Disuse
0
Use of buzzer
2
1000
hours
1
On/Off control
2
off control
3
Window on/off control
4
Disuse
5
On/Off control
6
off control
7
Window on/off control
8
Disuse
Reverse
Control
1
Operation on
1
Use
1
Disuse of
buzzer
6
2000
hours
9
On/Off control
A
off control
B
Window on/off control
C
Disuse
D
On/Off control
E
off control
F
Window on/off control