background image

SINGLE

Technical 

Data Book

Wind-Free 4Way Cassette for America

(R410A, HP)

Model : 

Wind-Free 4Way Cassette (600x600) - CNH**NDB (AC***BNNDCH/AA), CXH**ADB (AC***BXADCH/AA)

               Wind-Free 4Way Cassette - CNH**4DB (AC***BN4DCH/AA), CXH**ADB (AC***BXADCH/AA)

Summary of Contents for AC009BNNDCH/AA

Page 1: ...Technical Data Book Wind Free 4Way Cassette forAmerica R410A HP Model Wind Free 4Way Cassette 600x600 CNH NDB AC BNNDCH AA CXH ADB AC BXADCH AA Wind Free 4Way Cassette CNH 4DB AC BN4DCH AA CXH ADB AC BXADCH AA ...

Page 2: ...Wind Free 4Way Cassette for North America 21 12 04 Ver 2 0 Updated the Max Heat Line up 21 12 28 Ver 2 1 Updated the format 22 02 22 Ver 2 2 Updated drain pipe spec 22 12 12 Ver 2 3 Modified data on specification page 23 02 24 Ver 2 4 Updated fresh air knockout note F A Knockout ...

Page 3: ...mption compared to non inverter air conditioners 200 300 400 500 600 Wh h Saving 302 Wh h 621 4 Wh h Non inverter Wind Free Cooling with Micro holes The Wind Free Air conditioner pushes air out through 15 000 micro holes in the panel producing a dispersed and gentle flow of air actually defined as still air and the key here is all of those holes create a still cooled air flow that infiltrates the ...

Page 4: ...to 50 and provide warmth in the freezing cold of 20 to ensure a constant and comfortable home environment Ideal comfort in minutes The CAC Single digital inverter air conditionerworks at maximum capacity at startup As soon as the temperature reaches the desired or set temperature CAC Single performs fine adjustments to cope with any changes This means less temperature fluctuation and ideal comfort...

Page 5: ... Way Cassette 600x600 4 4 Way Cassette 360 Cassette Wind Free 4 Way Cassette L LSP Duct H HSP Duct C Ceiling J Console A AR9500 Wall Mounted 5 2 Feature1 Outdoor Unit A Inv Side General Temp S Inv Side Low Temp Q Inv Side Tropical Temp F Inv Top Tropical Temp 6 Feature 7 Version B 2022 Model Name C 1 N 2 H 3 48 4 4 5 D 6 B 7 C Cooling Only H Heat Pump T MAX4 Wall Mounted Z Multi position AHU F Fla...

Page 6: ... Unit 5 Product Notation 6 Feature F Flagship S Standard D Deluxe P Premium 7 Rating Voltage C 1Φ 208 230V 60Hz 8 Mode B 2022 C Cooling Only H Heat Pump 1 1 Way Cassette N 4 Way Cassette 600x600 Wind Free 4 Way Cassette 600x600 4 4 Way Cassette 360 Cassette Wind Free 4 Way Cassette L LSP Duct H HSP Duct C Ceiling J Console A AR9500 Wall Mounted T MAX4 Wall Mounted Z Multi position AHU ...

Page 7: ...N Indoor Unit NASA X Outdoor Unit NASA 5 Feature1 A Inv Side General Temp S Inv Side Low Temp Q Inv Side Tropical Temp F Inv Top Tropical Temp 6 Feature2 7 Rating Voltage C 1Φ 208 230V 60Hz H 3Φ 400V 60Hz 8 Mode H Heat Pump R410A C Cooling Only R410A E Heat Pump R22 D Cooling Only R22 AC CAC B 2022 F Flagship S Standard D Deluxe P Premium C Deluxe Low Temp ...

Page 8: ... 48 Wind Free 4Way Cassette OutdoorUnit Model Capacity kBtu h 18 24 30 36 42 48 CXH ADB AC BXADCH AA Model Capacity kBtu h 9 12 18 Wind Free 4Way Cassette 600 x 600 Model Capacity kBtu h 9 12 18 1Phase Wind Free 4Way Cassette Wind Free 4Way Cassette 600x600 ...

Page 9: ... Contents Wind Free 4Way Cassette 26 Outdoor Units 50 Wind Free 4Way Cassette 600x600 10 Installation 73 ...

Page 10: ...on 12 2 Summary Table 14 3 Capacity Table 15 4 Dimensional Drawing 18 5 Center of Gravity 19 6 Electrical Wiring Diagram 20 7 Sound Data 21 8 Temperature and air flow distribution 23 Wind Free 4Way Cassette 600x600 ...

Page 11: ...efficient design and robust performance Wind Free 4Way Cassette 600 x 600 Tasteful design Compact Lightweight build Refine the interiorwith an elegant compact design The enhanced Samsung Wind Free 4Way Cassette 600 x 600 indoor air conditioner features a selection of simple panel patterns to blend seamlessly into any interior design Its uniquely lightweight frame blends effortlessly and beautifull...

Page 12: ... 0153FF 1930F9 272328 370000 0153FF 19345D 25343B 370000 020010 100001 200000 300000 020010 100001 200000 300000 020010 100001 200000 300000 Φ V Hz 1 2 208 230 60 1 2 208 230 60 1 2 208 230 60 Fin Tube Fin Tube Fin Tube Fin Al Al Al Tube Cu Cu Cu Green Hydrophile Green Hydrophile Green Hydrophile Turbo Turbo Turbo EA 1 1 1 m 3 min 8 0 7 0 6 0 9 2 8 0 6 4 10 5 9 5 8 5 ft min 283 247 212 325 283 226...

Page 13: ...x 14 61 35 94 x 24 49 x 14 61 40 28 x 34 69 x 16 26 Casing Material Body Steel Steel Steel 18 50 0 122 18 50 0 122 18 50 0 122 25 24 13 75 25 24 13 75 25 24 13 75 Operating Temp Cooling Heating Fan Motor Type Output Sound Sound Pressure Level External Dimension Net Weight Gross Weight Net Dimensions WxHxD Gross Dimensions WxHxD Output Oil Fan Type Discharge direction Quantity Air Flow Rate H M L A...

Page 14: ...0 High 371 371 39 56 Std 17 400 20 000 Mid 336 336 34 Min 5 500 3 300 Low 300 300 29 NOTE Sound data is based on cooling operation Electric Characteristics Model Outdoor Unit Input Current Amperes Power Supply Indoor Unit Outdoor Unit Rated Voltage range Outdoor Unit Indoor Unit Total MCA A MOP A Hz Volts Min Max Cooling Heating CNH09NDB AC009BNNDCH AA CXH09ADB AC009BXADCH AA 60 208 to 230 187 253...

Page 15: ...5 6 0 0 67 8 8 6 2 0 69 9 1 6 4 0 70 9 3 6 3 0 71 9 7 6 2 0 71 10 2 6 1 0 73 115 10 1 7 8 1 22 10 6 8 0 1 24 11 0 8 3 1 27 11 4 8 5 1 30 11 6 8 4 1 31 12 2 8 4 1 32 12 8 8 2 1 35 122 7 6 6 7 1 02 8 1 6 9 1 04 8 4 7 1 1 06 8 6 7 3 1 09 8 8 7 3 1 10 9 3 7 2 1 11 9 7 7 1 1 13 Outdoor Temp DB Indoor Temperature DB WB 68 57 72 61 77 64 80 67 82 70 86 72 90 75 TC PI TC PI TC PI TC PI TC PI TC PI MBH kW ...

Page 16: ... 10 5 7 3 0 84 10 8 7 6 0 86 11 0 7 5 0 87 11 6 7 4 0 88 12 1 7 3 0 89 115 10 5 8 1 1 30 11 1 8 4 1 32 11 5 8 6 1 35 11 9 8 9 1 38 12 1 8 8 1 39 12 7 8 7 1 40 13 4 8 6 1 43 122 8 1 7 1 1 09 8 5 7 3 1 12 8 9 7 6 1 14 9 2 7 8 1 16 9 4 7 7 1 17 9 8 7 6 1 18 10 3 7 5 1 21 Outdoor Temp DB Indoor Temperature DB WB 68 57 72 61 77 64 80 67 82 70 86 72 90 75 TC PI TC PI TC PI TC PI TC PI TC PI MBH kW MBH k...

Page 17: ...1 55 17 4 12 2 1 58 17 7 12 1 1 60 18 6 11 9 1 61 19 6 11 7 1 64 115 16 9 13 5 2 97 17 8 13 9 3 03 18 6 14 3 3 10 19 1 14 7 3 16 19 5 14 6 3 19 20 5 14 4 3 22 21 5 14 2 3 29 122 13 9 11 4 2 60 14 6 11 8 2 66 15 2 12 2 2 71 15 7 12 5 2 77 16 0 12 4 2 79 16 8 12 3 2 82 17 6 12 0 2 88 Outdoor Temp DB Indoor Temperature DB WB 68 57 72 61 77 64 80 67 82 70 86 72 90 75 TC PI TC PI TC PI TC PI TC PI TC P...

Page 18: ...8 620 24 3 8 381 15 66 2 5 8 Adjustable until 550mm 165 225 51 140 188 207 249 269 212 8 5 16 5 6 3 4 22 5 8 5 15 16 250 M4 Screw 11 13 16 5 7 16 8 7 8 3 1 2 4 6 1 2 9 13 16 Adjustable until 21 5 16 inches 9 1 4 7 3 16 12 5 16 9 13 16 2 5 1 2 7 3 8 8 1 8 10 9 16 Ceiling opening Ceiling opening No Name Description CNH09 12NDB AC009 012BNNDCH AA CNH18NDB AC018BNNDCH AA 1 Liquid pipe connection Φ 6 3...

Page 19: ...5 Centerof Gravity 5 Centerof Gravity Units mm inches Wind Free 4Way Cassette 600x600 620 24 3 8 295 11 5 8 145 5 11 16 266 10 7 16 620 24 3 8 320 12 5 16 ...

Page 20: ...N 10K EXT_CONTROL EXTERNAL_CONTROL EVA OUT 10K Thermistor EVA OUT 10K NOTE This wiring diagram applies only to the Indoor unit Symbols show as follow blk black red red blu blue wht white yel yellow brn brown sky skyblue grn green For connection wiring indoor outdoor transmission F1 F2 indoor wired remote controller transmission F3 F4 Protective earth screw connector The wire quantity Wind Free 4Wa...

Page 21: ...nd pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure level Reference acoustic pressure 0 dB 20μPa Wind Free 4Way Cassette 600x600 Model High Mid CNH09NDB AC009BNNDCH AA 31 28 CNH12NDB AC012BNNDCH AA 34 30 CNH18NDB AC...

Page 22: ...ower level is an absolute value that a sound source generates dBA A weighted sound power level Reference power 1pW Measured according to ISO 3741 Unit dB A Model Cooling CNH09NDB AC009BNNDCH AA 48 CNH12NDB AC012BNNDCH AA 51 CNH18NDB AC018BNNDCH AA 56 2 CNH12NDB AC012BNNDCH AA NC Curve 1 CNH09NDB AC009BNNDCH AA 3 CNH18NDB AC018BNNDCH AA ...

Page 23: ...DB AC009BNNDCH AA Cooling AirVelocity distribution Discharge angle 41 degree Cooling temperature distribution Discharge angle 41 degree Heating AirVelocity distribution Discharge angle 56 degree Heating temperature distribution Discharge angle 56 degree Wind Free 4Way Cassette 600x600 ...

Page 24: ...00x600 CNH12NDB AC012BNNDCH AA Cooling AirVelocity distribution Discharge angle 41 degree Cooling temperature distribution Discharge angle 41 degree Heating AirVelocity distribution Discharge angle 56 degree Heating temperature distribution Discharge angle 56 degree ...

Page 25: ...00x600 CNH18NDB AC018BNNDCH AA Cooling AirVelocity distribution Discharge angle 41 degree Cooling temperature distribution Discharge angle 41 degree Heating AirVelocity distribution Discharge angle 56 degree Heating temperature distribution Discharge angle 56 degree ...

Page 26: ...e 4Way Cassette 1 Specification 28 2 Summary Table 34 3 Capacity Table 35 4 Dimensional Drawing 43 5 Center of Gravity 45 6 Electrical Wiring Diagram 46 7 Sound Data 47 8 Temperature and air flow distribution 51 ...

Page 27: ...ation Ease installation and minimize maintenance with a detachable no drip design Wind Free 4Way Cassette Stylishly clean design Aesthetic panel and display Wind Free 4Way Cassette offers two different pattern designs for the panel The simple display design with rounded corners adds a chic sophistication to the interior Power Defrost Time Clean Neat and clean design The indoorWind Free 4Way Casset...

Page 28: ...370020 0143FF 195418 275A5E 370040 020010 100001 200000 300000 020010 100001 200000 300000 020010 100001 200000 300000 Φ V Hz 1 2 208 230 60 1 2 208 230 60 1 2 208 230 60 Fin Tube Fin Tube Fin Tube Fin Al Al Al Tube Cu Cu Cu Green Hydrophile Green Hydrophile Green Hydrophile Turbo Turbo Turbo EA 1 1 1 m 3 min 24 0 21 0 18 0 24 0 21 0 18 0 28 2 23 6 17 8 ft min 848 742 636 848 742 636 996 833 629 l...

Page 29: ... 28 x 34 69 x 16 26 39 17 x 43 15 x 16 77 39 17 x 43 15 x 16 77 Casing Material Body Steel Steel Steel 18 50 0 122 18 50 0 122 18 50 0 122 25 24 13 75 25 24 13 75 20 24 4 75 Model Name Indoor Unit Outdoor Unit US Code Indoor Unit Outdoor Unit Gross Dimensions WxHxD Control System Infrared remote control Wired remote control Drain Pump Drain Pump Max lifting Height Displacement Indoor Unit Material...

Page 30: ...0143FF 19548C 278C9B 370040 020010 100001 200000 300000 020010 100001 200000 300000 020010 100001 200000 300000 Φ V Hz 1 2 208 230 60 1 2 208 230 60 1 2 208 230 60 Fin Tube Fin Tube Fin Tube Fin Al Al Al Tube Cu Cu Cu Green Hydrophile Green Hydrophile Green Hydrophile Turbo 3D Turbo 3D Turbo 3D EA 1 1 1 m 3 min 34 2 25 8 19 0 35 3 27 0 20 1 36 5 28 2 21 2 ft min 1208 911 671 1247 954 710 1289 996 ...

Page 31: ... 39 17 x 54 65 x 16 77 39 17 x 54 65 x 16 77 39 17 x 54 65 x 16 77 Casing Material Body Steel Steel Steel 18 50 0 122 18 50 0 122 18 50 0 122 20 24 4 75 20 24 4 75 20 24 4 75 Model Name Indoor Unit Outdoor Unit Net Weight Gross Weight Net Dimensions WxHxD Gross Dimensions WxHxD Control System Infrared remote control Wired remote control US Code Indoor Unit Outdoor Unit Indoor Unit Material Panel M...

Page 32: ...6 Min 12 000 13 000 Low 749 749 NOTE Sound data is based on cooling operation Electric Characteristics Model Outdoor Unit Input Current Amperes Power Supply Indoor Unit Outdoor Unit Rated Voltage range Outdoor Unit Indoor Unit Total MCA A MOP A Hz Volts Min Max Cooling Heating CNH184DB AC018BN4DCH AA CXH18ADB AC018BXADCH AA 60 208 to 230 187 253 20 1 25 CNH244DB AC024BN4DCH AA CXH24ADB AC024BXADCH...

Page 33: ...2 2 1 27 18 0 12 6 1 30 18 4 12 5 1 31 19 3 12 3 1 33 20 2 12 1 1 35 115 16 2 12 1 2 02 17 1 12 4 2 06 17 8 12 8 2 10 18 4 13 2 2 15 18 7 13 1 2 17 19 7 13 0 2 19 20 6 12 7 2 23 122 14 3 11 8 1 96 15 1 12 2 2 00 15 7 12 6 2 04 16 2 13 0 2 08 16 5 12 8 2 10 17 4 12 7 2 12 18 2 12 4 2 16 Outdoor Temp DB Indoor Temperature DB WB 68 57 72 61 77 64 80 67 82 70 86 72 90 75 TC PI TC PI TC PI TC PI TC PI ...

Page 34: ... 24 0 16 8 1 90 24 5 16 6 1 92 25 7 16 5 1 94 27 0 16 1 1 98 115 21 7 17 9 3 13 22 8 18 4 3 19 23 7 19 0 3 26 24 5 19 6 3 33 25 0 19 4 3 36 26 2 19 2 3 39 27 5 18 8 3 46 122 18 0 15 8 2 77 19 0 16 3 2 83 19 8 16 8 2 89 20 4 17 3 2 95 20 8 17 2 2 97 21 8 17 0 3 00 22 9 16 7 3 06 Outdoor Temp DB Indoor Temperature DB WB 68 57 72 61 77 64 80 67 82 70 86 72 90 75 TC PI TC PI TC PI TC PI TC PI TC PI MB...

Page 35: ...7 27 9 19 8 2 62 29 1 20 4 2 68 30 0 21 0 2 73 30 6 20 8 2 76 32 1 20 6 2 78 33 7 20 2 2 84 115 23 9 19 7 3 34 25 1 20 3 3 41 26 2 21 0 3 48 27 0 21 6 3 55 27 5 21 4 3 58 28 9 21 2 3 62 30 4 20 7 3 69 122 19 9 17 5 2 95 21 0 18 0 3 02 21 8 18 6 3 08 22 5 19 1 3 14 23 0 18 9 3 17 24 1 18 7 3 20 25 3 18 4 3 27 Outdoor Temp DB Indoor Temperature DB WB 68 57 72 61 77 64 80 67 82 70 86 72 90 75 TC PI T...

Page 36: ...5 33 5 23 7 3 01 34 9 24 4 3 07 36 0 25 2 3 13 36 7 24 9 3 16 38 6 24 7 3 19 40 5 24 2 3 26 115 28 7 23 7 3 54 30 2 24 4 3 61 31 4 25 1 3 68 32 4 25 9 3 76 33 0 25 7 3 79 34 7 25 4 3 83 36 4 24 9 3 91 122 23 9 20 9 2 65 25 1 21 6 2 71 26 2 22 3 2 76 27 0 23 0 2 82 27 5 22 7 2 85 28 9 22 5 2 87 30 4 22 0 2 93 Outdoor Temp DB Indoor Temperature DB WB 68 57 72 61 77 64 80 67 82 70 86 72 90 75 TC PI T...

Page 37: ...5 39 1 27 7 4 03 40 7 28 5 4 12 42 0 29 4 4 20 42 8 29 1 4 24 45 0 28 8 4 28 47 2 28 2 4 37 115 31 6 26 1 4 35 33 2 26 9 4 44 34 6 27 7 4 53 35 7 28 6 4 62 36 4 28 3 4 67 38 2 28 0 4 71 40 1 27 4 4 81 122 26 0 22 8 3 36 27 4 23 5 3 43 28 5 24 2 3 50 29 4 25 0 3 57 30 0 24 7 3 61 31 5 24 5 3 64 33 1 24 0 3 71 Outdoor Temp DB Indoor Temperature DB WB 68 57 72 61 77 64 80 67 82 70 86 72 90 75 TC PI T...

Page 38: ...4 44 7 31 6 5 55 46 6 32 6 5 66 48 0 33 6 5 78 49 0 33 3 5 84 51 4 32 9 5 90 54 0 32 3 6 01 115 34 0 28 0 5 17 35 8 28 9 5 27 37 2 29 8 5 38 38 4 30 7 5 49 39 2 30 4 5 55 41 1 30 1 5 60 43 2 29 5 5 71 122 27 6 24 2 4 35 29 1 25 0 4 44 30 3 25 7 4 53 31 2 26 5 4 62 31 8 26 3 4 67 33 4 26 0 4 72 35 1 25 5 4 81 Outdoor Temp DB Indoor Temperature DB WB 68 57 72 61 77 64 80 67 82 70 86 72 90 75 TC PI T...

Page 39: ...tion CNH184DB AC018BN4DCH AA CNH244DB AC024BN4DCH AA 1 Liquid pipe connection Φ 6 35mm 1 4 2 Gas pipe connection Φ 12 7mm 1 2 Φ 15 88mm 5 8 3 Drain pipe connection 3 4 OD 26 67 1 05 4 Power supply Communication wiring conduit 5 Fresh air intake knockout hole Φ101mm 4 Use M4 Screw NOTE As for suspension bolt please use M8 M10 Procured at local site ...

Page 40: ...es No Name Description 1 Liquid pipe connection Φ 9 52mm 3 8 2 Gas pipe connection Φ 15 88mm 5 8 3 Drain pipe connection 3 4 OD 26 67 mm 1 05 4 Power supply Communication wiring conduit 5 Fresh air intake knockout hole Φ101mm 4 Use M4 Screw NOTE As for suspension bolt please use M8 M10 Procured at local site Wind Free 4Way Cassette ...

Page 41: ...e 4Way Cassette 5 Centerof Gravity 5 Centerof Gravity Units mm inches 890 910 35 1 16 35 13 16 890 910 35 1 16 35 13 16 445 17 1 2 445 17 1 2 A B A B 24kBtu h 30 48kBtu h 305 12 130 5 1 8 265 10 7 16 114 4 1 2 ...

Page 42: ...VA IN 10K EXT_CONTROL EXTERNAL_CONTROL EVA OUT 10K Thermistor EVA OUT 10K NOTE This wiring diagram applies only to the Indoor unit Symbols show as follow blk black red red blu blue wht white yel yellow brn brown sky skyblue grn green For connection wiring indoor outdoor transmission F1 F2 indoor wired remote controller transmission F3 F4 Protective earth screw connector The wire quantity Wind Free...

Page 43: ...without prior notice Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure level Reference acoustic pressure 0 dB 20μPa Model High Mid CNH184DB AC018BN4DCH AA 36 33 CNH244DB AC024BN4DCH AA 36 33 CNH304DB AC030BN4DC...

Page 44: ...und pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure level Reference acoustic pressure 0 dB 20μPa Model High Mid CNH424DB AC042BN4DCH AA CNH484DB AC048BN4DCH AA Low Wind Free 4Way Cassette 44 40 45 40 34 35 ...

Page 45: ...te value that a sound source generates dBA A weighted sound power level Reference power 1pW Measured according to ISO 3741 Unit dB A Model Cooling CNH184DB AC018BN4DCH AA 53 CNH244DB AC024BN4DCH AA CNH304DB AC030BN4DCH AA 2 CNH244DB AC024BN4DCH AA NC Curve 1 CNH184DB AC018BN4DCH AA 3 CNH304DB AC030BN4DCH AA 4 CNH364DB AC036BN4DCH AA CNH364DB AC036BN4DCH AA 53 53 59 ...

Page 46: ...t prior notice Sound power level is an absolute value that a sound source generates dBA A weighted sound power level Reference power 1pW Measured according to ISO 3741 Unit dB A Model Cooling CNH424DB AC042BN4DCH AA CNH484DB AC048BN4DCH AA 6 CNH484DB AC048BN4DCH AA NC Curve 5 CNH424DB AC042BN4DCH AA 60 61 ...

Page 47: ... degree Discharge angle 45 degree Heating AirVelocity distribution Heating temperature distribution Discharge angle 52 degree Discharge angle 52 degree CNH244DB AC024BN4DCH AA Cooling AirVelocity distribution Cooling temperature distribution Discharge angle 45 degree Discharge angle 45 degree Heating AirVelocity distribution Heating temperature distribution Discharge angle 52 degree Discharge angl...

Page 48: ...irVelocity distribution Heating temperature distribution Discharge angle 52 degree Discharge angle 52 degree CNH364DB AC036BN4DCH AA Cooling AirVelocity distribution Cooling temperature distribution Discharge angle 45 degree Discharge angle 45 degree Heating AirVelocity distribution Heating temperature distribution Discharge angle 52 degree Discharge angle 52 degree Wind Free 4Way Cassette ...

Page 49: ...ngle 45 degree Heating AirVelocity distribution Heating temperature distribution Discharge angle 52 degree Discharge angle 52 degree CNH484DB AC048BN4DCH AA Cooling AirVelocity distribution Cooling temperature distribution Discharge angle 45 degree Discharge angle 45 degree Heating AirVelocity distribution Heating temperature distribution Discharge angle 52 degree Discharge angle 52 degree ...

Page 50: ... 1 Summary Table 55 2 Dimensional Drawing 56 3 Center of Gravity 61 4 Electrical Wiring Diagram 64 5 Sound Data 67 6 Capacity Correction 73 7 Operation Range 77 8 Piping Diagram 78 OutdoorUnits ...

Page 51: ...000 CXH12ADB AC012BXADCH AA 31 10 x 21 57 x 11 22 74 3 1 059 47 48 61 18 000 CXH18ADB AC018BXADCH AA 34 65 x 31 42 x 12 20 118 4 2 154 48 48 62 24 000 CXH24ADB AC024BXADCH AA 37 01 x 39 29 x 12 99 158 7 2 684 50 52 30 000 CXH30ADB AC030BXADCH AA 37 01 x 39 29 x 12 99 158 7 2 684 50 52 36 000 CXH36ADB AC036BXADCH AA 37 01 x 47 64 x 12 99 189 6 3 532 52 54 42 000 CXH42ADB AC042BXADCH AA 37 01 x 47 6...

Page 52: ...Dimensional Drawing CXH09ADB AC009BXADCH AA CXH12ADB AC012BXADCH AA Units mm inches OutdoorUnits No Name Description 1 Refrigerant gas pipe Φ 9 52mm 3 8 2 Refrigerant liquid pipe Φ 6 35mm 1 4 3 Drain Hole ...

Page 53: ...OutdoorUnits CXH18ADB AC018BXADCH AA Units mm inches No Name Description 1 Refrigerant liquid pipe Φ 12 7mm 1 2 2 Refrigerant gas pipe Φ 6 35mm 1 4 3 Drain hole 2 Dimensional Drawing ...

Page 54: ...ut hole Front Side Rear Bottom 4 Powerwiring conduit 5 Communication wiring conduit 6 Drain Hole CXH24ADB AC024BXADCH AA CXH30ADB AC030BXADCH AA CXH24ADB AC024BXADCH AA CXH30ADB AC030BXADCH AA OutdoorUnits Φ 9 52mm 3 8 Φ 15 88mm 5 8 Front Side Rear Φ 34mm 1 3 8 Front Side Rear Φ 22mm 7 8 Connectwiththeprovideddrainplugifapplicable Φ 6 35mm 1 4 22 7 8 ...

Page 55: ...tion 1 Refrigerant liquid pipe 2 Refrigerant gas pipe 3 Piping intake knockout hole Front Side Rear Bottom 4 Powerwiring conduit 5 Communication wiring conduit 6 Drain Hole Connect with the provided drain plug if applicable OutdoorUnits Φ 9 52mm 3 8 Φ 15 88mm 5 8 Front Side Rear Φ 34mm 1 3 8 Front Side Rear Φ 22mm 7 8 22 7 8 ...

Page 56: ...3 3 C Cent enter erof Gr of Gra avity vity OutdoorUnits CXH09ADB AC009BXADCH AA CXH12ADB AC012BXADCH AA Units mm inches CXH18ADB AC018BXADCH AA Units mm inches ...

Page 57: ...3 Centerof Gravity OutdoorUnits CXH24ADB AC024BXADCH AA CXH30ADB AC030BXADCH AA Units mm inches Units mm inches CXH36ADB AC036BXADCH AA CXH42ADB AC042BXADCH AA CXH48ADB AC048BXADCH AA ...

Page 58: ...ndoor outdoor transmission F1 F2 outdoor outdoor transmission OF1 OF2 refer to the installation manual Protective earth screw connector The wire quantity CXH09ADB AC009BXADCH AA CXH12ADB AC012BXADCH AA OutdoorUnits MAIN PCB Printed circuit board MAIN EEV Electronic Expansion Valve INVERTER PCB Printed circuit board INVERTER M BLDC BLDC Motor OLT TH 200K Thermistor OLP DIS TH 200K Thermistor DISCHA...

Page 59: ...evice High Pressure switch For connection wiring indoor outdoor transmission F1 F2 outdoor outdoor transmission OF1 OF2 refer to the installation manual Protective earth screw connector The wire quantity OutdoorUnits MAIN PCB Printed circuit board MAIN EEV Electronic Expansion Valve INVERTER PCB Printed circuit board INVERTER M BLDC BLDC Motor OLT TH 200K Thermistor OLP DIS TH 200K Thermistor DISC...

Page 60: ...t shortcircuit the protection device High Pressure switch For connection wiring indoor outdoor transmission F1 F2 outdoor outdoor transmission OF1 OF2 refer to the installation manual Protective earth screw connector The wire quantity MAIN PCB Printed circuit board MAIN EEV Electronic Expansion Valve INVERTER PCB Printed circuit board INVERTER M BLDC BLDC Motor OLT TH 200K Thermistor OLP DIS TH 20...

Page 61: ... NC Curve 1 CXH09ADB AC009BXADCH AA 3 CXH18ADB AC018BXADCH AA 4 CXH24ADB AC024BXADCH AA NOTE Specifications may be subject to change without prior notice Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure level ...

Page 62: ... pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound pressure level Reference acoustic pressure 0 dB 20μPa Model Cooling Heating CXH30ADB AC030BXADCH AA 50 52 CXH36ADB AC036BXADCH AA 52 54 CXH42ADB AC042BXADCH AA 53 55 CXH48ADB...

Page 63: ...ue that a sound source generates dBA A weighted sound power level Reference power 1pW Measured according to ISO 3741 Unit dB A Model Cooling CXH09ADB AC009BXADCH AA 59 CXH12ADB AC012BXADCH AA CXH18ADB AC018BXADCH AA 2 CXH12ADB AC012BXADCH AA NC Curve 1 CXH09ADB AC009BXADCH AA 3 CXH18ADB AC018BXADCH AA 4 CXH24ADB AC024BXADCH AA CXH24ADB AC024BXADCH AA 61 62 65 ...

Page 64: ...ue that a sound source generates dBA A weighted sound power level Reference power 1pW Measured according to ISO 3741 Unit dB A Model Cooling CXH30ADB AC030BXADCH AA CXH36ADB AC036BXADCH AA CXH42ADB AC042BXADCH AA 2 CXH36ADB AC036BXADCH AA NC Curve 1 CXH30ADB AC030BXADCH AA 3 CXH42ADB AC042BXADCH AA 4 CXH48ADB AC048BXADCH AA CXH48ADB AC048BXADCH AA 67 69 70 72 ...

Page 65: ... 49 2 0 93 32 8 0 93 16 4 1 00 0 93 0 0 1 00 0 93 16 4 1 00 0 98 0 95 0 93 32 8 0 97 0 95 0 93 0 92 49 2 0 94 0 91 Heating 0 95 0 98 0 98 0 95 0 95 0 95 Pipe Length ft 24 6 32 8 49 2 65 6 Level Difference ft 49 2 0 91 32 8 0 91 16 4 1 00 0 91 0 0 1 00 0 91 16 4 1 00 0 97 0 94 0 91 32 8 0 97 0 94 0 94 0 91 49 2 0 94 0 91 0 97 0 97 0 97 0 94 0 94 0 94 6 Capacity Correction ...

Page 66: ...8 32 8 0 98 0 97 0 96 0 95 0 94 0 92 0 91 0 89 0 87 49 2 0 97 0 96 0 94 0 93 0 92 0 90 0 88 0 85 65 6 0 95 0 94 0 93 0 91 0 89 0 87 0 83 82 0 0 94 0 92 0 91 0 89 0 86 0 82 98 4 0 92 0 90 0 88 0 85 0 80 Heating Pipe Length ft 24 6 32 8 49 2 65 6 82 0 98 4 114 8 131 2 147 6 164 0 Level Difference ft 98 4 0 94 0 93 0 92 0 91 0 90 82 0 0 96 0 94 0 93 0 92 0 91 0 90 65 6 0 97 0 96 0 94 0 93 0 92 0 91 0...

Page 67: ... 0 89 0 88 0 86 0 84 0 80 Heating Pipe Length ft 16 4 32 8 49 2 65 6 82 0 98 4 114 8 131 2 147 6 164 0 180 4 196 9 213 3 229 7 246 1 Level Difference ft 98 4 0 96 0 95 0 94 0 93 0 92 0 91 0 91 0 90 0 89 0 88 82 0 0 97 0 96 0 95 0 94 0 93 0 92 0 91 0 91 0 90 0 89 0 88 65 6 0 97 0 97 0 96 0 95 0 94 0 93 0 92 0 91 0 91 0 90 0 89 0 88 49 2 0 98 0 97 0 97 0 96 0 95 0 94 0 93 0 92 0 91 0 91 0 90 0 89 0 ...

Page 68: ... 32 64 to 90 18 to 50 0 to 122 80 or less Drying 18 to 32 64 to 90 18 to 50 0 to 122 30 86 or less 25 to 24 13 to 75 NOTE The assumed installation conditions are follows The pipe length including elbow is 7 5m 24 6ft The level difference is 0 m Heating 20 to 24 4 to 75 24kBtu h 30 48kBtu h 80 or less CXH ADB AC BXADCH AA ...

Page 69: ...ronic Expansion Valve Main E_M Thermistor Discharge pipe T_D Thermistor Compressor Top T_CT Heat Exchanger Main Outdoor unit HX_M Thermistor IDU Heat Exchanger Mid T_IM Thermistor Ambient T_A Thermistor CondOut T_CO Solenoidvalve 4Way V_4W Thermistor IDU Heat Exchanger IN T_II Outdoor Fan Motor1 OFM1 Heat Exchanger Indoor unit HX_ID INDOOR UNIT OUTDOOR UNIT Thermistor Indoor Room T_IR Indoor Fan M...

Page 70: ...pansion Valve Main E_M Thermistor Discharge pipe T_D Thermistor Compressor Top T_CT Heat Exchanger Main Outdoor unit HX_M Thermistor IDU Heat Exchanger Mid T_IM Thermistor Ambient T_A Thermistor CondOut T_CO Solenoidvalve 4Way V_4W Thermistor IDU Heat Exchanger IN T_II Outdoor Fan Motor1 OFM1 Heat Exchanger Indoor unit HX_ID Accumulator AC INDOOR UNIT OUTDOOR UNIT Thermistor Indoor Room T_IR Indoo...

Page 71: ...pansion Valve Main E_M Thermistor Discharge pipe T_D Thermistor Compressor Top T_CT Heat Exchanger Main Outdoor unit HX_M Thermistor IDU Heat Exchanger Mid T_IM Thermistor Ambient T_A Thermistor CondOut T_CO Solenoidvalve 4Way V_4W Thermistor IDU Heat Exchanger IN T_II Outdoor Fan Motor1 OFM1 Heat Exchanger Indoor unit HX_ID Accumulator AC INDOOR UNIT OUTDOOR UNIT Thermistor Indoor Room T_IR Indoo...

Page 72: ... IDU Heat Exchanger Mid T_IM Thermistor Ambient T_A Thermistor CondOut T_CO Solenoidvalve 4Way V_4W Thermistor Indoor Room T_IR Indoor Fan Motor IFM Thermistor IDU Heat Exchanger IN T_II Outdoor Fan Motor1 OFM1 Heat Exchanger Indoor unit HX_ID Accumulator AC INDOOR UNIT CNH364DB AC036BN4DCH AA CXH36ADB AC036BXADCH AA CNH424DB AC042BN4DCH AA CXH42ADB AC042BXADCH AA CNH484DB AC048BN4DCH AA CXH48ADB ...

Page 73: ...lowing places A place with exposure to mineral oil oil vapour or cooking area where there is spray If oil adheres to the heat exchanger performance degradation spray or condensation scattering may occur If oil adheres to a plastic component the component may deform or get damaged Such issues may result in a system failure or refrigerant leak The place where corrosive gas such as sulphuric acid gas...

Page 74: ... an extra10 mm thick polyethylene insulation ora similartype of insulation to the body of the indoorunit Cut away the part where pipes are pulled out forthe insulating work 4 way Cassette B D A E C Insulate the end of the pipe and some curved area by using separate insulator NOTE A Reference forthe outer circumference of the unit When insulating the body of the indoor unit use A as the reference f...

Page 75: ...st the strength of each attached suspension bolt If the length of the suspension bolt is more than 4 92ft 1 5m vibration prevention is recommended If this is not possible create an opening on the false ceiling in orderto be able to use it to perform the required operations on the indoor unit 4 Screw eight nuts and washers to the suspension bolts making space for hanging the indoor unit CAUTION You...

Page 76: ...drain hose and drain pipe 1 Push the supplied drain hose as far as possible over the drain socket 2 Tighten the metal clamp as shown in the picture 3 Wrap the supplied large sealing pad overthe metal clamp and drain hose to insulate and fix it with clamps 4 Insulate the complete drain piping inside the building field supply If the drain hose cannot be sufficiently set on a slope fit the hose with ...

Page 77: ... the hose an upward gradient beyond the connection port This will cause waterto flow backwards when the unit is stopped resulting in water leaks Under gradient Ceiling Do not apply force to the piping on the unit side when connecting the drain hose The hose should not be allowed to hang loose from its connection to the unit Fasten the hose to a wall frame or other support as close to the unit as p...

Page 78: ...ain pipe To prevent waterfrom flowing back to indoorunits install an individual airvent at the top of each indoorunit The airvents should be T or 7 shaped to prevent dust orforeign substances from entering You may not need to install an airvent if the horizontal drain pipe has a proper slope Connecting the powerand communication cables Bushing bracket installation When connecting the powersupplywi...

Page 79: ...hrough the outdoor unit by means of a H05 RN F connection cable or a more power model with insulation in synthetic rubber and a jacket in polychloroprene neoprene in accordance with the requirements specified in the standard EN 60335 2 40 1 Remove the screw on the electrical component box and remove the cover plate 2 Route the connection cord through the side of the indoor unit and connect the cab...

Page 80: ...sten it with a clamp The unbalanced power must be maintained within10 of supply rating among whole indoor units If the power is unbalanced greatly it may shorten the life of the condenser If the unbalanced power is exceeded by more than10 of supply rating the indoor unit will protect itself by stopping and displaying an error code Connect the power cable to the auxiliary circuit breaker An all pol...

Page 81: ...rchased a system air conditioner and it has been installed byyour installation specialist This device must be installed according to the national electrical rules Ifyouroutdoorunitexceedsanetweightof132 2lb 60kg donotinstallitonasuspendedwall butstanditonafloor The reliability of our product cannot be guaranteed under conditions of A or less OutdoorModel A 13 25 AC030 036 042 048BXADCH 4 20 When i...

Page 82: ...etc based on the product condition When the product is to be shut down for a long period of time such as off peak hours take appropriate measures like covering the product If the product installed within1640 4 ft of seashore special anti corrosion treatment is required Please contact your local SAMSUNG representative forfurther details CAUTION In areas with heavy snow fall piled snow could block t...

Page 83: ...23 62 600 ormore 23 62 600 ormore 59 06 1500 or more 23 62 600 ormore 23 62 600 ormore 23 62 600 ormore 11 81 300 ormore 11 81 300 or more 11 81 300 ormore 11 81 300 ormore 19 69 500 or more 19 69 500 or more CAUTION The outdoor unit must be installed according to the specified distances in orderto permit accessibility from each side to guarantee correct operation maintenance and repair of the uni...

Page 84: ...one line cannot be used to ground the air conditioner 3 DIf the outdoor unit is exposed to strong winds install shield plates around the outdoor unit so that the fan can operate correctly NOTE Install provided rubberlegs to prevent vibration and noise AC018BXADCH Unit inch mm Anchorbolt hole 26 02 661 14 06 357 13 31 338 14 13 359 34 65 880 AC024 030 036 042 048BXADCH Unit inch mm Anchorbolt hole ...

Page 85: ...een the outdoor unit and the indoor unit CAUTION During installation make first the refrigerant connections and then the electrical connections If the unit is being removed first disconnect the electrical cables and then the refrigerant connections Connect the air conditionerto the earthing system before making the electrical connections Connecting wire conduits When connecting cables between the ...

Page 86: ... Main power cable L F1 Electrical component box Communication cable N IndoorUnit Main power cable MCCB 1 Communication cable Outdoor to indoorpowercable OutdoorUnit Earthing ELB ELCB 1 OR IndoorUnit Main power cable MCCB 1 OutdoorUnit Communication cable Outdoor to indoorpowercable Earthing ELB ELCB 1 OR 2 Insert the cables through the conduits and then fix the conduits to the conduit plate with t...

Page 87: ...x Main power cable The appearance of the unit maybe different from the picture depending on the model Powersupply 1 L 2 N L N F1 F2 When using ELB forAC018BXADCH 1 phase F2 PowerSupply The appearance of the unit maybe different from the picture depending on the model Cable tie MCCB Outdoorto indoor powercable 1 L ELB Cable clamp 2 N IndoorUnit Main power cable L F1 Electrical component box Communi...

Page 88: ...es with contact gap of a least 0 12 inch 3mm Devices disconnected from the power supply should be completely disconnected in the condition of overvoltage category Keep distances of1 97 inch 50mm or more between power cable and communication cable Main powerterminal block specifications AC009 012 018BXADCH 1 phase Unit inch mm AC power M4 screw 1 L L F1 0 64 16 3 0 40 10 1 Communication M4 screw 2 ...

Page 89: ...14 7 1 25 1 25 0 79 AC036BN6DCH 0 79 AC036BNHDCH 3 50 AC036BNTDCH 0 51 AC036BNZDCH 3 60 24 5 35 0 AC042BXADCH AC042BN4DCH 20 9 1 25 1 25 0 79 AC042BN6DCH 0 79 AC042BNHDCH 3 50 32 2 40 0 AC042BNZDCH 3 40 AC048BXADCH AC048BN4DCH 20 9 1 25 1 25 0 79 AC048BN6DCH 0 79 AC048BNHDCH 3 50 AC048BNZDCH 4 10 32 8 40 0 Model PowerSource RLA A Outdoor Indoor MCA A MOP A Outdoor Indoor MOC Rated input current of...

Page 90: ...s are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits Maximum allowable voltage variation between phases is 2 Wire size type must complywith the applicable local and national code Wire size Based on the value of MCA Wire type 1 phase 60245 IEC57 IEC orH05RN F CENELEC grade ormore Silence mode controllerwiring diagram with Ext...

Page 91: ...oft copper tin plated eyelet terminal with M4 screw hole NOT SUPPLIED WITH UNITACCESSORIES The appearance of the unit may be different from the picture depending on the model Outdoor to indoorpowerterminal specifications Connect the cables to the terminal board using the compressed ring terminal Cover a solderless ring terminal and a connector part of the power cable and then connect it Silversold...

Page 92: ...5 0 0 1 8 0 07 8 3 16 22 7 8 13 1 2 43 1 11 16 8 4 1 3 16 50 0 07 8 3 16 22 7 8 0 3 0 011 13 5 1 2 0 5 0 019 0 2 0 007 11 4 7 16 0 3 0 011 17 5 11 16 14 9 16 50 2 8 4 1 3 16 0 4 0 015 0 0 1 8 0 07 70 0 10 8 3 16 24 1 0 4 0 015 17 5 11 16 0 5 0 019 0 4 0 015 13 3 1 2 18 5 20 0 4 0 4 0 015 3 4 3 4 0 015 51 2 8 4 1 3 16 0 0 2 0 0 078 Connect the rated cables only Connect using a driverwhich is able t...

Page 93: ... be lighterthan polychloroprene sheathed flexible cord Code designation IEC 60245 IEC 57 CENELEC H05RN F When installing the indoorunit in a computerroom or network room use the double shielded tape aluminum polyesterbraid copper cable of FROHH2R type Indoorpowersupply Powersupply Max Min V Indoorpowercable 1Φ 208 230V 60Hz 10 0 0012 inch 0 75mm2 3 wires Communication cable 0 0012 inch 0 75mm2 2 w...

Page 94: ...Head Office Suwon Korea 129 Samsung Ro Yeongtong Gu Suwon City Gyeonggi Do Korea 16677 Website www samsung com https partnerhub samsung com Email airconditioner samsung com Images and data in this book may subject to change without prior notice ...

Reviews: