2. Summary Table
2. Summary Table
Performance Characteristics
Model Code
Net Weight
(kg)
Capacity
Fan Speed
Airflow
(Cooling/Heating)
(CMM)
Sound Pressure Level
(dBA)
Sound Power Level
(dBA)
Cooling
(kW)
Heating
(kW)
AC026NNNDKH/EU
11.4
Max.
3.4
4.1
High
8.0 / 10.0
31
48
Std.
2.6
3.4
Mid
7.0 / 9.0
28
-
Min.
1.0
0.98
Low
6.0 / 8.0
25
-
AC035NNNDKH/EU
11.4
Max.
4.0
4.8
High
9.2 / 10.4
34
50
Std.
3.5
4.0
Mid
8.0 / 9.0
30
-
Min.
1.0
1.0
Low
6.4 / 7.8
25
-
AC052NNNDKH/EU
11.6
Max.
5.9
7.5
High
10.5 / 10.5
39
56
Std.
5.0
5.5
Mid
9.5 / 9.5
34
-
Min.
1.3
1.3
Low
8.5 / 8.5
29
-
AC060NNNDKH/EU
11.6
Max.
6.5
9.0
High
11.0 / 11.0
41
56
Std.
5.8
7.0
Mid
10.0 / 10.0
37
-
Min.
1.8
1.6
Low
9.0 / 9.0
32
-
AC071NNNDKH/EU
11.8
Max.
8.0
9.0
High
11.5 / 11.5
42
58
Std.
6.8
7.5
Mid
10.5 / 10.5
39
-
Min.
2.2
1.9
Low
9.5 / 9.5
36
-
NOTE
•
Sound data is based on cooling operation.
Electric Characteristics
Model
Outdoor Unit
Input Current (Amperes)
Power Supply
Indoor Unit
Outdoor Unit
Rated
Voltage range
Outdoor Unit
Indoor Unit
Total
MCA(A)
MFA(A)
Hz
Volts
Min. Max.
Cooling
Heating
AC026NNNDKH/EU AC026MXADKH/EU
50
220 to 240 198 264
10
10
1
11
11
12.5
AC035NNNDKH/EU AC035MXADKH/EU
50
220 to 240 198 264
10
10
1
11
11
12.5
AC052NNNDKH/EU AC052MXADKH/EU
50
220 to 240 198 264
20
20
1
21
21
25
AC060NNNDKH/EU AC060MXADKH/EU
50
220 to 240 198 264
20
20
1
21
21
25
AC071NNNDKH/EU AC071MXADKH/EU
50
220 to 240 198 264
20
20
1
21
21
25
NOTE
• MCA : Minimum circuit amperes
• MFA : Maximum fuse amperes
•
Select wire size based on the value of MCA