EB 8389S EN
25
Statistical information
3.2
Data logger
The data logger records the measured vari-
ables (
valve position x, set point w, set point
deviation e
and
drive signal y
). The recorded
data are plotted against time in a graph.
Note:
The data logger is interrupted and
must be reactivated when one of the
following events occurs.
−
Change of the operating mode
−
Air supply failure
−
Failure of power sup-
ply of the positioner
−
Failure of power supply of the ex-
ternal solenoid valve
3.2.1
Permanent data logging
The measured variables are logged at the
rate defined in 'Scan rate' and saved in a
circular buffer, which holds 100 data points
per measured variable at one time.
Note:
You can read the measured data
logged over the past 24 hours from
the 'Data logger' graph when the
Di-
agnosis
folder (
> Statistical informa-
tion > Data logger
) is left open over
this period.
Defining parameters
1. Select 'Permanent' (Selection).
2. Enter scan rate.
3. Start data logger.
Fig. 2:
Diagnosis > Statistical information > Data logger