Error during operation
9.3 Temperature monitoring
When a system deviation greater than 10 °C persists in a control circuit for 30 minutes, an
Err 6 message (temperature monitoring alarm) is generated.
Functions
WE
Configuration
Temperature monitoring
0
CO5 > F19 - 1
9.4 Error status register
The error status register is used to indicate controller or system errors.
Error message
Meaning
Decimal value
Err 1
Sensor failure
1
1
Err 2
–
2
Err 3
Disinfection temperature not reached
4
Err 4
Max. charging temperature reached
8
Err 5
–
16
Err 6
Temperature monitor alarm
32
32
Err 7
Unauthorized access occurred
64
Err 8
Error message of a binary input
128
Err 9
–
256
Total
Example: Value of error status register when a sensor fails and a
temperature monitoring alarm =
33