8
Appendix
8.1
Settings level
Menu item
Functions/parameters
Setting range
WE
See
section
Date/time
System time (date and time) freely configurable
Automatic summer time On / Off
On
RS-232/Slave
*
)
Only with
modem = On
Modbus slave
Station address
16-bit addressing
1 to 247, 255
Yes / No
255
No
Control system
monitoring
1 to 300 min
30 min
Modem
Cyclical initialization *
)
Auto. disconnection *
)
On / Off
1 to 300 min
1 to 300 min
Off
30 min
5 min
Baud rate
9600, 19200
9600
RS-485/Master
Gateway
On / Off
Off
Addressing
8 bit, 16 bit
8 bit
Baud rate
9600, 19200
9600
Frame
On / Off
Off
Bias voltage
On / Off
Off
Validity
0 to 600 s
0 s
Pause
0 to 100 ms
0 ms
Timeout
100 to 10000 ms
100 ms
Expansion module
Station address
0 to 255
0
RS-232/Prog
Station address
1 to 247, 255
255
Baud rate
9600, 19200
9600
32
EB 5571 EN
Appendix