Functions
WE
Configuration
Control system monitoring
0
CO6 -> F07 - 0
Parameters
*
WE
Parameter level / Range of values
Station address (ST.-NR)
255
PA6 / 1 to 247 with CO6 -> F02 - 1: 1 to 32000
Baud rate (BAUD)
9600
PA6 / 19200, 9600
Cyclical initialization (I)
30 min PA6 / 1 to 255 min
Modem dialing pause (P)
5 min
PA6 / 0 to 255 min
Modem time-out (t)
5 min
PA6 / 1 to 255 min
No. of redialing attempts (C)
5
PA6 / 1 to 255
Phone no. of control station (tELnr) –
PA6 / Max. 22 characters; 1, 2, 3, …9, 0;
“-“ end of a string, “P“ pause
* –> section 9.3 (“Description of communication parameters to be adjusted“)
9.2
System bus interface with RS-232/RS-485 cable converters
(for two-wire and four-wire bus)
To operate the controller in combination with cable converters, a constant bus connection is
required (data cable). The bus line links the control units/devices in an open ring. At the end
of the bus line, the data cable is connected to the control station using an RS-485/RS-232
converter (e.g. TROVIS 5484).
The maximum range of the bus connection (cable length) is 1,200 meters. A maximum of
126 devices (two-wire bus) can be connected to such a segment.
94
EB 5576 EN
Communication
1
2
3
4
5
6
7
8
Device bus
Device bus
+5V
RD
CTS
DTR
TD
GND
Fig. 13 · Assignment of the RJ-45 jack