EB 8389 EN
121
Appendix
9.2 Error messages and recommended corrective action
Message
Possible reasons
Recommended action
Status
classifica
-
tion
Single reset
Diagnostics > Status messages
Control loop (Code 57)
−
Actuator is blocked.
−
Positioner attachment has
shifted subsequently.
−
Insufficient supply pressure
−
Check attachment.
−
Check supply pressure.
•
[ ]
–
Zero point (Code 58)
−
Mounting arrangement or
linkage has slipped.
−
Valve trim, particularly
with soft seat, is worn.
−
Check valve and position-
er attachment.
−
Calibrate zero.
−
We recommend to re-
initialize the positioner if
zero deviates by more
than 5 %.
•
[ ]
•
Autocorrection (Code 59)
Data section error in position-
er.
–
–
•
Fatal error (Code 60)
−
Error detected in safety-
relevant data. Possible
cause: EMC disturbances.
The valve is moved to fail-safe
position.
–
–
–
w too small (Code 63)
The set point (w) is lower than
3.7 mA.
Check set point (w). If
necessary, restrict lower limit
of current source to ensure
that a current below 3.7 mA
cannot be issued.
•
[ ]
–
Total valve travel exceeded
'Absolute total valve travel'
exceeded 'Total valve travel
limit'.
–
•
[ ]
–
Temperature exceeded
–
–
•
[ ]
–
Extended diagnosis
(Code 79)
Extended diagnostics
messages generated by
EXPERTplus.
See Diagnosis >
Status messages > Extended.
–
–
Reference variable outside
range
Set point smaller than 4 mA or
greater than 20 mA.
If possible, limit current
source at lower (4 mA) and/
or upper (20 mA) limit.
–
–