62
EB 8384-3 EN
Mounting and start-up
5.7 Attachment to Type 3510
Micro-flow Valve
Î
Refer to Fig. 19
Î
Required mounting parts and accesso-
ries: Table 4 on page Seite 23.
Î
Observe travel tables on page Seite
The positioner is attached to the valve yoke
using a bracket.
1. Fasten the bracket (9.1) to the stem con-
nector.
2. Screw the two bolts (9.2) to the bracket
(9.1) of the stem connector (9), place the
follower plate (3) on top and use the
screws (9.3) for fastening.
3. Mount the travel indication scale (acces-
sories) to the outer side of the yoke using
the hex screws (12.1), ensuring that the
scale is aligned with the stem connector.
4. Fasten the hex bar (11) onto the outer
side of yoke by screwing the M8 screws
(11.1) directly into the holes on the yoke.
5. Fasten the bracket (10) to the hex bar us-
ing the hex screw (10.1), washer and
tooth lock washer.
6. Mount connecting plate (6) or pressure
gauge bracket (7) with pressure gauges
on the positioner, making sure the two
seals are seated properly.
7. Unscrew the standard M lever (1) includ-
ing follower pin (2) from the positioner
shaft.
8. Take the S lever (1) and screw the follow-
er pin (2) in the hole for pin position 17.
9. Place the S lever on the positioner shaft
and screw tight using the disk spring
(1.2) and nut (1.1).
Move lever once all the way as far as it
will go in both directions.
10. Place positioner on the bracket (10) in
such a manner that the follower pin
slides into the groove of the follower pin
(3). Adjust the lever (1) correspondingly.
Screw the positioner to the bracket (10)
using both its screws.
5.8
Attachment to rotary actu
-
ators
Î
Refer to Fig. 21
Î
Required mounting parts and accesso-
ries: Table 7 on page Seite 24.
Î
Observe travel tables on page Seite
The positioner is mounted to the rotary actu-
ator using two pairs of brackets.
Prior to attaching the positioner to the
SAMSON Type 3278 Rotary Actuator,
mount the associated adapter (5) to the free
end of the rotary actuator shaft.
On attaching the positioner as described be
-
low, it is imperative that the actuator's direc-
tion of rotation is observed.
1. Place follower clamp (3) on the slotted
actuator shaft or adapter (5).
10.1
1
2
1.1
1.2
6.1
6
7
8
10
9
9.1
11
11.1
3
12.1
9.2
9.3
S lever
NOTICE
!
Only use the connecting plate (6)
included in the accessories to connect
supply and output.
Never screw threaded parts directly
into housing.
1
Lever
1.1
Nut
1.2
Disk spring
2
Follower pin
3
Follower plate
6
Connecting plate
6.1
Seals
7
Pressure gauge bracket
8
Pressure gauge
mounting kit
9
Stem connector
9.1
Bracket
9.2
Bolt
9.3
Screws
10
Bracket
10.1 Screw
11
Hex bar
11.1 Screws
12.1 Screws
Fig. 19:
Attachment to Type 3510 Micro-flow Valve
Note
Summary of Contents for TROVIS 3730-3
Page 38: ...38 EB 8384 3 EN...
Page 40: ...40 EB 8384 3 EN...
Page 80: ...80 EB 8384 3 EN...
Page 94: ...94 EB 8384 3 EN...
Page 118: ...118 EB 8384 3 EN...
Page 124: ...124 EB 8384 3 EN Decommissioning and removal...
Page 146: ...146 EB 8384 3 EN...
Page 150: ...150 EB 8384 3 EN...
Page 151: ...EB 8384 3 EN 151...
Page 152: ...152 EB 8384 3 EN...
Page 153: ...EB 8384 3 EN 153...
Page 154: ...154 EB 8384 3 EN...
Page 155: ...EB 8384 3 EN 155...
Page 156: ...156 EB 8384 3 EN...
Page 157: ...EB 8384 3 EN 157...
Page 158: ...158 EB 8384 3 EN...
Page 159: ...EB 8384 3 EN 159...
Page 160: ...160 EB 8384 3 EN...
Page 161: ...EB 8384 3 EN 161...
Page 162: ...162 EB 8384 3 EN...
Page 163: ...EB 8384 3 EN 163...
Page 164: ...164 EB 8384 3 EN...
Page 165: ...EB 8384 3 EN 165...
Page 166: ...166 EB 8384 3 EN...
Page 167: ...EB 8384 3 EN 167...
Page 168: ...168 EB 8384 3 EN...
Page 169: ...EB 8384 3 EN 169...
Page 170: ...170 EB 8384 3 EN...
Page 171: ...EB 8384 3 EN 171...
Page 177: ...EB 8384 3 EN 177...
Page 178: ...178 EB 8384 3 EN...
Page 179: ...EB 8384 3 EN 179...