EB 8384-3 EN
71
Mounting and start-up
−
In addition, the instructions in
sections 5.15 and 5.16 apply for the
pneumatic and electrical connection.
−
Since 2009, the back of the position
sensor (20) is fitted with two pins acting as
mechanical stops for the lever (1). If this
position sensor is mounted using old
mounting parts, two corresponding
Ø 8 mm holes must be drilled into the
mounting plate/bracket (21). A template is
available for this purpose. See Table 8.
5.10.1 Mounting the position
sensor with direct at
-
tachment
Type 3277-5 Actuator with 120 cm² (Fig. 6)
The signal pressure from the positioner is
routed over the signal pressure connection of
the connecting plate (9, Fig. 27 left) to the
actuator diaphragm chamber. To proceed,
first screw the connecting plate (9) included
in the accessories onto the actuator yoke.
−
Turn the connecting plate (9) so that the
correct symbol for the fail-safe action
"actuator stem extends" or "actuator
stem retracts" is aligned with the marking
(Fig. 27, below).
−
Make absolutely sure that the gasket for
the connecting plate (9) is correctly in-
serted.
−
The connecting plate has threaded holes
with NPT and G threads. Seal the
threaded connection that is not used with
the rubber seal and square plug.
Type 3277 Actuator with 175 to 750 cm²:
The signal pressure is routed to the connec-
tion at the side of the actuator yoke for the
version with fail-safe action "actuator stem
extends". For the fail-safe action "actuator
stem retracts" the connection on the top dia-
phragm case is used. The connection at the
side of the yoke must be fitted with a venting
plug (accessories).
Mounting the position sensor
1. Place the lever (1) on the sensor in
mid-position and hold it in place. Un-
thread the nut (1.1) and remove the lever
together with the disk spring (1.2) from
the sensor shaft.
2. Screw the position sensor (20) onto the
mounting plate (21).
3. Depending on the actuator size and rat-
ed valve travel, determine which lever
and position of the follower pin (2) is to
be used from the travel table on
page Seite 26. The positioner is deliv
-
ered with the
M
lever in pin position
35
on the sensor. If necessary, remove the
follower pin (2) from its pin position and
move it to the hole for the recommended
pin position and screw tight.
4. Place the lever (1) and disk spring (1.2)
on the sensor shaft. Place the lever
in
mid-position
and
hold it in place
. Screw
on the nut (1.1).
5. Place follower clamp (3) on the actuator
stem, align it and screw tight so that the
mounting screw is located in the groove
of the actuator stem.
Note
Summary of Contents for TROVIS 3730-3
Page 38: ...38 EB 8384 3 EN...
Page 40: ...40 EB 8384 3 EN...
Page 80: ...80 EB 8384 3 EN...
Page 94: ...94 EB 8384 3 EN...
Page 118: ...118 EB 8384 3 EN...
Page 124: ...124 EB 8384 3 EN Decommissioning and removal...
Page 146: ...146 EB 8384 3 EN...
Page 150: ...150 EB 8384 3 EN...
Page 151: ...EB 8384 3 EN 151...
Page 152: ...152 EB 8384 3 EN...
Page 153: ...EB 8384 3 EN 153...
Page 154: ...154 EB 8384 3 EN...
Page 155: ...EB 8384 3 EN 155...
Page 156: ...156 EB 8384 3 EN...
Page 157: ...EB 8384 3 EN 157...
Page 158: ...158 EB 8384 3 EN...
Page 159: ...EB 8384 3 EN 159...
Page 160: ...160 EB 8384 3 EN...
Page 161: ...EB 8384 3 EN 161...
Page 162: ...162 EB 8384 3 EN...
Page 163: ...EB 8384 3 EN 163...
Page 164: ...164 EB 8384 3 EN...
Page 165: ...EB 8384 3 EN 165...
Page 166: ...166 EB 8384 3 EN...
Page 167: ...EB 8384 3 EN 167...
Page 168: ...168 EB 8384 3 EN...
Page 169: ...EB 8384 3 EN 169...
Page 170: ...170 EB 8384 3 EN...
Page 171: ...EB 8384 3 EN 171...
Page 177: ...EB 8384 3 EN 177...
Page 178: ...178 EB 8384 3 EN...
Page 179: ...EB 8384 3 EN 179...