5-3
Installation
Installation with thermowell
When a thermowell is used, a welding sock-
et with G 1 female thread must be used.
1. Seal the thermowell into the welding
socket.
2. Insert the sensor and tighten it with the
clamping screw.
For temperature regulators with safety tem-
perature limiter (TR/STL), install the sensor of
the limiter near the sensor of the regulator.
Dynamic behavior of Type 2430 and
Type 2430-3 Control Thermostats
The dynamics of the regulator are mainly de-
termined by the response of the sensor with
its characteristic time constant. Table 5-1
shows the dynamic behavior of the
Type 2430 and Type 2430-3 Control Ther-
mostats measured in water.
Capillary tube
Carefully run the capillary tube without
bending or twisting it. Avoid locations with
considerable ambient temperature fluctua-
tions along the entire length of the tube.
Do not damage or shorten the capillary
tube. Roll up any capillary tube that is not
used. The smallest permissible bending radi-
us is 50 mm.
Note
Note
Support and suspension
The plant engineering company is responsi-
ble for selecting and implementing a suitable
support or suspension of the installed regula-
tor with control thermostat and the pipeline.
Depending on the regulator version and
mounting position, the regulator and pipe-
line must be supported or suspended.
Do not attach supports directly to the regula-
tor or control thermostat.
Note
NOTICE
!