EB 5206 EN
15
Operation
5 Operation
5.1 Temperature regulator (TR)
Adjust the set point at the set point adjuster
(4).
Limiting the set point range
The lower range value and upper range val-
ue of the set point range can be limited.
4a
4
4
Set point adjuster
4a
Pin to limit the set point range
1. Turn the set point adjuster (4) to a value
within the required temperature range.
2. Pull the set point adjuster (4) off the tem-
perature regulator.
3. Break off the pin (4a).
4.
Insert the pin (4a) at the point where the
temperature is to be limited (min./max.
temperature).
5.
Place the set point adjuster back on the
temperature regulator.
5.2 Safety temperature mon-
itor (STM)
Open the thermostat housing and adjust the
set point using a flat-blade screwdriver.
5.3 Safety temperature limiter
(STL)
Open the thermostat housing and adjust the
set point using a flat-blade screwdriver.Open
the thermostat housing and adjust the set
point using a flat-blade screwdriver.
Unlocking safety temperature limiters
The safety temperature limiter can only be
reset after the temperature has fallen below
the adjusted limit by approximately 10 %.
Use a flat-blade screwdriver to unlock the
thermostat.
5a
5
5
Screw lid
5a
Spring for unlocking
1. Unscrew the screw lid (5).
2. Use a flat-blade screwdriver to move the
spring (5a) from the bottom to the top as
far as it will go.
Note