6
EB 5206 EN
General safety instructions
2.2 Technical data
Single thermostats:
Type 5343 (STM), Type 5344 (TR), Type 5345 (STL)
Double thermostats:
Type 5347 (TR/STL), Type 5348 (TR/STM), Type 5349 (STM/STL)
Permissible ambient temperature
Transportation and storage
–30 to +80 °C
Service
Max. 80 °C
Max. pipe temperature when
mounted as a contact
thermostat
Max. 120 °C
Degree of protection
IP 54 according to EN 60529
Cable entry
M20x1.5 cable gland, suitable for 6 to 12 mm cable diameter
Minimum switching capacity
AC/DC = 24 V, 100 mA
Maximum switching capacity
Temperature regulator (TR),
safety temperature monitor
(STM)
With 230 V AC +10 %
NC contact:
16 A (2.5); cos
φ
= 1 (0.6)
NO contact:
6.3 A (2.5); cos
φ
= 1 (0.6)
With 230 V DC +10 %
NC contact:
0.25 A
NO contact:
0.25 A
Safety temperature limiter
(STL)
With 230 V AC +10 %
NC contact:
16 A (2.5); cos
φ
= 1 (0.6)
Signal contact:
2 A (2.5); cos
φ
= 1 (0.4)
With 230 V DC +10 %
NC contact:
0.25 A
Signal contact:
0.25 A
Influence of mean ambient
temperature based on the set point
A shift of the switching point arises when the ambient temperature at the
knob and at the capillary tube deviates from the calibration ambient tem-
perature of +22 °C:
Higher ambient temperature
g
Lower switching point
Lower ambient temperature
g
Higher switching point
This influence is minimized by temperature compensation.
Connection
Spring-cage terminals, 0.75 to 2.5 mm² wire cross-section
Materials
Bottom section of the housing
PA (reinforced)
Housing cover
ABS with window (PMMA)
Temperature sensor, capillary
tube
Cu (copper)
Weight
Single thermostat approx. 0.225 kg · Double thermostat approx. 0.45 kg
Compliance
·
1)
1)
No EAC compliance for Type 5349
Summary of Contents for EB 5206 EN Series