12
EB 5206 EN
Installation
3.3.1 Wall mounting with the
capillary tube to the
thermowell
The thermostats are fastened to the wall us-
ing two screws (not included in the scope of
delivery).
7. Drill holes in wall as shown in Fig. 3.
8.
Insert the seal (6).
9. Fix the capillary tube in the notch at the
side of the thermostat housing or let it
run down the middle (Fig. 4b).
10. Fasten the back of the housing (1) using
two screws to the wall.
11. Screw the thermowell (7) into the pipe or
tank.
12. Push the sensor (2) as far as it will go in-
to the thermowell (7).
13. Fasten the capillary tube (3) to the ther-
mowell (7) using the supplied clip (7a).
14. Connect the wiring as described in sec-
15. Screw the front cover back onto the ther-
mostat.
TR:
Place the set point adjuster onto the tem-
perature regulator.
3.3.2 Mounting on tanks or in
pipes
The thermostats are fastened to the thermow-
ells which are screwed into place.
7.
Insert the seal (6).
8. Screw the thermowell (7) into the pipe or
tank.
9. Insert the small metal plate (7b) at the
back of the housing (1) and secure in
place with the screw (7c).
10. Push the sensor (2) as far as it will go in-
to the thermowell (7), making sure that
the round hole at the back of the housing
(1) rests on the collar on the thermowell.
11. Push the thermostat approx. 2 mm
lengthways toward the SAMSON logo to
allow the thermowell to engage.
12. Tighten screw (7c) until the housing is
fixed into place on the thermowell.
13. Connect the wiring as described in sec-
14. Screw the front cover back onto the ther-
mostat.
TR:
Place the set point adjuster onto the tem-
perature regulator.
95
95
42.4
95.4
Ø 4.
5
Ø 4.5
Single thermostat
Double
thermostat
Fig. 3:
Drill templates