12
EB 2519 EN
Design and principle of operation
3.2
Technical data
The nameplates on the pressure element and valve provide information on the device version.
See section 2.1 and the valve documentation.
Table 1:
Technical data · All pressure stated as gauge pressure in bar
Valves
Type 2111, Type 2119, Type 2422
1)
Valve size DN
DN
15
20
25
32
40
50
65
80 100
125
150
Type 2111
Data Sheet
u
–
Type 2119
Data Sheet
u
Type 2422
1)
Data Sheet
u
Pressure rating
PN 16 to 40
Type 2401-1/-2 Pressure
Element
Size 50
2)
Size 150
2)
Adjustment range of limit value
1 to 10 bar
Permissible operating pressure
10 bar
Permissible ambient
temperature
Max. 80 °C
Permissible operating
temperature
200 °C
Conformity
Capillary tube length
Approx. 2 m
Strainer
Type 1 NI, G ½, PN 16 (
u
Switching cycles according to
DIN EN 14597
500
Electric signal transmitter
Max. load at 230 V (AC)
10 A with resistive load
1)
Formerly Type 2114
2)
Size 50: Type 2401-1/-2 for valve DN 15 to 50 | Size 150: Type 2401-1/-2 for valve DN 65 to
150
Dimensions and weights
Table 2 to Table 4 provide an overview of the dimensions and weights of the different combi
-
nations (pressure element and valve). The lengths and heights in the dimensional drawings
are shown on page 14.
Dimensions in mm · Weights in kg