7.3 Parameter description
SP - Set point with status: Reference variable w in "Auto" operating mode
The reference variable w of the positioner is preset via SP in automatic mode ("Auto").
SP consists of a floating point value (4 bytes) and the associated status (1 byte).
Value and status must be transferred together (data consistency = 5 bytes). If the status of the
reference variable is "bad" (value < 64dec.), the positioner remains in the fail-safe position
determined by the actuator.
RCAS_IN/RCAS_OUT: Reference variable w in "RCAS" operating mode
The reference variable w of the positioner is preset in the REMOTE CASCADE "RCAS" opera-
ting mode via RCAS_IN/RCAS_OUT. RCAS_IN/RCAS_OUT both are made up of one float-
ing point value (4 bytes) and the associated status (1 byte).
Value and status must be transferred together (data consistency = 5 bytes). If the status of the
reference variable is "bad" (value < 64dec.), the positioner remains in the fail-safe position
determined by the actuator.
NOTE: The RCAS operating mode is implemented in version K1.60 and higher.
READBACK - Current position with status: Controlled variable x
The position feedback is transmitted via the READBACK parameter and consists of a floating
point value (4 bytes) and the associated status (1 byte).
POS_D - Discrete valve position feedback with status: Final position indication
The final valve position is indicated via the POS_D parameter and consists of one message
value (1 byte) and the associated status (1 byte).
The message value is encoded as follows:
0 = not initialized, 1 = closed (x< 0.5%), 2 = open (x>99.5%), 3 = intermediate
CHECKBACK - Device status: Detailed device information, coded bit-wise encoded
Bit no.
Name
Description
Byte
0
CB_FAIL_SAFE
Fail-safe position (MODE = out of service)
0
1
CB_REQ_LOC_OP
Request for local operation
2
CB_LOCAL_OP
Device in local mode
3
CB_OVERRIDE
Emergency operation / Forced venting active
4, 5, 6
Not used
7
CB_TRAV_TIME
Status of movement monitoring (is reset automatically)
0
40
EB 8382-1 EN
How to implement the PROFIBUS Master Class 1
Summary of Contents for 3785 series
Page 69: ...EB 8382 1 EN 69...
Page 70: ...70 EB 8382 1 EN...
Page 71: ...EB 8382 1 EN 71...
Page 72: ...72 EB 8382 1 EN...
Page 73: ...EB 8382 1 EN 73...
Page 74: ...74 EB 8382 1 EN...
Page 75: ...EB 8382 1 EN 75...
Page 76: ...76 EB 8382 1 EN...
Page 77: ...EB 8382 1 EN 77...
Page 78: ...78 EB 8382 1 EN...
Page 79: ...EB 8382 1 EN 79...