Table 1: 

Technical data

Type 3725 Positioner

Travel (adjustable)

Direct attachment to Type 3277 Actuator:

3.75 to 30 mm

Direct attachment to Type 2780-2 Actuator:

6/12/15 mm

Attachment to Type 3372 Actuator:

15/30 mm

Attachment according to IEC 60534-6 (NAMUR):

3.75 to 50 mm

Attachment to rotary actuators:

24 to 100°

Reference variable w  

(reverse polarity protection)
Static destruction limit

4 to 20 mA signal range · Two-wire device · Split-range operation 4 to 11.9 mA and 12.1 to 20 mA

±33 V

Minimum current

3.8 mA

Load impedance

Max. 6.3 V

Supply air 

Air quality acc. to ISO 8573-1

Supply air: 1.4 to 7 bar (20 to 105 psi)

 

Max. particle size and density: Class 4 · Oil content: Class 3 · Pressure dew point: Class 3 or at least 10 K 

below the lowest ambient temperature to be expected

Signal pressure (output)

0 bar up to the capacity of the supply pressure · Can be limited to approx. 2.3 bar by software

Characteristic

3 characteristics for globe valves · 9 characteristics for rotary valves

Hysteresis

≤ 0.3 %

Sensitivity

≤ 0.1 %

Transit time

Only for actuators with initialization time > 0.5 s 

1)

Direction of action

w/x reversible

Air consumption

≤ 100 l

n

/h with a supply pressure up to 6 bar and a signal pressure of 0.6 bar

Air output capacity

Actuator filled with air

At Δp = 6 bar:   8.5 m

n

3

/h,

At Δp = 1.4 bar: 3.0 m

n

3

/h

K

Vmax

(20 °C) = 0.09

Actuator vented

At Δp = 6 bar: 14.0 m

n

3

/h,

At Δp = 1.4 bar: 4.5 m

n

3

/h

K

Vmax

(20 °C) = 0.15

Permissible ambient temperature

–20 to +80 °C

 

–25 to +80 °C with metal cable gland
The limits in the test certificates additionally apply for explosion-protected versions

Safety

Influences

Temperature:

≤ 0.15 %/10 K

Influence of vibrations:

≤ 0.25 % up to 2000 Hz and 4 g according to IEC 770

Supply air:

None

Electromagnetic compatibility

Complying with EN 61000-6-2, EN 61000-6-3 and NAMUR Recommendation NE 21

Explosion protection

 II 2G Ex ia IIC T4 according to ATEX

Intrinsically safe, Ex ia IIC T4 according to CSA Group

 1Ex ia IIC T4 Gb X according to GOST

Degree of protection

IP 66

Materials

Housing

Polyphthalamide (PPA)

Cover

Polycarbonate (PC)

External parts

Stainless steel 1.4571 and 1.4301

Cable gland

M20 x 1.5, black polyamide (PA)

Venting

High-density polyethylene (PE-HD)

Weight

Approx. 0.5 kg

1)

  For faster actuators, a volume restriction must be used. Otherwise, the initialization cannot be performed successfully.

Table 2: 

Explosion protection certificates

Type of approval

Certificate number

Date

Comments

EC Type Examination Certificate

PTB 11 ATEX 2020 X

2011-08-25

II 2G Ex ia IIC T4

GOST certification

RU C-DE.GB08.B.00697

2014-12-15

1Ex ia IIC T4 Gb X

CSA certification

2703735

2014-06-03

Ex ia IIC T4

Reviews: