Samson 3301 Mounting And Operating Instructions Download Page 5

Process medium and scope of application

EB 7065 EN 

 5 

Process medium and scope of application

Pneumatic controller functioning as a proportional controller to control the temperature of gases 
and vapors at the point of measurement with a pneumatic control valve.
Medium temperatures from 0 to 300 °C

The controller compares the temperature measured by the fixed expansion bulb sensor with the 
adjusted set point and issues a pneumatic signal between 0.2 to 1 bar at the output. This signal 

pressure acts on the connected pneumatic control valve. The controller requires a supply pres-

sure of 1.4 bar. The measured temperature is indicated at the controller.

2.1 

Transportation and storage

Transportation and storage in the permissible temperature range from –10 to +90 °C. Protect 
the controller against adverse influences, such as dirt or moisture during storage.

2.2 

Versions

Two versions of the Type 3301 Controller are available that have different set point ranges.

Table 1: 

Type 3301 

 Versions

Type

Set point range

Configuration ID 

(Var.-ID)

3301-9001

0 to 200 °C

Var.-ID 1063422

3301-9002

100 to 300 °C

Var.-ID 1294879

The mounting parts are not included in the scope of delivery. They must be ordered separately 
(see section 4 on page 8, Fig. 4 and Fig. 5).

Summary of Contents for 3301

Page 1: ...Mounting and Operating Instructions EB 7065 EN Edition January 2014 Pneumatic Controller for Temperature Type 301 1 Pneumatic Controller for Temperature Type 3301...

Page 2: ...2 EB 7065 EN Definition of the signal words used in these mounting and operating instructions Note Supplementary explanations informa tion and tips...

Page 3: ...operation 6 3 1 Operating and indicating elements 7 3 2 Pneumatic connections 7 4 Installation 8 4 1 Mounting position 8 5 Operation 10 5 1 Adjusting the operating direction 10 5 2 Set point adjustmen...

Page 4: ...e and experience as well as their knowledge of the applicable standards To ensure appropriate use only use the device in applications where the op erating pressure and temperatures do not exceed the s...

Page 5: ...pneumatic control valve The controller requires a supply pres sure of 1 4 bar The measured temperature is indicated at the controller 2 1 Transportation and storage Transportation and storage in the p...

Page 6: ...ider controlled by the flapper As a result the output pressure pA controlled variable 0 2 to 1 bar is regulated proportional to the sys tem deviation and in relation to the fixed op erating point of 0...

Page 7: ...rol ler They are designed as 1 8 NPT tapped holes Various screw fittings to connect pipes and plastic hoses are available Fig 3 Pneumatic connections underneath the controller Adjustment screw for Xp...

Page 8: ...ntroller is being replaced Screw the thermowell into the sleeve Push the temperature sensor into the thermowell and fasten with the coupling nut G Order no 1080 4888 G Order no 1080 4889 Fig 4 Mountin...

Page 9: ...100 Clamping flange For wall mounting e g on pressureless vessels in air conditioning and ventilation plants Screw the flange to the wall using the two screws Attach the temperature sensor in the flan...

Page 10: ...en 2 and 20 The red dot on the adjustment screw 6 serves as the orientation mark 5 Operation See Fig 1 on page 6 5 1 Adjusting the operating direction Adjust the operating direction before start up as...

Page 11: ...rature reading at the reference thermometer and the adjusted set point of the controller deviate from each oth er you need to readjust zero 1 Unscrew the four corner screws on the cover and remove cov...

Page 12: ...oint continuously adjustable 0 to 200 C or 100 to 300 C Output Control signal y 0 2 to 1 bar Supply air Supply air 1 4 0 1 bar Air consumption in steady state 0 25 mn 3 h Max air output capacity 0 11...

Page 13: ...on the SAMSON website in all SAMSON product catalogs or on the back of these Mounting and Operat ing Instructions To assist diagnosis and in case of an unclear mounting situation specify the followin...

Page 14: ......

Page 15: ......

Page 16: ...SAMSON AG MESS UND REGELTECHNIK Weism llerstra e 3 60314 Frankfurt am Main Germany Phone 49 69 4009 0 Fax 49 69 4009 1507 Internet http www samson de EB 7065 EN 2014 01 27...

Reviews: