EB 8321 EN
7-1
Malfunctions
7 Malfunctions
Read hazard statements, warnings and caution notes in the 'Safety instructions and mea
-
sures' section.
7.1 Troubleshooting
Malfunction
Possible reasons
Recommended action
Actuator shaft does not
move on demand.
Actuator is blocked.
Check attachment.
Remove the blockage.
Insufficient signal
pressure
Check the signal pressure.
Check the signal pressure line for leakage.
Signal pressure not
connected to the correct
connection.
See 'Signal pressure routing' in the 'Design and
principle of operation' section.
Diaphragm in the
actuator defective
See 'Replacing the diaphragm' in the 'Servicing'
section.
Actuator shaft does not
stroke through its
complete opening
angle.
Handwheel restricts the
opening angle
Turn the handwheel to the neutral position (see the
'Operation' section).
Insufficient signal
pressure
Check the signal pressure.
Check the signal pressure line for leakage.
Incorrect setting of
valve accessories.
Check the actuator without valve accessories.
Check the settings of the valve accessories.
Contact our after-sales service for malfunctions not listed in the table.
7.2 Emergency action
Plant operators are responsible for emergency action to be taken in the plant.
Note
Summary of Contents for 3278
Page 10: ...1 6 EB 8321 EN...
Page 12: ...2 2 EB 8321 EN...
Page 18: ...3 6 EB 8321 EN...
Page 22: ...4 4 EB 8321 EN...
Page 26: ...5 4 EB 8321 EN...
Page 28: ...6 2 EB 8321 EN...
Page 30: ...7 2 EB 8321 EN...
Page 36: ...9 2 EB 8321 EN...
Page 38: ...10 2 EB 8321 EN...
Page 40: ...11 2 EB 8321 EN...
Page 42: ...12 2 EB 8321 EN...
Page 46: ...13 4 EB 8321 EN...
Page 47: ......