Quick Guide Installation

Model: RT510 / RT510RF / RT510TX / RT510BC / RXRT510

Always isolate the AC Mains supply before installing or working 

on any components that require 230 VAC 50Hz supply.

Introduction

The RT510 thermostat will switch your heating system on or off, as needed, in accordance 
with the temperature set by you.  The RT510 series includes the following products:
• RT510 for wired applications
• RT510RF (R RXRT510) for wireless applications
• RT510TX for wireless application, using 5 x 5 receiver
• RXRT510 for wireless application using 5 x 5 transmitter
• RT510BC for wireless application

Go to www.salus-manuals.com for the full PDF version of the manual.

Product Compliance

EU Directives: 2014/30/EU, 2014/35/EU, 2014/53/EU and 2011/65/EU. Please check  
www.saluslegal.com for the full information.

Safety Information

Use in accordance with the EU and national regulations.
For indoor use only.
Keep your device completely dry.
This product must be installed by a competent person and in accordance with all the 
EU and national regulations.

Installation

Installation

Button Functions RT510 and RT510TX

Pairing the RT510TX with the Receiver/Boiler Controller

Installer Mode

Dip Switch Settings

RT510 and RT510RF Quick Guide

RT510 Thermostat

 Terminal 

Description 

Backplate

Common Terminal

1 (COM)

2 (NC)

Switched Live OFF

3 (NO)

Switched Live ON

RESET

SELECT

+Hr

SET

RESET

+Hr

SELECT

SET

RESET

+Hr

SELECT

SET

TEST / PAIRING

SELECT

+Hr

SET

TEST / PAIRING

SELECT

+Hr

SET

TEST / PAIRING

SELECT

+Hr

SET

Insert the batteries and 
wire up the device.

RT510RF (RXRT510)Thermostat and Receiver

RT510

RT510TX

ON

AUTO

OFF

MANUAL

Insert the batteries and wire up the receiver. After that please switch the 
receiver ON. If you are using the RT510RF pack, the pairing between the 
thermostat and the receiver is already done.

COM

NO

L N

Terminal 

Description 

Receiver Terminals

NO

COM

L

N

Switch Terminal

Common Switch Terminal

Mains Live (230VAC)

Mains Neutral

RT510BC (Boiler Controller)

Insert the batteries and wire up the boiler controller. 

If you are using the 

RT510BC pack, the pairing between the thermostat and the receiver is 

already done.

N L 1 2 3 4

N L 1 2 3 4 5 6

N L 1 2 3 4

N L 1 2 3 4 5 6

N L 1 2 3 4

N L 1 2 3 4 5 6

N L 1 2 3 4

N L 1 2 3 4 5 6

N L 1 2 3 4

N L 1 2 3 4 5 6

N L 1 2 3 4

N L 1 2 3 4 5 6

N L 1 2 3 4

N L 1 2 3 4 5 6

N L 1 2 3 4

N L 1 2 3 4 5 6

NL

12

34

NL

12

34

56

NL

12

34

NL

12

34

56

NL

12

34

NL

12

34

56

NL

12

34

NL

12

34

56

NL

12

34

NL

12

34

56

NL

12

34

NL

12

34

56

NL

12

34

NL

12

34

56

NL

12

34

NL

12

34

56

NL

12

34

NL

12

34

56

NL

12

34

NL

12

34

56

NL

12

34

NL

12

34

56

NL

12

34

NL

12

34

56

NL

12

34

NL

12

34

56

NL

12

34

NL

12

34

56

N L 1 2 3 4

N L 1 2 3 4 5 6

NL

12

34

NL

12

34

56

NL

12

34

NL

12

34

56

NL

12

34

NL

12

34

56

NL

12

34

NL

12

34

56

NL

12

34

NL

12

34

56

N L 1 2 3 4

N L 1 2 3 4 5 6

N L 1 2 3 4

N L 1 2 3 4 5 6

1

2

3

4

 Terminal 

Description 

Rear of controller

4 (NO)

3 (COM)

2 (L)

1 (N)

Switch Terminal

Common Switch Terminal

Mains Live

Mains Neutral

Boiler internal connections

The DIP switches are found on the rear of 
your thermostat and can be used to change 
the span (temperature accuracy) of your 
thermostat from the default 

+/-

0.5°C to 

+/-

0.25°C and the programmes 5-2 or 24h. 

Changing DIP Switch 2 may cause your boiler 
to operate more frequently. The DIP switches 
are located on the back of the thermostat.

24H

5-2

+/-0.25

+/-0.5

ON

1

2

Key

Function

+Hr

SELECT

SELECT

SET

SET

+

+

+

1. Press once to activate Frost Mode
2. Press for 3 seconds in order to activate Holiday Mode.
Press once to activate/deactivate Boost function

Press once to enter/exit Permanent Override function.

Increase button

Decrease button

Select the clock or programme settings

Press to confirm your settings

Press the buttons for 3 seconds to enter Installer Mode

Press the buttons for 3 seconds to enter Clock Settings

1. Press once to enter in Test Mode for RT510RF
2. Press for 3 seconds to enter/exit Pairing Mode for RT510RF
3. Press once to return to Factory Settings for the RT510 

RESET

+Hr

SELECT

SET

3 Sec

3 Sec

3 Sec

Press the three buttons
together for 3 seconds.

dxx

Function

Parameter Description

Default 

value

d01

Temperature display 

increments

0.1 or 0.5

°

C

Select temperature display 

increments

0.5

°

C

d02

Temperature /-3.0

°

C

Calibrate your thermostat 

temperature

0.0

°

C

d03

Frost setpoint

5.0

-17.0°C

Set the Frost Point temperature 5.0

°

C

If you are using the RT510RF or RT510BC pack, the pairing between 

the thermostat and the receiver/boiler controller is already done.

If you bought an RT510TX and RXRT510 separately then pair as follows.

Please make sure that the Receiver/Boiler Controller is set on Auto.

Begin the pairing process

TEST / PAIRING

SELECT

+Hr

SET

TEST / PAIRING

SELECT

+Hr

SET

TEST / PAIRING

SELECT

+Hr

SET

3 Sec

ON

AUTO

OFF

MANUAL

TEST / PAIRING

SELECT

+Hr

SET

Wait 9 minutes for the timeout 

process to be complete.

End the pairing process

3 Sec

ON

AUTO

OFF

MANUAL

TEST / PAIRING

+Hr

SELECT

SET

TEST / PAIRING

+Hr

SELECT

SET

Test the pairing process

If you bought an RXRT510 or RT510TX and intend pairing with other 

devices in the 5x5 range, please refer to the Receiver Units manual, or the 

relevant manuals available at www.salus-manuals.com

Button Description for RXRT510 Receiver

Button  Function

ON

The receiver is enabled, ready for use.

OFF

The receiver is disabled, will not function.

AUTO

The receiver will switch on and off automatically, 

as operated by the thermostat.

MANUAL

Providing ON is selected,the receiver will switch 

on continuously, overriding the thermostat.

Button Description for RXBC605 Boiler Controller

Button  Function

SYNC

The boiler controller will be syncronised with the 

thermostat.

AUTO

The receiver will switch on and off automatically, 

as operated by the thermostat.

MANUAL

Select in the event of thermostat failure to switch 

boiler on continuously, overriding the thermostat.

ON

AUTO

OFF

MANUAL