24
pump runs with minimum rpm value (
Pmin
parameter) and in case it has dropped below this
value, the pump stops.
If, in case of operation with one solar
collector, temperature of the second collector has
grown above the temperature of the first one (or
v.v.) and the value of
dTonDHW
has been
reached, the regulator switches over the solar
collector circuit.
Once the pump has stopped,
P2
valve is set
at “0” (power supply is cut off).
The system operates until the temperature of
water in DHW tank has reached the value set in
TzCWU
(read-out of T2 sensor), then it stops.
Once
T1 or T3
temperature of solar
collector has reached the critical value of
TCOLkr
,
the
regulator
(despite
the
set
temperature of
TzCWU
has been reached) allows
to start
P1
collector serving pump and to set
P2
valve at the solar collector of higher temperature
in order to reduce the temperature of the
collectors below the value of
HP1
hysteresis.
Once the temperature of DHW tank has
reached the value of
TCWUmax (
read-out of
T2
sensor
),
the regulator, in-spite of reached critical
temperature of the collectors (
TCOLkr
), stops
collector serving pumps to prevent collector
cooling down. It protects DHW tank from
overheating.
List of parameters in
Adjustment
menu
TzCWU -
set temperature of DHW tank.
Night cooling
–
YES
/
NO
- switches on/off
night cooling mode active from 00
00
÷ 05
00
.
Night cooling ON
–
temperature of DHW tank
(read-out of
T2
sensor), upon excess of
which, the regulator will activate night
cooling mode at 0
00
(provided that night
cooling function is enabled).
Night cooling OFF
–
temperature of DHW tank
(read-out of
T2
sensor) to which the
regulator will cool down DHW tank (provided
that night cooling function is enabled and
temperature of
Tschł WŁ
has been exceeded
within the period of time from 00
00
to 05
00
).
Alarm TCOLkr
–
switches on (YES) or off (NO)
the "Temperature of
TCOLkr
exceeded"
alarm. This function does not affect the
regulator operation. Setting this parameter
at "NO
” causes the regulator will not produce
the alarm of exceeded
TCOLkr
temperature
for
T1
and
T3
solar collector sensors.
13.14.
Solar thermal scheme M
Loading of the DHW container with low-
temperature function assisting to loading of the
CH installation and controlling from CT7 room
temperature sensor.
Fig. 13.13 Solar thermal scheme M
The collector pump
P1
will be started with
100% capacity, if the difference between
T1
and
T2
exceeds
value
of
dTonDHW
setting
and it will be working for the time specified in
parameter
tP
. If after this time the difference
between
T1
and
T2
is still above
dTonDHW
, the
pump speed will remain at 100%. If the said
difference between
T1
and
T2
drops below
dTonDHW,
the controller will start reducing the
pump speed, until the difference between
T1
and
T2
reaches
the
value
specified
as
dToffDHW
. If the difference between
T1
and
T2
is between the values
dTonDHW
÷
dToffDHW
,
the controller will calculate and set the pump
speed proportionally.
When
dToffDHW
is reached, the pump will work
at minimal speed (
Pmin
), below it will be
stopped.
If the collector temperature
T1
reaches
the value of
TCOLcr
, then the collector pump will
be
started
(despite
of
reaching
TsDHW
temperature). It is aimed to reduce the
collector’s temperature. It will be stopped, when
T1
drops below
T1<TCOLcr-HP1, or
if the
container temperature at
T2
sensor reaches the
value of
TDHWmax
.
If the temperature in the heated room
reaches
Room
temp
.
then
the
room
temperature sensor CT7, at input
T3
, will affect
at the regulator which will switch off the
P2
pump. It is necessary here to fulfill the condition
that the temperature
T2
must be above the
TsDHWmin heater
parameter.
List of parameters in
Adjustment
menu
TsDHW
–
Preset container temperature.
TsDHWmin heater
–
The minimum temperature
for the DHW container below which the P2
pump will be switched off independently of
the room temperature sensor CT7. If the
temperature of the DHW container does not
rise above the
TsDHWmin heater
value,
the
P2
pump remains off.
dTAB-
temperature difference between
A
buffer
and
system return
(on
T3
and
T4
sensors),
after which the regulator switches three-way
valve.
P2
is enabled, when
dTAB
difference