Description
Nr pin
Input/output
UPS fault
1
Output
General alarm
2
Output
Ground (GND)
3
Input
Remote shutdown
4
Input
Common
5
Input
Bypass
6
Output
Batería low
7
Output
UPS On
8
Output
Mains fault
9
Output
DB9 connector, standard.
Description
Nr pin
Input/output
Mains fault
Programmable
Output
Low battery
Programmable
Output
General alarm
Programmable
Output
Bypass status
Programmable
Output
Summary alarm
Programmable
Output
Battery test
Programmable
Output
Shutdown in process
Programmable
Output
Overload alarm
Programmable
Output
UPS signal "On"
1 (GND) - 14
Input
UPS signal "Off"
1 (GND) - 7
Input
Programmable signal as:
- EPO
- Shutdown on battery mode
- Shutdown on any mode
- Remote control "On-Off"
1 (GND) - 8
Input
UPS "On"
Programmable
Output
AS400 connector, optional.
Table 5.
Relays interface alarms.
• The most common use of this type of ports is to provide the
needed information for the closing file software.
• This card has a RS232 port through a RJ connector. So, in
case of requiring a DB9 connector, use the adaptor RJ / DB9
supplied with the relays interface card.
• For more information, contact with our S.T.S. or our nearest
distributor.
Installation.
• Remove the protection cover from the relays interface slot of
the equipment.
• Take the relays interface card and insert it into the reserved
slot. Make sure that it is well connected, so the resistance
that the own connector inside the slot makes has to be over-
come.
• Make the needed connections in the alarm terminal strip.
• Put the new protection cover that it is supplied with the relays
interface card and fix it through the same screws that fixed
the original cover.
5.3.9. Software.
• Free software download - WinPower.
WinPower is a UPS monitoring software, which makes a
user-friendly interface of monitoring and management. This
software supplies an auto Shutdown for a system based on
several PCs in case of an electrical blackout. With this soft-
ware, the end-users can monitor and manage any UPS in the
same IT network, through the RS232 or USB communication
port, never mind the distance between them.
• Installation procedure:
Go to website:
http://support.salicru.com
Choose the operating platform that you need and follow
the instructions described in the web site to download the
software.
When downloading the needed files from Internet, enter
the following licence to install the software:
511C1-01220-0100-478DF2A .
When the computer is rebooted, WinPower software will be
shown as an icon with plug shape and green colour in the
system tray, near the clock.
Fig. 15.
Main screen of the monitoring software.
5.3.10. Considerations before starting up
the connected loads.
•
It is recommended to charge the batteries for 12 hours
as minimum before using the UPS for first time.
For models with single phase input (TWIN PRO) or three
phase (TWIN/3 PRO up to 10 kVA):
It will be necessary to supply power supply voltage to the
equipment and turn "On" the circuit breaker switch on the
back M1. The battery charger will be started up automati-
cally.
For models with three phase input (TWIN/3 PRO > 10
kVA):
Supply voltage to the input and bypass terminals of the
equipment. Turn "On" the circuit breakers switches on the
back M1 and M2 and check that the neutral switch N is
in "On" position. Battery charger will work automatically.
For external battery modules:
Also for those models with batteries or extended back
up time modules external to the equipment, the battery
circuit breaker of each cabinet has to be turned "On".
• Although the equipment can work without charging the bat-
teries during the stated 12 hours without any problem, the
risk of a long blackout has to be valued during the first op-