Salicru UPS SLC TWIN PRO series User Manual Download Page 21

21

SALICRU

Description

Nr pin

Input/output

UPS fault

1

Output

General alarm

2

Output

Ground (GND)

3

Input

Remote shutdown

4

Input

Common

5

Input

Bypass

6

Output

Batería low

7

Output

UPS On

8

Output

Mains fault

9

Output

DB9 connector, standard.

Description

Nr pin

Input/output

Mains fault

Programmable

Output

Low battery

Programmable

Output

General alarm

Programmable

Output

Bypass status

Programmable

Output

Summary alarm

Programmable

Output

Battery test

Programmable

Output

Shutdown in process

Programmable

Output

Overload alarm

Programmable

Output

UPS signal "On"

1 (GND) - 14

Input

UPS signal "Off"

1 (GND) - 7

Input

Programmable signal as:

- EPO

- Shutdown on battery mode

- Shutdown on any mode

- Remote control "On-Off"

1 (GND) - 8

Input

UPS "On"

Programmable

Output

AS400 connector, optional.

Table 5. 

Relays interface alarms.

•  The most common use of this type of ports is to provide the 

needed information for the closing file software.

•  This card has a RS232 port through a RJ connector. So, in 

case of requiring a DB9 connector, use the adaptor RJ / DB9 

supplied with the relays interface card.

•  For more information, contact with our S.T.S. or our nearest 

distributor.

Installation.
•  
Remove the protection cover from the relays interface slot of 

the equipment.

•  Take the relays interface card and insert it into the reserved 

slot. Make sure that it is well connected, so the resistance 

that the own connector inside the slot makes has to be over-

come.

•  Make the needed connections in the alarm terminal strip.
•  Put the new protection cover that it is supplied with the relays 

interface card and fix it through the same screws that fixed 

the original cover.

5.3.9.  Software.

•  Free software download - WinPower.

WinPower is a UPS monitoring software, which makes a 

user-friendly interface of monitoring and management. This 

software supplies an auto Shutdown for a system based on 

several PCs in case of an electrical blackout. With this soft-

ware, the end-users can monitor and manage any UPS in the 

same IT network, through the RS232 or USB communication 

port, never mind the distance between them.

•  Installation procedure:

 

ˆ

Go to website: 
http://support.salicru.com

 

ˆ

Choose the operating platform that you need and follow 

the instructions described in the web site to download the 

software.

 

ˆ

When downloading the needed files from Internet, enter 

the following licence to install the software:
511C1-01220-0100-478DF2A .

When the computer is rebooted, WinPower software will be 

shown as an icon with plug shape and green colour in the 

system tray, near the clock.

Fig. 15. 

Main screen of the monitoring software.

5.3.10. Considerations before starting up 

the connected loads.

• 

It is recommended to charge the batteries for 12 hours 

as minimum before using the UPS for first time.

 

ˆ

For models with single phase input (TWIN PRO) or three 

phase (TWIN/3 PRO up to 10 kVA):
It will be necessary to supply power supply voltage to the 

equipment and turn "On" the circuit breaker switch on the 

back M1. The battery charger will be started up automati-

cally.

 

ˆ

For models with three phase input (TWIN/3 PRO > 10 

kVA):
Supply voltage to the input and bypass terminals of the 

equipment. Turn "On" the circuit breakers switches on the 

back M1 and M2 and check that the neutral switch N is 

in "On" position. Battery charger will work automatically.

 

ˆ

For external battery modules:
Also for those models with batteries or extended back 

up time modules external to the equipment, the battery 

circuit breaker of each cabinet has to be turned "On".

•  Although the equipment can work without charging the bat-

teries during the stated 12 hours without any problem, the 

risk of a long blackout has to be valued during the first op-

Summary of Contents for UPS SLC TWIN PRO series

Page 1: ...UNINTERRUPTIBLE POWER SUPPLY USER S MANUAL UPS SLC TWIN PRO series 4 20 kVA...

Page 2: ......

Page 3: ...on 5 3 9 Software 5 3 10 Considerations before starting up the connected loads 6 Operating 6 1 Commissioning 6 1 1 Controls before commissioning 6 2 Start up and shutdown of the UPS 6 2 1 Start up of...

Page 4: ...l exclusively Although we have made every effort to guarantee a com plete and accurate information in this user s manual we are not responsible for any errors or omissions that may exist The images in...

Page 5: ...installation and commissioning in an easy and ordered way without doubt Finally once the equipment is installed and operative for future requests or doubts that could arise it is recommended to keep...

Page 6: ...IEC 62040 2 Uninterruptible power supply UPS Part 2 EMC requirements The manufacturers responsibility is excluded in the event of any modification or intervention in the product by the customer s sid...

Page 7: ...due to the constant evolution of the product some discrepancies or small contradictions can arise In front of any doubt the labelling of the equipment will always prevail Figures regarding its main f...

Page 8: ...slot EPO RS 232 USB Protection cover for external batteries IEC output connectors Protection cover for manual bypass switch maintenance and output Protection cover for power blocks USB RS 232 EPO Pro...

Page 9: ...9 SALICRU Battery switch Protection cover for power blocks Batteries module for models 10 kVA Batteries module for models up to 10 kVA Battery switch Power blocks Fig 3 Rear view batteries module...

Page 10: ...ith no accessories screws and electrical cables Batteries owned by the client will be installed out from the case or cabinet of the UPS Under request it is possible to supply the acces sories screws a...

Page 11: ...low input current distortion so mains pollution is decreased Great adaptability to the worst conditions of the input mains Wide margins of the input voltage frequency range and wave shape so it is av...

Page 12: ...adaptor The big IT systems based on LANs and WANs that integrate servers with different platforms they have to include an easy way of controlling and management at the manager system dis posal This f...

Page 13: ...es type B for RCD devices and C characteristic for circuit breakers For the output load feeding C characteristic for circuit breaker Regarding the size they will be as minimum to the currents stated i...

Page 14: ...o the instructions described in this manual and charge them for 12 hours In parallel systems it is not needed to make the connection among the equipments to charge the batteries It can be treated as s...

Page 15: ...correct torque in the screws of the power blocks In installations with only one UPS the Jumper cable as bridge mode connected from factory between the terminals JP1 and JP2 has to be kept as it is Fo...

Page 16: ...the power contactor 2 with 400V AC coil and NO contact of 5A 1A at least 4 Cable installed from factory as a bridge mode in any TWIN 3 PRO 10 kVA equipment Remove this cable fitted in as a bridge mode...

Page 17: ...connection JP2 Output neutral N Output phase U L Output earth bonding UPS connection power block TWIN PRO UPS connection power block TWIN 3 PRO 10 kVA UPS connection power block TWIN 3 PRO up to 10 k...

Page 18: ...the first bat tery module and from this last negative to the second module and so on Proceed in the same way to connect the red posi tive cable and the green yellow earth cable In parallel systems th...

Page 19: ...and it can t be extended under any other concept due to the risk of interfer ences and communication failures that it could cause In those installations with only one UPS the Jumper cable as bridge mo...

Page 20: ...ion software 5 3 8 2 Smart slot UPS s have a unique slot for TWIN PRO and two slots for TWIN 3 PRO hidden rear the covers stated in the views of the equipment One of them allows inserting the SNMP car...

Page 21: ...h makes a user friendly interface of monitoring and management This software supplies an auto Shutdown for a system based on several PCs in case of an electrical blackout With this soft ware the end u...

Page 22: ...will be done gradually to avoid any problem as minimum in the first commissioning If inductive loads with big inrush current apart from sensi tive ones are required to be connected like laser printers...

Page 23: ...ck that the battery switch is in position On models B0 and B1 Turn the input M1 and bypass M2 circuit breakers to On Switch M2 is only available in models TWIN 3 PRO 10 kVA In equipments with single p...

Page 24: ...sfer to Bypass mode Put all the equipments on manual bypass To do it re move the cover from manual bypass switch which is located at the back of each equipment and turn all the switches to position BY...

Page 25: ...S T S Press over the shutdown key in any UPS for more than 3 seconds and each one will be shutdown supplying output voltage through the bypass Turn On the output circuit breaker switch of the distrib...

Page 26: ...UPS and put the mechanical lock To avoid wrong manoeuvring the mechanical lock has to be fit otherwise the equipment and loads are exposed to serious damages even the de struction of both or fire Turn...

Page 27: ...r 1 sec as minimum to validate the modified option and change the settings Table 6 Functionality of the buttons or keypad of the control panel The UPS has a control panel with the following parts Four...

Page 28: ...s UPS only 8 20 kVA TWIN 3 Blue 81 Fault Heatsink over temperature Red Code Condition Description Color LCD 82 Alarm Ambient over temperature UPS only 4 10 kVA TWIN Blue 83 Alarm Ambient NTC abnormal...

Page 29: ...UPS power supply information single phase input Fig 17 Main screen of the equipment with single phase input Information of load level connected to the UPS UPS power supply information three phase inpu...

Page 30: ...ls due to fault or wrong the equipment will transfer to Battery mode to feed the load s properly Fig 24 Frequency converter mode screen This function can be activated through the settings of the contr...

Page 31: ...beadaptedto the own needs and optimise the function of the equipment 7 3 1 Main screen From main screen when pressing the key or for less than 1 sec it is shown detailed information about the alarm pa...

Page 32: ...UPS status menu Structure of main menu Press 1 sec Fig 31 UPS status screen Press 1 sec Press o 1 sec Structure of Data logger submenu Structure of main menu Press 1 sec Fig 32 Event logger submenu Pr...

Page 33: ...T S password only Fig 34 Control submenu screens 7 3 5 Control submenu When pressing the key the key for less than 1 sec from this Control submenu it is accessed to the control structure see figure 34...

Page 34: ...ation from factory 7 4 1 Operating on ECO mode 7 4 1 1 Short description of the ECO mode ECO mode function allows supplying the load s from mains directly through the internal filters only meanwhile t...

Page 35: ...rs or service cen tres in order to avoid overheating and sparks with fire risk because the size is not enough Do not short the and poles of the batteries there is risk of fire or electrocution Be sure...

Page 36: ...ooling and the ambient temperature of the room NTC abnormal UPS internal fault Consult with the S T S Communication cable male disconnected Para cable Male Loss Alarm code E3 Parallel bus cable is dis...

Page 37: ...er Under Voltage Inv Under Voltage Alarm code 33 UPS internal fault Consult with the S T S Inverter Softstart Failed Inv Softstart Fail Alarm code E34 UPS internal fault Consult with the S T S Negativ...

Page 38: ...ypothetical fault 8 3 2 Out of scope of supply Our company is not forced by the warranty if it appreciates that the defect in the product doesn t exist or it was caused by a wrong use negligence insta...

Page 39: ...oad 2 Voltage THD with non linear load 5 Output voltage recovering time 100 ms IEC 62040 3 70 ms IEC 62040 3 60 ms IEC 62040 3 Transient response of the output voltage with load fluctuation of 0 100 0...

Page 40: ...ending on model 273 V DC 13 65 V DC block 4 A 345 6 V DC 14 4 V DC block Floating voltage block set 13 65 V DC 273 V DC 13 65 V DC 327 6 V DC Maximum charging current 1 A 1 4 A 4 A Recharging time 5 h...

Page 41: ...mitting Diode Circuit breaker A circuit breaker or switch is a device ready to break the electrical current of a circuit when it over comes the maximum set values On Line mode Regarding to an equipmen...

Page 42: ...42 USER MANUAL...

Page 43: ...43 SALICRU...

Page 44: ...mpany salicru salicru_SA Product Range Uninterruptible Power Supplies UPS Lighting Flow Dimmer Stabilisers DC Power Systems Static Inverters Photovoltaic Inverters Voltage stabilisers The Technical Se...

Reviews: