Hardware Manual for the PCD3 Series│Document 26/789; Version E 5│31.01.2005
Saia-Burgess
Controls Ltd.
Diagnostic information on RIOS
PCD3.Mxxx0 Classic CPUs and expansion housings
3-39
3
3.19.6 Diagnostic information on RIOS
LEDs
These three LEDs on the PCD3.T76x head station display the operating
states - error, alert, diagnostics etc. The LEDs are used as described in
the table below.
RUN
BF
DIAG
Explanation
OFF
ON
OFF
Bus error, Slave not assigned to any Master
ON
OFF
OFF
Slave working correctly
ON
OFF
ON
Diagnostic / alert from Slave
OFF
ON
ON
Bus error, Slave not assigned to any Master, but config-
ured and in a diagnostic state
X
X
flashing
5x
At least one “Lock” active
OFF
ON
flashing
2x
Current configuration comes from EEPROM or web server
ON
OFF
flashing
2x
Current configuration comes from EEPROM; Master has
the same configuration and is connected
DP diagnostics
The PCD3.T76x provides Profibus-DP with standard diagnostics in octets*) 1...6. See
also DIN 19245 part 3
*) In DIN 19245 a byte is called an octet, so the same term is used here.
Standard diagnostics:
Octet Bit
Abbreviation
Explanation
1
0
non_exist
Slave does not exist (Master set)
1
station_not_ready
Slave not ready to exchange data
2
cfg_fault
Configuration data for Master and Slave
differ
3
ext_diag
Extended diagnostic bytes
4
5
invalid_slave_response Always set to “0” by Slave
6
prm_fault
Incorrect parameter
7
master_lock
Slave parameterized via a Master
2
0
prm_req
Slave must be re-parameterized
1
stat_diag
Static diagnosis
2
Always “1”
3
wd_on
Watchdog monitoring on
4
freeze_mode
“Freeze” instruction on
5
sync_mode
“Sync” instruction on
6
Spare
7
slave_deactivated
“1” when Slave deactivated by Master
3
0 ... 6
Spare
7
ext_diag_overflow
Diagnostic data overflow in Master or
Slave
4
5, 6
Master address
ID (0xCD32)
Run green
BF red
Diag yellow