Parameterizing and diagnosis functions for all bus couplers
PCD0
26/766 E2
(HB_PCD0 26 766_E2.DOC)
SAIA-Burgess Controls Ltd.
Page 157
10.15
Function 11 Mode word for temperature module with thermo elements
Function 11 is used for parameterizing a temperature module with
thermo elements.
Diagnose Output
Diagnose Input
Byte 3
Byte 2
Byte 1
Byte 0
Byte 3
Byte 2
Byte 1
Byte 0
EC/BC
7 0
n
11
11
xxxx xxxx
0000 00xx
15 8
01
Diagnose Output
Byte 2 and Byte 3 Mode word
Byte 2 and Byte 3 are used to transmit the parameters for
characteristics, channel numbers, resolutions and number formats.
Parameter
Meaning
K-characteristic
J-characteristic
Characteristics
L-characteristic
Spare
Spare (must always be 00)
4 channels used
1 channel used
2 channels used
Channel number
3 channels used
0.1°C
0.2°C
Spare
Resolution
Spare
SIMATIC S7
SIMATIC S5
Voltage
Number format
Spare
Default setting: all bits = 0 (K-characteristic; 4 channels; 0.1°C; S7)