PCD0
Parameterizing and diagnosis functions for all bus couplers
Page 146
ã
SAIA-Burgess Controls Ltd.
(HB_PCD0 26 766_E2.DOC)
26/766 E2
10.4
Function 0 Output group error
Function 0 supplies the group error message and the last error code.
Diagnose Output
Diagnose Input
Byte 3
Byte 2
Byte 1
Byte 0
Byte 3
Byte 2
Byte 1
Byte 0
EC/BC
EC
0000 0xxx
0000 0xxx
7 0
7 0
Diagnose Input
Byte3
Current errors
Bit no.
0
A module on the bus node signals output
driver overload.
1
A module on the bus node has signaled
an error in the 24V power supply.
2
An error message is generated and
displayed on the bus coupler. The error
message is transmitted in coded form in
Byte 2 (see below).
Byte 1
Error bits from Byte 3 saved statically
Error bits are deleted when diagnosis has been
reset with function 255 (Reset) or the bus coupler
has been switched off.
Byte 2 EC (error code)
The error code is also displayed as an error message on the BC bus
coupler.