PCD0
Operating modes of the BC bus coupler
Page 138
ã
SAIA-Burgess Controls Ltd.
(HB_PCD0 26 766_E2.DOC)
26/766 E2
8.6
STOP
In Stop mode all inputs/outputs are switched off, i.e. all outputs
are set to zero and are no longer refreshed. Inputs are no longer
sent to the PLC.
If a preferred shut-off state has been set this state is adopted in Stop
mode. For preferred shut-off states see parameterizing function 5.
Channels whose control status was set using LOCK will
not
be
overridden by the preferred shut-off state.
If you have set shut-off code 2 for a module the I/O channels of this
module will continue to be refreshed.
The shut-off code is set using parameterizing and diagnosis function
5.