Manual PCD7.D412DTPF & PCD7.D4xxxT5F │ Document 27-620 – Release ENG07 │ 2019-06-20
9-5
General recommendations for the Web Editor
9
9.6
Expanded error messages for the SVGA panel
Other:
The following messages * can be displayed if the amount of memory required by the gif
files, painters, HTML tags, container variables, online /offline trends, HD logs, and language
resources (.csv files) is too large. In this case, some parameters must be adjusted by modifying
their values directly in the Setup menu (see "5.4.4
Special Settings" on page 5-8)! After mak
-
ing modifications, the panel must be restarted.
Recommendations:
We do not recommend setting the maximum value immediately, but rather first trying a moder
-
ate value, as problems could occur and performance is substantially reduced by setting all the
memory values to their maximum value.
Error messages *
Default values
Moderate
values
Maximum
values
■ out of memory in ramdisk
512 kbytes
640 kbytes
1024 kbytes
■ out of memory in heap 1
1536 kbytes
792 kbytes
2048 kbytes
■ out of memory in heap 2
1024 kbytes
2048 kbytes
4096 kbytes
■ out of memory in heap 3
1280 kbytes
2048 kbytes
4096 kbytes
■ out of memory for language resource
(or LR: out of memory)
512 kbytes
768 kbytes
1024 kbytes
9.7
Extended alarm macros
9.8
Trend macros for MB panels with "save logs to files"
The Web Editor macro library does not contain any special trend macros
with S2F (save to files) for MicroBrowser panels* . These macros must, for
the moment, be downloaded on the Support screen, and will only be inte-
grated in the next version of PG5.
● These trend macros are 100% based on the default trend macros (minimum
and complete) with some additional edit fields and buttons (container variables),
which allow for display and management functionality, and if necessary for the
deletion of csv files.
● The names of the macros are identical to the default macros and have the pre
-
fix "MB_”
● The online and offline trend logos can be saved as a "CSV format file” on the
MB panel itself, and be played back there. 20TThese .CSV files can be read as
text via FTP access, and are stored on the MB panel in a subdirectory of IN
-
TFLASH/ WEBPAGES/ "TRENDLOGS" (or optionally on the SD memory card).
● The name of the CSV file is created automatically up to a prefix of max. 5 char
-
acters. The name contains the full date when the file was created: Day, Month,
Day and Hour/Minute/Second.
Examples: TR_20110713081305.CSV (TR_is the prefix).