23
3410330_GB
ELECTRICAL CONNECTION
The electrical connection and connection systems of the unit must comply with the
regulations in force in the country of installation and must be carried out by qualified
personnel authorised by the manufacturer.
CAUTION:
do not use adapters or extension cords for
connection to the mains.
DO NOT USE ADAPTER PLUGS.
Due to safety hazards that may arise
in certain situations, the use of adapter plugs is strongly discouraged.
DO NOT USE EXTENSION CORDS.
The manufacturer does not guarantee the unit if an
extension cord is used.
WARNING: any damaged power cord must be replaced by the
manufacturer, after-sales service, or qualified personnel to prevent
risks.
Check that the mains voltage corresponds to the voltage stated on the
technical rating plate of the unit.
CAUTION
: The unit must be connected to an effective earthing system
.
CAUTION:
It is compulsory to insert the unit into an equipotential system
according to the regulations in force. The connection must be made between
the different units via the equipotential terminal
.
CAUTION:
An omnipolar switch is to be installed before the
appliance, in compliance with the current regulations applied
in the country where the appliance is installed.
The electrical mains cables must be correctly sized and selected based on the installation
conditions.
The electrical connection is carried out from the rear part.
Models 51M-51H
have 3m of three-pin cable (3G 1.5mm²) with a SHUKO type plug.
Use of any other type of electrical connection or modifying the size of the cable by less than
its length is not permitted. Take care to replace it, if necessary, with one having identical
characteristics to the original.
Models 101L-101S
are provided with 3.5m of pentapolar cable for three-phase power
supply (5G 2.5mm²) without a plug.