Tying
Unless stated otherwise, all dimensions are given in mm.
9.4.3 Using the MANTO Taper Tie
The MANTO Taper Tie can be used with the conventional tying system, however due to
the dimensions of the component, several factors must be taken into account, such as
the maximum and minimum wall thickness possible and the protruding end of the rod.
Ø 22
Ø 19
254
482
254
990
Minimum: 452
75
X
X
75
Protruding end of tie rod
Wall thickness [mm]
X [mm]
200
181
240
161
250
156
300
131
350
106
360
101
400
81
450
56
Example for a 300 mm thick wall:
X = Total length - wall thickness - 2 x (MANTO Tie Nut MANTO panel thickness)
X = (990 - 300 - 2 x (75 + 140)) / 2
X = (990 - 300 - 2 x (214)) / 2
X = (990 - 300 - 428) / 2
X = 262 / 2
X = 130 mm
9.5 FU Tightener and Edge Tie Fastener MR
The FU Tightener and the Punched Steel Tape are an alternative solution for tying
through, e.g. when panels are used for foundations.
The Safe Working Load (N) of the Edge Tie Fastener MR is 10.00 kN and of the FU
Tightener is 12.00 kN. This lead to a maximum distance between ties of 1.75 m when
used in a 0.90 m high formwork structure.
The Edge Tie Fastener MR can be placed anywhere along the edge profile of the panel.
The tie fastener connects the Tie Rod to the edge profile of the MANTO panel.
Summary of Contents for Huennebeck MANTO G3
Page 1: ...MANTO Large frame panel formwork User guide...
Page 9: ...9 Unless stated otherwise all dimensions are given in mm MANTO...
Page 61: ...61 Unless stated otherwise all dimensions are given in mm MANTO MANTO G3 M MANTO G3 M...
Page 219: ...219 Unless stated otherwise all dimensions are given in mm MANTO...