MorphoAccess® SIGMA Extreme Series - Installation Guide
Identity & Security
Section 4 :Electrical Interface
38
This document and the information therein are the property of
Safran Identity & Security
.
They must not be copied or communicated to a third party without the prior written authorization of Safran
2017_2000024418 - V1
Output Relay
Figure 14: Output relay wiring
21 Yellow / White
Relay NO
Contact relay (normally open)
22 Grey / White
Relay COM
Contact relay common
19 Orange / White
Relay NC
Contact relay (normally closed)
Nominal characteristics of relay
Load characteristics:
1 A max @ 30 VDC (according to the safety extra low voltage requirements
independently of the power supply),
Resistive load or inductive load; see warning information hereafter for inductive
load,
The internal relay is designed for at least 100 000 cycles (resistive load).
Inductive load management requires a parallel diode for a better contact
lifetime.
Example of connection for electrical door locks
Figure 15: Example of electric latch connection
+ VCC <30V
Imax < 1A
Electric
door lock
Protection
diode
MorphoAccess®
SIGMA Extreme
Terminal
Button on other
side of the door
Relay
Pin 1
Relay
Pin 2