Connect the hot lead of the input volt-

age (120 VAC, 60 HZ) to terminal H. Connect
the neutral lead to terminal GN.
120 VAC, 60 HZ must be supplied to terminals
H and GN for internal operation of the control.

Connect terminal GN to

A2

burner circuit neutral. Connect terminal P2 to
burner circuit in series with other limit controls.
Consult boiler manufacturer instructions for
proper terminal connections. Control should be
wired in series with and before other circuits.

P1

P2

A

+

0

LIMIT

CONTROLS

BURNER
CIRCUIT

NEUTRAL

HOT

GN

H

ALARM

P1

P2

A

HOT

BURNER
CIRCUIT

NEUTRAL

GN

H

BURNER

POWER

SOURCE

(24 or

120VAC)

P1

P2

A

NEUTRAL

HOT

BURNER

+

0

LIMIT

CONTROLS

GN

H

GN

P1

P2

A

BURNER

POWER

SOURCE

120VAC

H

NEUTRAL

HOT

FACTORY

INSTALLED

JUMPER

H

P1

P2

A

ALARM

GN

P2

A

120VAC

H

NEUTRAL

HOT

P1

P1

P2

A

+

0

LIMIT

CONTROLS

BURNER
CIRCUIT

HOT

NEUTRAL

GN

H

WIRING METHOD A:

SAME POWER SOURCE FOR CONTROL AND BURNER CIRCUIT.

B1

WARNING! Remove the jumper

between H and P1. 

Connect the hot lead of the

input voltage (120 VAC, 60 HZ) to terminal H.
Connect the neutral lead to terminal GN. 
120 VAC, 60 HZ must be supplied to terminals
H and GN for internal operation of the control.

Connect hot lead from the 24 VAC    

B2

or 120 VAC burner power source to terminal P1.
This terminal supplies power to terminal P2 in
normal operating conditions when water is at
the probe. Connect neutral to burner circuit.
Note: consult boiler manufacturer instructions
for proper terminal connections.

A3

Optional alarm connection. Connect

alarm common to terminal GN. Connect alarm
hot to terminal A.

Upon completion of wiring, replace control
box cover.

B3

Connect terminal P2 to burner 

circuit in series with and before other limit con-
trols.

Optional alarm connection. Connect

B4

alarm hot to terminal A. Connect alarm common
to neutral of the burner power source.

Upon completion of wiring, replace control
box cover.

A1

A2

A3

B1

B3

B2

B4

WIRING METHOD B:

SEPARATE POWER SOURCE FOR CONTROL AND BURNER CIRCUIT.

WARNING: 

Be sure to

remove the jumper
between H and P1.