OSY2 Gate Valve 

Supervisory Switch

INSTALLATION AND MAINTENANCE INSTRUCTIONS

Important

Please Read Carefully And Save

This instruction manual contains important information 

on the installation and operation of supervisory switches.  

Purchasers who install supervisory switches for use by oth-

ers must leave this manual or a copy of it with the user. 

These instructions apply to Safe Signal switches for out-

side screw and yoke valves only. Read all instructions 

carefully before beginning installation.

WARNING

Do NOT use this switch in explosive or potentially explosive 

atmospheres.

Do NOT leave unused wires exposed.

All supervisory switch installations must comply with local codes 

and ordinances and the requirements of the authority having 

jurisdiction. Additional information is available in National Fire 

Protection Association standards NFPA 13, 13D, 13R, 71, and 72.

General Installation Considerations

The OSY2 Supervisory Switch can be mounted on open yoke 

valves between 

1

2

 and 12

 in diameter in the positions shown 

in Figure 1 only. If the switch is installed with the actuator 

pointing upward, water may leak into the interior of the switch. 

Therefore, do NOT install the OSY2 with its actuating lever 

pointing upward.

All OSY2 models are equipped with a ground screw inside the 

switch housing near the conduit exit hole for those applications 

where grounding is required. 

Specifications

Contact Ratings: 

10 A @ 125/250 VAC 

 

2.5 A @ 24 VDC 

Dimensions: 5

3

4

H X 3

1

2

W X 3

1

4

L

Maximum Stem Extension: 

2

5

8

Minimum Stem Extension: 

5

8

Bracket Span: 

6

3

4

Operating Temperature Range: 

32° – 120°F (0°C – 49°C)

Shipping Weight: 

2

3

4

 lb.

Enclosure Rating: 

 NEMA Type 3R when mounted with the actuator vertical (cover on top) as tested by 

Underwriters Laboratories, Inc.

 IP54

U.S. Patent Number: 

5,213,205

Narrow Yoke Valves

As Figure 2 suggests, installing the valve with mounting bolts 

inside the yoke is recommended. However, some valves may have 

yokes that are too narrow for this arrangement. If this is the case, 

the bolts can be positioned on the outside of the yoke.

Limited Clearance Valves

The OSY2 mounting bracket fits most of the open yoke valves 

used in fire protection systems. However, some of these valves, 

especially those less than 1

1

2

 in diameter, have irregularly 

shaped yokes or such limited clearances that the clamping bar 

cannot be installed properly and/or it causes the valve to bind. If 

this is the case, the use of J-bolts is required to attach the OSY2 

to the valve (see J-Bolt Detail, Figure 2). J-bolts can be purchased 

separately by ordering the OSYRK Replacement Kit.

Installation Instructions

See Figures 2 and 3, as required, while performing the procedure 

that follows.

Perform step 1 on valves 1

1

2

 in diameter and smaller only. 

Proceed directly to step 2 if the switch is being installed on a 

valve larger than 1

1

2

 in diameter.

Figure 1:

THE FOLLOWING ARE EXAMPLES OF
ACCEPTABLE MOUNTING POSITIONS:

THE FOLLOWING MOUNTING
POSITION IS 

NOT ACCEPTABLE:

ACTUATOR

VERTICAL (DOWN)

ACTUATOR

HORIZONTAL

ACTUATOR VERTICAL

(POINTING UP)

W0221-00

I56-0393-J

  

I56-0393-J 

 

 4/21