79-15259-00
www.srsmith.com
Page 4 of 7
WARNING
•
TURN OFF INCOMING POWER BEFORE SERVICING EQUIPMENT.
•
ALL INSTALLATION AND MAINTENANCE WORK MUST BE PERFORMED BY
QUALIFIED ELECTRICAL PERSONEL ONLY.
•
GFCI BREAKER MUST BE USED TO CONNECT SRS-TX-30 TO INPUT POWER.
•
VERIFY ALL ELECTRICAL RATINGS BEFORE INSTALLATION IS COMPLETE.
FOLLOW PROPER WIRING PRACTICES IN ACCORDANCE WITH ALL LOCAL
REGULATORY REQUIREMENTS.
WIRING INSTRUCTIONS
LOCATION
The SRS-TX-30 is housed in a Type 3R rainproof enclosure and can be mounted anywhere
between the pool equipment and the breaker panel.
GFCI
Power Connections:
To wire the SRS-TX-30 use insulated
COPPER wire only, 12 gauge minimum. Run
a ½” to ¾” conduit from the main breaker
panel to the right most bottom conduit knock
out of the SRS-TX-30. Pull appropriate wires
from the main breaker panel to the SRS-TX-
30 unit. To make the input power
connections, unscrew the Isolation Cover
covering the right side of the terminal strip
and remove 3/8 inches of insulation from the
wire ends. Insert the bare end of each wire
under the pressure plate of the appropriate
screw terminal (Power Input 120V AC,
NEUTRAL
)
. Use 1/8-in. flat head
screwdriver to tighten terminal screws firmly
(10.0 in-lbs. minimum). Connect the house
ground line to the Input Ground line on the
SRS-TX-30. Install a 20 Amp max GFCI
circuit breaker in the main breaker panel and
connect the
HOT
wires from the SRS-TX-30.
As a final step replace the Isolation Cover
over the Input wire terminals and reattach the
grounding attachment screw. Use provided
cable tie to secure the Input Wires to the
Isolation cover.
GROUND
NEUTRAL
120V LINE INPUT
NEUTRAL FROM
GFCI LOAD
120V POWER
FROM GFCI LOAD
ON
OFF