S.R.Smith SRS-TX-30 Installation Instructions Manual Download Page 4

 

79-15259-00  

www.srsmith.com 

Page 4 of 7 

 

WARNING 

 

TURN OFF INCOMING POWER BEFORE SERVICING EQUIPMENT.  

 

ALL INSTALLATION AND MAINTENANCE WORK MUST BE PERFORMED BY 
QUALIFIED ELECTRICAL PERSONEL ONLY. 

 

GFCI BREAKER MUST BE USED TO CONNECT SRS-TX-30 TO INPUT POWER. 

 

VERIFY ALL ELECTRICAL RATINGS BEFORE INSTALLATION IS COMPLETE. 

FOLLOW PROPER WIRING PRACTICES IN ACCORDANCE WITH ALL LOCAL 
REGULATORY REQUIREMENTS. 

WIRING INSTRUCTIONS

LOCATION 

The SRS-TX-30 is housed in a Type 3R rainproof enclosure and can be mounted anywhere 
between the pool equipment and the breaker panel. 

GFCI 

Power Connections:

  

To wire the SRS-TX-30 use insulated 
COPPER wire only, 12 gauge minimum.  Run 
a ½” to ¾” conduit from the main breaker 
panel to the right most bottom conduit knock 
out of the SRS-TX-30.  Pull appropriate wires 
from the main breaker panel to the SRS-TX-
30 unit.  To make the input power 
connections, unscrew the Isolation Cover 
covering the right side of the terminal strip 
and remove 3/8 inches of insulation from the 
wire ends.  Insert the bare end of each wire 
under the pressure plate of the appropriate 
screw terminal (Power Input 120V AC, 
NEUTRAL

)

.  Use 1/8-in. flat head 

screwdriver to tighten terminal screws firmly 
(10.0 in-lbs. minimum).  Connect the house 
ground line to the Input Ground line on the 
SRS-TX-30. Install a 20 Amp max GFCI 
circuit breaker in the main breaker panel and 
connect the 

HOT

 wires from the SRS-TX-30.

As a final step replace the Isolation Cover 
over the Input wire terminals and reattach the 
grounding attachment screw.  Use provided 
cable tie to secure the Input Wires to the 
Isolation cover. 

GROUND

NEUTRAL

120V LINE INPUT 

NEUTRAL FROM 
GFCI LOAD 

120V POWER 
FROM GFCI LOAD 

ON 

 
 

OFF 