Program 6 – temperature setpoint definition for heat exchanger connection module
12.2.2 Setting program 6 via DIP switch S1
S1-1 S1-2 S1-3 S1-4
Designation
OFF ON
ON
OFF
Program 6: Temperature setpoint definition for heat exchanger connection
module
Table 39: DIP switch setting for program 6
12.2.3 Setting functions for program 6 via DIP switch S2
The following table lists the functions for program 6 in brief. See
Interface expansion module” on page 23
for a detailed description of the functions.
DIP switch
Status
Function
S2-1
ON
OFF
CompTrol Interface
is
configured as master in the X/Y remote control bus
CompTrol Interface
is
configured as slave in the X/Y remote control bus
S2-2
ON
OFF
X4b-II
, operating signal;
X4c-III
, heating signal
X4b-II,
compressor signal;
X4c-III
, defrost signal
S2-3
OFF
Inoperative, switch setting is always
OFF
S2-4
ON
OFF
Automatic fan speed control
Inoperative
S2-5
ON
OFF
Forced mode
Inoperative
S2-6
ON
OFF
All digital outputs are closed without a signal (NC)
All digital outputs are open without a signal (NO)
S2-7
ON
OFF
Setting determines the value shown on the 7-segment display (see
7-segment display” on page 21).
S2-8
ON
OFF
Setting determines the value shown on the 7-segment display (see
7-segment display” on page 21).
Table 40: Functions in program 6
12.2.4 Setting the analog signal type on S4 and S7
The position of the jumpers on pin headers
S4
and
S7
determines the current analog signal type
(see “4.4.1 Analog input X3” on page 19).
12.3 Analog input
Note
●
Analog input
X3-S
is only evaluated if a signal is applied to digital input
X2b-D4
(see
Functions of analog input X3” on page 23).
●
The “Thi-A” return air sensor on the heat exchanger connection module must be replaced
with a 5.0 kΩ fixed resistor (see other applicable documents: Technical Manuals for heat ex
-
changer connection module).