Functions of the CompTrol Interface expansion module
The required
resistance values from row E24 are listed in the table below:
R1 [Ω]
R2 [Ω]
Temperature setpoint [°C]
5100
0
18
4700
200
18.5
4700
430
19
4300
620
19.5
4300
820
20
3900
1100
20.5
3600
1200
21
3600
1500
21.5
3300
1600
22
3000
1800
22.5
3000
2200
23
2700
2200
23.5
2400
2400
24
2200
2700
24.5
2200
3000
25
1800
3000
25.5
1600
3300
26
1500
3600
26.5
1200
3600
27
1100
3900
27.5
820
4300
28
620
4300
28.5
430
4700
29
200
4700
29.5
0
5100
30
Table 9: Resistance values for voltage dividers
5.2 Functions via the digital inputs
5.2.1 Evaluating the analog input
When a signal is applied to digital input
X2b-D4
, analog input
X3-S
is evaluated. Depending on
the program, the analog signal is translated into a temperature or frequency setpoint. If no signal
is applied to
X2b-D4
, the analog input is not evaluated. In this case, the corresponding setpoint
can be specified via the wired remote control.
Analog input evaluation is possible in the following programs:
–
Program 0 and programs 2 to 9.