background image

Photoelectric

Smoke Detector

SF119 series 

Installation Wiring Diagram

TYPICAL WIRING DIAGRAM 

Figure 1.a shows the typical wiring diagram of 2-wire 

multiple-station smoke detector system. 

DO NOT USE LOOPED WIRE UNDER 

TERMINALS 2 AND 5 BREAK WIRE RUN TO 

PROVIDE SUPERVISION OF CONNECTIONS 

Figure 1.b shows the typical wiring diagram of 4-wire 

multiple-station smoke detector system.

DO NOT USE LOOPED WIRE UNDER 

TERMINALS 2 AND 5 BREAK WIRE RUN TO 

PROVIDE SUPERVISION OF CONNECTIONS 

WARNING

TO  PREVENT  DETECTOR  CONTAMINATION 

AND 

SUBSEQUENT 

WARRANTY 

CANCELL-TION,  SMOKE  DETECTOR  MUST 

REMAIN  COVERED  UNTIL  AREA  IS  CLEAN 

AND DUST  FREE. 

INSTALLING THE BASE 

1. To insure proper installation of the detector head to the 

base,  all  the  wires  should  be  properly  addressed  at 

installation: 

(A)Position all the wires flat against terminals. 

(B)Fasten the wires away from connector terminals. 

2. If  you  use  the  jumper  wire  to  connect  the  poles  of 

terminal  2  and  5  when  testing  the  detector  loop 

continuity, be sure to remove the jumper wire prior to 

the installation of the detector head. 

3. The  end-of-line  device  shown  in  Figure  1.a  &  1.b 

should  be  compatible  with  the  control  unit.  The 

end-of-line supervisory relay used should list the rated 

DC power voltage used. 

4. Per  UL  listing,  open  area  smoke  detectors  are 

intended  for  mounting  on  a  ceiling  no  less  than  6 

inches from a wall or mounting on a wall than no less 

than  4  inches  and  no  more  than  12  inches  from  a 

ceiling. 

5. The base of smoke detector can be mounted directly 

onto electrical junction box such as octagonal (3”, 3.5” 

or  4”),  round  (3”),  and  square  (4”  length)  box  without 

using any type of mechanical adapter. 

INSTALLING THE HEAD 

1. Align the components as shown in Figure 2. 

2. Mate the detector head onto the base and twist 

clockwise to secure it. 

3.

Do  not  install  the  detector  head  until  the  area  is 

thoroughly  cleaned  of  construction  debris,  dusts,  etc. 

The  maximum  number  of  smoke  detector  installed  in 

the same loop is 30 units.

Fig. 2 Mating detector head onto base 

ADJUSTMENT OF THE RELAY POSITION 

4-wire type: Adjust the relay set-position for wiring unit to 

the security monitoring system by the following steps: 

1. The  reset  position  for  the  relays  is  at  “normal  open” 

(NO) position, when energizing all the relays. 

2. If  one  needs  to  adjust  the  relay  set  point,  use  a 

screwdriver  to  loose  two  screws  on  the  back  of  the 

base. See Figure 3, there is a jump head next to the 

relay  on  the  PCB,  adjust  it  to  select  set  point  either 

“normal close” (NC) or “normal open” (NO) position. 

3. Relay contact rating: 

1A @30VDC, 

0.5A @125VAC. 

TESTING

1.

All  the  alarm  signal  services,  releasing  device  and 

extinguisher system should be disengaged during the 

test period and must be re-engaged immediately at the 

conclusion of testing. 

2.

After  energizing  the  detector  head  for  approximately 

one  minute,  check  to  see  the  indicator  red  LED 

flashing  once  every  1~3  seconds.  If  red  LED  fails  to 

flash, it indicates the non-functioning of the detector or 

faulty  wiring.  Re-check  the  wiring  or  replace  the 

detector if necessary. 

Fig. 3 Schematic of detector structure 

     When front cover is open   