TRANSFER OPENINGS AND GRILLE DUCT TERMINATIONS

INSTALLATION INSTRUCTIONS SUPPLEMENT

© Ruskin 2014

II-TRANS-514/

Replaces II-TRANS-1207

APPLICATIONS

Ruskin fire and combination fire and smoke dampers with 1

1

/

2

and

3 hour fire ratings may be installed in transfer opening and grille duct
termination applications. 

Grille installation in these applications is

optional.

Select  the  damper  with  sleeve  of  sufficient  length  to  fit  flush  with
wall or floor where appropriate and to permit attachment of perime-
ter mounting angles and ductwork where required. Ruskin fire and
combination  fire  and  smoke  dampers  require  mounting  angles  on
only one side of the wall or floor. Refer to the appropriate installa-
tion instructions for specific information.

GENERAL INSTALLATION

1. Install  dampers  within  opening  as  defined  in  the  appropriate

damper installation instructions sheet. Sleeve shall be flush with
wall  or  floor  on  one  side  of  the  damper  for  duct  termination
applications and on both sides for transfer opening applications.

2. Place  mounting  angles  around  damper  as  shown  in  the  appro-

priate  detail  above  on  in  accordance  with  the  specific  damper
installation  instruction.  Mounting  angles  shall  overlap  wall  or
floor  a  minimum  of  1"  (25).  Mounting  angles  installed  on  flush
side of walls shall be notched in order to meet 1" (25) wall over-
lap requirement at damper corners.

3.

Fasten angles to damper with type and quantity of fasten-

ers as specified and detailed in the appropriate installation

instructions for the damper model. The inverted mounting

angle on the grille side (refer to application figures above)

can be eliminated or the angle on the wall side opposite the

grille can be eliminated (refer to note #4). When a single

angle is used, the agle must be fastened to the damper

sleeve and wall or top of the floor in accordance with the

installation instructions for the damper.

Dimensions shown in parentheses (   ) indicate millimeters.

ITEM

DESCRIPTION

1.

Curtain type or multiple blade fire damper

2.

Damper sleeve

3.

Mounting angle (see note 4 below)

4.

Grille (optional – supplied by others)

5.

Duct

6.

Duct to damper sleeve connection

7.

Actuator (location varies)

8.

Jackshaft (indicates damper positioning)

9.

Access door (optional)

NOTES: 
1. For installation information not covered in this sheet, refer-

ence appropriate damper basic installation instructions.

2. Grilles are optional and supplied by others.
3. Vertical installation is shown; horizontal installation is similar.
4. 1

1

/

2

hour fire rated dampers that are 90"w x 48"h (2286 x

1219) or 48"w x 90"h (1219 x 2286) and smaller may be

installed with angles on only one side of the barrier (either

side of the wall or top of the floor).

FIGURE 1

TRANSFER OPENING

CURTAIN TYPE FIRE DAMPER

FIGURE 2

GRILLE DUCT TERMINATION

CURTAIN TYPE FIRE DAMPER

FIGURE 3

GRILLE DUCT TERMINATION

MULTIPLE BLADE FIRE DAMPER OR

COMBINATION FIRE AND SMOKE DAMPER

SEE COMPLETE MARKING 
ON PRODUCT