Product Installation
Connect the power cables of different colors to the corresponding grounding posts.
Ensure that the interface of the power supply cable is well connected to the power interface of the device. The power
cables must be protected using power cable retention clips after they are connected to the device.
Do not place any articles on the RG-ES100 series switch.
Reserve a spacing of at least 10 cm around the chassis for good ventilation. Do not stack the devices.
The switch should be located at places free from the large power radio launch pad, radar launch pad, and
high-frequency large-current devices. If necessary, electromagnetic shielding should be adopted. For example, use
interface cables to shield cables.
100-meter network cables should be laid inside the equipment room and outdoor cabling of such cables is prohibited.
If outdoor cabling is necessary, take relevant measures for lightning protection.
3.3.1 Mounting the Switch to a Standard 19-inch Rack
The RG-ES109G-LP-L series switches do not support rack mounting.
The RG-ES126G-P-L and RG-ES126G-LP-L series switches follow the EIA standard dimensions and can be installed in
19-inch rack. The following takes the RG-ES126G-P-L switch rack mounting procedures as an example.
Step 1: Attach the mounting brackets to the switch with the supplied screws, as shown in Figure 3-1.
Figure 3-1 Attaching the Mounting Bracket to RG-ES126G-P-L
Step 2: Use the supplied M6 screws and cage nuts to securely attach the mounting brackets to the rack, as shown in
Figure 3-2 and Figure 3-3.
Figure 3-2 Attaching the Brackets to the Rack to Install RG-ES126G-P-L
Figure 3-3 Attaching the Brackets to the Rack to Install RG-ES126G-P-L