Chapter 6
Certification
RUGGEDCOM RSG2300
Installation Guide
40
Other Approvals
•
China RoHS 2
Administrative Measure on the Control of Pollution Caused by Electronic Information Products
A copy of the Material Declaration is available online at
https://support.industry.siemens.com/cs/ww/en/
Section 6.1.9
Other Approvals
This device meets the requirements of the following additional standards:
•
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications Networking Devices in Electric
Power Substations
•
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity for Industrial Environments
•
IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General Requirements
Section 6.2
EMC and Environmental Type Tests
The RUGGEDCOM RSG2300 has passed the following Electromagnetic Compatibility (EMC) and environmental
tests.
EMC Type Tests per IEC 61850-3
Test
Description
Test Levels
Severity Levels
Enclosure Contact
±8 kV
IEC 61000-4-2
ESD
Enclosure Air
±15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
Signal Ports
±4 kV @ 2.5 kHz
DC Power Ports
AC Power Ports
IEC 61000-4-4
Burst (Fast Transient)
Earth Ground Ports
a
±4 kV
4
Signal Ports
±4 kV Line-to-Ground,
±2 kV Line-to-Line
4
DC Power Ports
±2 kV Line-to-Ground,
±1 kV Line-to-Line
3
IEC 61000-4-5
Surge
AC Power Ports
±4 kV Line-to-Ground,
±2 kV Line-to-Line
4
Signal Ports
IEC 61000-4-6
Induced (Conducted) RFI
DC Power Ports
10 V
3
Summary of Contents for RuggedSwitch RSG2300
Page 4: ...RUGGEDCOM RSG2300 Installation Guide iv...
Page 10: ...Preface RUGGEDCOM RSG2300 Installation Guide x Customer Support...
Page 16: ...Chapter 1 Introduction RUGGEDCOM RSG2300 Installation Guide 6 Supported Fiber Optic Cables...
Page 28: ...Chapter 2 Installing Device RUGGEDCOM RSG2300 Installation Guide 18 Wiring Examples...