BACnet/IP Server Configuration: Auto-Server Mode (Default)
While in Auto-Server mode no fields under the Data Groups can be edited. Auto-Server Mode looks at
the other protocol and then configures the Data Groups below to match. BACnet/IP points and will be
defined after the other protocol is configured.
Within the BACnet/IP Server, the data will automatically be configured according to the following rules:
•
Any 8 Bit Signed/Unsigned, 16 Bit Signed/Unsigned, 32 Bit Signed/Unsigned, 64 Bit
Signed/Unsigned, 32 Bit Float, and 64 Bit Float data will be mapped as
Analog Objects
.
•
Any Coils or 1/8/16/32 Bit Binary Packs will be mapped as
Binary Objects
.
•
Any String Data Types will be mapped as
CharacterString Value Objects
.
•
The Input or Output Object direction depends on whether it is configured as a Read or Write on
the other protocol.
•
If the other protocol exceeds the number of Analog, Binary or CharacterString Value Objects the
BACnet/IP Server supports (see limits on webpage), then nothing will be mapped. You will see
the # of Objects column remain at 0 and the main page will display the following error:
o
To fix this error, simply decrease the amount of data you configured on the other
protocol so that the max number of BACnet/IP objects is not exceeded OR call customer
support to increase the limits.
BACnet/IP Server Configuration: Manual Mode
1.
Click the
Edit Data Groups
button to switch from Auto-Server Mode to Manual Mode. Once
clicked the button will read
Auto-Configure Server
. The fields under the Data Groups can now
be edited.
a.
When prompted, click
OK
to confirm mode change or
Cancel
to remain in Auto Mode.
b.
Click
OK
again to keep current Data Groups and Object Properties (includes any default
Object Names, Units, and COV) or click
Cancel
to discard the current configuration.
2.
For each object type in the Read and Write Data Groups sections, select the number of objects
that the Server will support.
3.
Each object has its starting object number sequentially identified at 1. This field may be
modified.
4.
When done, click the
Save Parameters
button.
Real Time Automation, Inc.
19