background image

 

Real Time Automation, Inc. 

52 

1-800-249-1612 

 

 

 

 

 

Mapping 

– Auto-Configure Mode to Manual Configure Mode 

To transition from Auto-Configure Mapping Mode to Manual Configure Mode, click the dropdown at the 
top of the Mapping Configuration page and select Manual Configure.  

After you click this button, you will be prompted to confirm if this is really what you want to do.   

 

Click 

OK

 to proceed to Manual Configure Mode or click 

Cancel

 to remain in Auto-Configure Mappings 

Mode.   

Once OK is clicked, there are 2 options on how to proceed from here.  

 

1)

 

To keep the mappings that are already configured press 

OK

a)

 

You would want this option if you are adding additional mappings or you want to modify the 
mapping(s) that already exist. 

2)

 

To delete the mappings that are already there and start over press 

Cancel

To modify the number of mappings, enter a number in the text field next to 

# of Mappings to Configure

 

and click the 

Set Max # of Mappings

 button. You can always add more mappings if needed. 

Summary of Contents for 460ESBS-N700

Page 1: ...Real Time Automation Inc 1 1 800 249 1612 Firmware Version 8 7 22 460ESBS N700 Protocol Gateway Product User Guide...

Page 2: ...ion or limitation of incidental or consequential damages therefore the limitations set forth in this agreement may not apply to you No patent liability is assumed by Real Time Automation with respect...

Page 3: ...Type 19 EtherNet IP Adapter Data Group Configuration Manual Mode 20 EtherNet IP Adapter Data Group Configuration Using Strings 22 EtherNet IP Adapter Mapping Configuration 25 BACnet IP Server Configur...

Page 4: ...ing Data Validiation Triggering 55 Security Configuration 57 Security Configuration Security Levels 58 Security Log In 59 Security Log Out 59 Email Configuration 60 Alarm Configuration 61 Diagnostics...

Page 5: ...7 4 9 1 20 Features Added 1 BMS BM DFM DS DM TCP USB PBS have been ported to the latest base software 2 TCP BMS BM now Available on N2E and N2EW hardware Platform 3 New ASCII Mode Available on TCP A U...

Page 6: ...re the 460ESBS N700 gateway For further customization and advanced use please reference the appendices located on the CD or online at http www rtautomation com product 460 gateway support If at any ti...

Page 7: ...h as LEDs For these sections be sure to identify the hardware platform you are using To find which hardware platform you are using 1 Look on the front or back label of the unit for the part number 2 O...

Page 8: ...Real Time Automation Inc 8 1 800 249 1612 Hardware N700 Powering the Gateway 1 Connect a 12 24 VDC power source to the gateway a 2 Pin Terminal power connection with Red Wire Black Wire...

Page 9: ...under the DIN Rail 3 While pressing the 460ESBS N700 against the rail press up to engage the spring loaded lower clip and rotate the unit parallel to the DIN Rail 4 Release upward pressure Removing F...

Page 10: ...ogram from the CD ROM 3 Find unit under Select a Unit a Change Gateway s IP address to match that of your PC if DHCP has failed i You will know DHCP has failed if the gateway s IP address is AutoIP at...

Page 11: ...fault Gateway 2 The gateway must be on the same Network Subnet as the PC whether it s setup for DHCP or Static Once you have both devices on the same network you should be able to ping the gateway usi...

Page 12: ...ed after every change Multiple changes can be made before a restart but they will not be committed until the gateway is restarted When all desired changes have been made press the Restart Now button T...

Page 13: ...led Configuration cannot be changed during Running Mode If changes are needed click the Configuration Mode button shown in the green box below Configuring Mode Protocol communication is stopped and no...

Page 14: ...ice Configuration The device configuration area is where you assign the device description parameter Changes can only be made when the gateway is in Configuration Mode Once you are done configuring th...

Page 15: ...Once you are done configuring the Network Settings click the Save Parameters button If you are changing the IP Address of the gateway the change will not take effect until the unit has been rebooted...

Page 16: ...lick the EIP Adapter button to access the configuration page 1 Network Interface Network to make EtherNet IP connection If using single port hardware the Network Interface will default to Ethernet Por...

Page 17: ...group 2 Data Format sets the formatting of the data Automap will use this packing size to map data to from the other protocol There are three ways to configure this protocol 1 Auto Configure Group by...

Page 18: ...d as 64 Bit Int or 64 Bit Uint matching signs whenever possible 5 Any 32 Bit Float will be mapped as 32 Bit Float 6 Any 64 Bit Float will be mapped as 64 Bit Float 7 Any coils or 8 16 32 Bit Binary Pa...

Page 19: ...e other protocol on the gateway and auto configures the data groups on the EtherNet IP adapter for all the data points within the other protocol Another way to view this option is to say that the data...

Page 20: ...OK to confirm mode change or Cancel to remain in Auto Configure Mode b Once OK is clicked there are two options for how to proceed i To keep the data groups that are already configured press OK c You...

Page 21: ...r Save Parameters is pressed Example Use the instances and sizes next to the I O Type for information to connect to an EtherNet IP scanner client Input Instance or destination for target to originator...

Page 22: ...gth Each String String 1 Port String 2 Port String 3 Port and String 4 Port may have 99 characters When using String 1 Port use Input Assembly 101 Output Assembly 113 where Byte 0 would be the length...

Page 23: ...the gateway 3 The Coms Format Select the format you wish to display in your PLC 4 The Connection Parameters Keep in mind that the RTA sizes that are display on the EtherNet IP adapter web base configu...

Page 24: ...LC Comm Format is setup for Data Int then the PLC size needs to be setup at 48 Since INT has 2 bytes you ll need 48 instances of 16 bits which will equal 96 bytes to the RTA If PLC Comm Format is setu...

Page 25: ...le will reference how the RTA gateway mapping references RSLogix Below the RTA gateway is configured as follows Within the PLC the Comm Format is selected as Data INT with a size of 48 16 bit NOTE RTA...

Page 26: ...Real Time Automation Inc 26 1 800 249 1612...

Page 27: ...re going to represent each 16 bit data format Listed below the start is O2T_Grp1 0 and the end is O2T_Grp1 15 Each group is going to represent 32 bytes of data in a 16 bit format In your RSLogix there...

Page 28: ...is 47808 0xBAC0 4 Enter a unique Instance identifier for the gateway This value must be unique on the BACnet IP network 5 Inactivity Timeout Enter the amount of time in milliseconds the gateway should...

Page 29: ...oup by Data Type Default 2 Manual Configure Mode NOTE You may go back and forth between modes but when reverting from Manual Configure Mode to Auto Configure Mode all changes made in Manual Mode will...

Page 30: ...Real Time Automation Inc 30 1 800 249 1612...

Page 31: ...at data will be mapped as Analog Objects 4 Any Coils or 1 8 16 32 Bit Binary Packs will be mapped as Binary Objects 5 Any String Data Types will be mapped as CharacterString Value Objects 6 The input...

Page 32: ...bject properties includes any default object names units and COV that are already configured press OK You would want this option if you are adding additional data groups or you want to modify the data...

Page 33: ...RTA gateway is monitoring and sending over to the Build Automation System BAS to monitor you can configure the group to represent each device The image above displays 1 device if there are 5 total de...

Page 34: ...ce When in Auto Configure Mode these fields are not configurable Follow these steps to configure binary inputs or outputs in Manual Configure Mode 1 Select Binary Input or Binary Output from the upper...

Page 35: ...to Configure Mode these fields are not configurable Follow these steps to configure CharacterString value reads and writes in Manual Configure Mode 1 Select CharacterString Value Read or CharacterStri...

Page 36: ...The Group Name is designed to be used when there are multiple BACnet IP objects that have the same name This is useful when you have multiple identical devices connected on the other protocol Follow t...

Page 37: ...ting to a BACnet IP client on a different subnet 1 Foreign Device Registration recommended This option can be used ONLY when the BACnet IP Broadcast Management Device BBMD device on the other subnet o...

Page 38: ...eway will automatically take the string data type from one protocol and map it into the other See String Auto Configure section for more details Option 3 Manual Configure Mappings If you don t want to...

Page 39: ...isplay Data button to view how the data is mapped and what the values of each mapping are Here you will see how each data point excluding strings is mapped To view select the device from the dropdown...

Page 40: ...3 on BACnet NOTE If a data point is mapped twice only the first instance of it will show here EX If Modbus 400001 400040 from Slave 1 are both mapped to AI1 only 400001 will show as being mapped to AI...

Page 41: ...iew the actual data mappings click the Edit Mapping button For more details see the Data Mapping Explanation section To view the data mappings purely as text click the View as Text button For more det...

Page 42: ...ps from a string click the dropdown menu to generate the information regarding that device The string data will be displayed in both Hex and ASCII only the ASCII data is sent The example below shows d...

Page 43: ...Info drop down and navigating to ASCII Diagnostics page You will also have to select the port you want to view in the dropdown below ASCII To view the string mappings click the Edit Mapping button Fo...

Page 44: ...on would look like my example below There are more detailed examples of what all the fields represent in the ASCII Parsing section The message is broken up into 3 Groups or Parsing fields To view the...

Page 45: ...ata type If the Auto Configure function does not map the data as you want or you want to add modify the mappings you may do so by going into Manual Configure mode The following are examples of the Aut...

Page 46: ...then only 1 operation is allowed c Select the Operation s to perform i Math Operations are performed in the order they are selected ii If more than one point is selected on the source the Math Operat...

Page 47: ...ase In this example Ram0 is scaled into Ram1 Ram1 is then increased by 5 and stored into Ram2 Ram0 and Ram2 could be considered a source or destination group 2 Temporary Ram Double a This is like the...

Page 48: ...ys to map the NetBmpStat Option 1 Map the whole 32bit value to a destination Example below shows the NetBmpStat is going to an Analog BACnet object Using a connection of 5 Modbus Slave devices AI1 wil...

Page 49: ...ult 0x80 7 128 nonrecoverable fault For this example the ETC Status is mapped to a PLC tag called PLC_Status Example ETC Status is 0x00000013 19 decimal here is the break down Hex Bit Decimal Explanat...

Page 50: ...e fault config err 0x10 28 268 435 456 Configuration Mode 0x20 29 536 870 912 No Ethernet Cable Plugged In For this example the MC Status is mapped to a PLC tag called MC_Status Example MC Status is 0...

Page 51: ...string 1 Enable red box above Check to enable mapping If not checked this mapping is skipped 2 Source Field yellow box above a Group Select the string data group you set up in the protocol config to...

Page 52: ...ual Configure Mode or click Cancel to remain in Auto Configure Mappings Mode Once OK is clicked there are 2 options on how to proceed from here 1 To keep the mappings that are already configured press...

Page 53: ...op of the Mapping Configuration page and select Auto Configure Mappings Click OK to proceed to delete all current mappings and go back to Auto Configure Mappings Mode Click Cancel to keep all mappings...

Page 54: ...at register 1 and want to see if 400011 is mapped If it is not in this text box then it is not mapped and no data will be transferred This is the text display for the example shown under the Data Mapp...

Page 55: ...ake value is set equal to Trigger value 5 Map Handshake to reference data point Note is an internal reference to the Server Slave number you are settings up ex RTA Server Slave products can only be Tr...

Page 56: ...ppings 4 The first mapping is going to be the Data Validation Triggering AO21 will write to the RTA MC Trigger 1 will mark data invalid 5 The second mapping the MC Handshake will increment that all da...

Page 57: ...ax of 32 characters case sensitive a Re enter the Password 4 E mail In case the password was forgotten a user can have their password e mailed to them if e mail was configured 5 Hint A helpful reminde...

Page 58: ...can have a separate security level associated with it for each user Security Levels 1 Full Access Capability to view and configure a web page 2 View Access Capability to view a web page but cannot co...

Page 59: ...word This is used to reset security settings Confirm reset password must be selected to confirm this action Once confirmed there is a 15 minute window to do a hard reset of the gateway by physically r...

Page 60: ...use 2 SMTP Mail Password If authentication is required enter the SMTP Server s password Optional 3 SMTP Server Enter the Name of the SMTP Server or the IP Address of the Server 4 From E mail Enter th...

Page 61: ...ction a Top dropdown select the Data Group This dropdown menu will contain all groups that go from the gateway to the network b Lower dropdown select the Data Point s Specific Point This is used to se...

Page 62: ...he Clear Error Value Ex Ticks Since Powerup 5000 This will clear the alarm after 5000 ticks have elapsed since the unit powered up 6 Enter an Alarm Name This will make the alarm unique and will be ava...

Page 63: ...m 7 Status The current status of the alarm either OK or ALARM 8 of Times Active This count represents the number of times this alarm has become active If an alarm is triggered this count will incremen...

Page 64: ...hen an alarm is cleared the following will occur 1 A one time notification will be sent to the email associated with the alarm a For duplicate emails to occur the alarm must become active and then be...

Page 65: ...his is to be used to prevent jitter Default value is 0ms This timer takes priority over the Stale Data Timer There is a separate timer per data mapping This timer is active only after the first write...

Page 66: ...larm that was active Common Errors 1 Destination or Source Point does not exist a Solution Re map the mapping 2 Source or Destination Pointer too small a There is not enough space on either the Source...

Page 67: ...et all displayed values back to zero and clear the Status Strings 2 If viewing EtherNet IP adapter this will only clear the values for the EtherNet IP adapter section of the gateway Device Status 1 Co...

Page 68: ...O Input Msgs Sent Number of messages sent to the scanner Note Sum of all connections 3 I O Output Msgs Received Number of messages received from the scanner Note Sum of all connections 4 I O Heartbeat...

Page 69: ...nection in use 2 More than one guy configuring a Attempting to open Exclusive Owner Output Only connection that is already established 3 Connection size mismatch a Connection Input Output Size set up...

Page 70: ...P Server this will only clear the values for the BACnet IP Server section of the gateway Device Status 1 Connected The gateway is connected to a BACnet IP client 2 Not Connected The gateway is not con...

Page 71: ...Read Property Response Sent Number of Read Property Responses sent to the BACnet IP client 8 Read Multiple Property Response Sent Number of Read Property Multiple responses sent to the BACnet IP clie...

Page 72: ...Service request denied BACnet IP request cannot be processed because the BACnet IP connection is not established d Read access denied BACnet IP read request cannot be processed e Unknown object BACnet...

Page 73: ...her device into the 460 gateway whenever it is in Configuration Mode Upon clicking the Choose File button you will be prompted to select a location from which to load the saved file Once the location...

Page 74: ...tered an error while trying to load the saved configuration the gateway will indicate the first error it found and a brief description about it under the Load Configuration button Contact RTA Support...

Page 75: ...y you wish to copy the configuration from 2 Power up the gateway you wish to copy the configuration to DO NOT INSERT SD CARD YET 3 Navigate to the webpage inside the unit 4 Navigate to the dropdown Ot...

Page 76: ...tored in the Flash File System within the gateway Identify your device by clicking the Start Flashing LEDs button By clicking this button the two diagnostic LEDs will flash red and green Once you have...

Reviews: