background image

 

Real Time Automation, Inc. 

 

 1-800-249-1612 

 

 

 

 

 

 

 

 

 

 

             Firmware Version 8.7.53

 

 

460ECPS-N2EW 

Protocol Gateway 

 

Product User Guide 

Summary of Contents for 460ECPS-N2EW

Page 1: ...Real Time Automation Inc 1 1 800 249 1612 Firmware Version 8 7 53 460ECPS N2EW Protocol Gateway Product User Guide...

Page 2: ...ion or limitation of incidental or consequential damages therefore the limitations set forth in this agreement may not apply to you No patent liability is assumed by Real Time Automation with respect...

Page 3: ...guration 21 EtherNet IP Scanner Device Configuration 22 Configuring Input Instance 23 Configuring Output Instance 24 PROFINET IO Server Configuration 25 PROFINET IO Server Slot Configuration 26 PROFIN...

Page 4: ...gering Data Validiation Triggering 59 Security Configuration 61 Security Configuration Security Levels 62 Security Log In 63 Security Log Out 63 Email Configuration 64 Alarm Configuration 65 Diagnosti...

Page 5: ...Real Time Automation Inc 5 1 800 249 1612 Intelligent Reset Button 81 Utilities 82...

Page 6: ...tware 2 TCP BMS BM now Available on N2E and N2EW hardware Platform 3 New ASCII Mode Available on TCP A USB WI protocols 4 User Guides updated with more examples Bug Fixes 1 Improved Data Mapping and S...

Page 7: ...SCII devices is dependent on the Hardware and Product number of the 460 gateway For further customization and advanced use please reference the appendices located on the CD or online at http www rtaut...

Page 8: ...h as LEDs For these sections be sure to identify the hardware platform you are using To find which hardware platform you are using 1 Look on the front or back label of the unit for the part number 2 O...

Page 9: ...wer the gateway 1 2 1 Connect a 12 24 VDC power source to the gateway Red Wire Black Wire a The unit draws 8 VDC 900mA 7 2W Max b The unit draws 35 VDC 900mA 31 5W Max c The gateway has a voltage oper...

Page 10: ...max Supervised The unit is certified to be operated at 40 C to 50 C Instructions d alimentation et d installation pour environnement dangereux Cet quipement est con u pour tre utilis uniquement dans d...

Page 11: ...port specific parameters These settings must match the settings of the device s that you are connecting to Only 1 mode can be configured for this hardware Below are the wiring pinouts for each mode Wh...

Page 12: ...Real Time Automation Inc 12 1 800 249 1612 RS422 pinouts...

Page 13: ...e under the DIN Rail 3 While pressing the 460ECPS N2EW against the rail press up to engage the spring loaded lower clip and rotate the unit parallel to the DIN Rail 4 Release upward pressure Removing...

Page 14: ...ogram from the CD ROM 3 Find unit under Select a Unit a Change Gateway s IP address to match that of your PC if DHCP has failed i You will know DHCP has failed if the gateway s IP address is AutoIP at...

Page 15: ...fault Gateway 2 The gateway must be on the same Network Subnet as the PC whether it s setup for DHCP or Static Once you have both devices on the same network you should be able to ping the gateway usi...

Page 16: ...rted after every change Multiple changes can be made before a restart but they will not be committed until the gateway is restarted When all desired changes have been made press the Restart Now button...

Page 17: ...led Configuration cannot be changed during Running Mode If changes are needed click the Configuration Mode button shown in the green box below Configuring Mode Protocol communication is stopped and no...

Page 18: ...e Save Parameters button Network Configuration The network configuration area is where you assign the IP address and other network parameters Changes can only be made when the gateway is in Configurat...

Page 19: ...ifferent Network Interface options Independent Mode Switch Mode and Wi Fi Mode Below you can find the different use cases that each interface option allows for Independent Mode 1 Two Ethernet based pr...

Page 20: ...logy is NOT supported 2 Two Ethernet based protocols on same IP Network a Ethernet Port 1 used for direct protocol communication with another switch hub or router b Ethernet Port 2 available for a dai...

Page 21: ...rk you wish to communicate with EtherNet IP scanner If using single port hardware the Network Interface will default to Ethernet Port only 2 Delay Between Connect Attempts Enter the amount of time the...

Page 22: ...the and buttons and click the Delete Adapter button d Click the Save Parameters button to save change before restarting or going to another configuration page 2 The Enable check box should be selected...

Page 23: ...defined by the I O adapter device This must match for proper communication 5 Priority Select the appropriate value as defined by the I O adapter Default value is scheduled 6 Connection Type Select the...

Page 24: ...ill occur 4 Output Instance This is the output instance defined by the I O adapter device This must match for proper communication 5 Priority Select the appropriate value as defined by the I O adapter...

Page 25: ...d by TIA Portal or Classic STEP 7 Note To properly set communication to the PROFINET controller you will need to install the GSD file that is downloadable on the configuration web page or on the CD th...

Page 26: ...urable Options include 8 16 32 64 and 128 Bytes 3 Data Format sets the formatting of the data Automap will use this packing size to map data to from the other protocol There are three ways to configur...

Page 27: ...r possible 5 Any 32 Bit Float will be mapped as 32 Bit Float 6 Any 64 Bit Float will be mapped as 64 Bit Float 7 Any Strings will be mapped as Short String 8 Any Coils or 1 8 16 32 Bit Binary Packs wi...

Page 28: ...other protocol on the gateway and auto configures the data groups on the PROFINET server for all the data points within the other protocol Another way to view this option is to say that the data poin...

Page 29: ...clicked there are two options for how to proceed 4 To keep the data slots that are already configured press OK i You would want this option if you are adding additional data slots or you want to modi...

Page 30: ...e hardware option in the right pane Double click on the Hardware icon 2 IF YOU HAVE ALREADY INSTALLED THE GSD FILE SKIP TO STEP 9 OTHERWISE Under Options select Install GSD Files 3 On the PROFINET IO...

Page 31: ...l see the RTA profile under PROFINET IO Additional Field Devices Gateway 460PSxx 9 IF YOU HAVE ALREADY CONFIGURED THE PROFINET I O CONTROLLER SKIP TO STEP 11 OTHERWISE Right click on the PN IO block a...

Page 32: ...omation Inc 32 1 800 249 1612 11 Find the RTA device in the I O tree It will be under PROFINET IO Additional Field Devices Gateway 460PSxx 460PSxx 1 port 12 Once found drag the Standard icon into the...

Page 33: ...tomation Inc 33 1 800 249 1612 13 Double click the gateway icon to open the properties window If not already done uncheck the Assign IP Address via IO controller option some versions already do this a...

Page 34: ...evice click on the PLC tab select Ethernet then Assign Device Name 15 Click the Assign name button to give the RTA gateway a name This name will appear on the RTA PROFINET configuration page If you wo...

Page 35: ...e Save and Compile button and then the Download to PLC button Terminology Note and Example I addresses refer to input Q addresses refer to output B refers to bytes and W refers to words So in this cas...

Page 36: ...A Portal This is how you would set up the following example in your controller 1 In your project click the Device View tab and select your PLC 2 IF YOU HAVE ALREADY INSTALLED THE GSD FILE SKIP TO STEP...

Page 37: ...1612 3 On the RTA PROFINET IO Server configuration page download the zip file 4 Browse to folder containing the GSD file 5 Check the box to the left of the imported path and click Install 6 Click Clo...

Page 38: ...rdware platform if it has one Ethernet port or 2 Ethernet ports determines the icon to use 9 Drag the 460PSxx 1 port next to the PLC click on the Not Assigned and select the PLC to connect to 10 Once...

Page 39: ...1 800 249 1612 a The PROFINET Device Name field is the name to assign to the RTA gateway b Make sure the PROFINET device and the gateway are on the same network 14 Right click on the RTA device and se...

Page 40: ...n to give the RTA a valid name on the network Once the RTA gateway is in run mode this name will appear on the PROFINET web page 16 To match the above configuration in the 460 gateway add one 8 byte i...

Page 41: ...o Device button in red 19 Once everything is downloaded to the PLC there will be a green check box on both devices then click Go Online see red box Terminology Note and Example I addresses refer to in...

Page 42: ...eway will automatically take the string data type from one protocol and map it into the other See String Auto Configure section for more details Option 3 Manual Configure Mappings If you don t want to...

Page 43: ...isplay Data button to view how the data is mapped and what the values of each mapping are Here you will see how each data point excluding strings is mapped To view select the device from the dropdown...

Page 44: ...3 on BACnet NOTE If a data point is mapped twice only the first instance of it will show here EX If Modbus 400001 400040 from Slave 1 are both mapped to AI1 only 400001 will show as being mapped to AI...

Page 45: ...iew the actual data mappings click the Edit Mapping button For more details see the Data Mapping Explanation section To view the data mappings purely as text click the View as Text button For more det...

Page 46: ...ps from a string click the dropdown menu to generate the information regarding that device The string data will be displayed in both Hex and ASCII only the ASCII data is sent The example below shows d...

Page 47: ...Info drop down and navigating to ASCII Diagnostics page You will also have to select the port you want to view in the dropdown below ASCII To view the string mappings click the Edit Mapping button Fo...

Page 48: ...on would look like my example below There are more detailed examples of what all the fields represent in the ASCII Parsing section The message is broken up into 3 Groups or Parsing fields To view the...

Page 49: ...ata type If the Auto Configure function does not map the data as you want or you want to add modify the mappings you may do so by going into Manual Configure mode The following are examples of the Aut...

Page 50: ...then only 1 operation is allowed c Select the Operation s to perform i Math Operations are performed in the order they are selected ii If more than one point is selected on the source the Math Operat...

Page 51: ...ase In this example Ram0 is scaled into Ram1 Ram1 is then increased by 5 and stored into Ram2 Ram0 and Ram2 could be considered a source or destination group 2 Temporary Ram Double a This is like the...

Page 52: ...ys to map the NetBmpStat Option 1 Map the whole 32bit value to a destination Example below shows the NetBmpStat is going to an Analog BACnet object Using a connection of 5 Modbus Slave devices AI1 wil...

Page 53: ...ult 0x80 7 128 nonrecoverable fault For this example the ETC Status is mapped to a PLC tag called PLC_Status Example ETC Status is 0x00000013 19 decimal here is the break down Hex Bit Decimal Explanat...

Page 54: ...e fault config err 0x10 28 268 435 456 Configuration Mode 0x20 29 536 870 912 No Ethernet Cable Plugged In For this example the MC Status is mapped to a PLC tag called MC_Status Example MC Status is 0...

Page 55: ...string 1 Enable red box above Check to enable mapping If not checked this mapping is skipped 2 Source Field yellow box above a Group Select the string data group you set up in the protocol config to...

Page 56: ...ual Configure Mode or click Cancel to remain in Auto Configure Mappings Mode Once OK is clicked there are 2 options on how to proceed from here 1 To keep the mappings that are already configured press...

Page 57: ...op of the Mapping Configuration page and select Auto Configure Mappings Click OK to proceed to delete all current mappings and go back to Auto Configure Mappings Mode Click Cancel to keep all mappings...

Page 58: ...at register 1 and want to see if 400011 is mapped If it is not in this text box then it is not mapped and no data will be transferred This is the text display for the example shown under the Data Mapp...

Page 59: ...ake value is set equal to Trigger value 5 Map Handshake to reference data point Note is an internal reference to the Server Slave number you are settings up ex RTA Server Slave products can only be Tr...

Page 60: ...ppings 4 The first mapping is going to be the Data Validation Triggering AO21 will write to the RTA MC Trigger 1 will mark data invalid 5 The second mapping the MC Handshake will increment that all da...

Page 61: ...ax of 32 characters case sensitive a Re enter the Password 4 E mail In case the password was forgotten a user can have their password e mailed to them if e mail was configured 5 Hint A helpful reminde...

Page 62: ...can have a separate security level associated with it for each user Security Levels 1 Full Access Capability to view and configure a web page 2 View Access Capability to view a web page but cannot co...

Page 63: ...word This is used to reset security settings Confirm reset password must be selected to confirm this action Once confirmed there is a 15 minute window to do a hard reset of the gateway by physically r...

Page 64: ...use 2 SMTP Mail Password If authentication is required enter the SMTP Server s password Optional 3 SMTP Server Enter the Name of the SMTP Server or the IP Address of the Server 4 From E mail Enter th...

Page 65: ...ction a Top dropdown select the Data Group This dropdown menu will contain all groups that go from the gateway to the network b Lower dropdown select the Data Point s Specific Point This is used to se...

Page 66: ...he Clear Error Value Ex Ticks Since Powerup 5000 This will clear the alarm after 5000 ticks have elapsed since the unit powered up 6 Enter an Alarm Name This will make the alarm unique and will be ava...

Page 67: ...either OK or ALARM 8 of Times Active This count represents the number of times this alarm has become active If an alarm is triggered this count will increment Alarms Active While one or more alarms a...

Page 68: ...occur 1 A one time notification will be sent to the email associated with the alarm a For duplicate emails to occur the alarm must become active and then be cleared again 2 Total Alarms Active will d...

Page 69: ...his is to be used to prevent jitter Default value is 0ms This timer takes priority over the Stale Data Timer There is a separate timer per data mapping This timer is active only after the first write...

Page 70: ...larm that was active Common Errors 1 Destination or Source Point does not exist a Solution Re map the mapping 2 Source or Destination Pointer too small a There is not enough space on either the Source...

Page 71: ...rs dropdown and clicking View Additional diagnostic information can be found by clicking the Help button NOTE This page will auto refresh every five seconds with the latest data Clear All Values This...

Page 72: ...nected to all the EtherNet IP adapters that are configured and enabled 2 Solid Green Connected Idle The gateway is connected to all the EtherNet IP adapters that are configured and enabled but the con...

Page 73: ...r I O Allocation Total number of refused connections Status Strings These are the values for All Adapters or the specific adapter selected 1 Last I O Allocation Error Displays the last error code rece...

Page 74: ...le The gateway is trying to access the adapter too quickly Increase the RPI value in the gateway 6 Unsupportable RPI The value configured in the gateway for the RPI is not supported in the adapter dev...

Page 75: ...atus 1 Connected A PROFINET IO controller has a connection for the gateway 2 Not Connected a The PROFINET IO controller has not initiated communication to the gateway b The PROFINET IO server has an i...

Page 76: ...or the number of parameters written by the IO controller 4 PN Ethernet Pkts Received a Number of Layer 2 Ethernet Messages received 5 PN Ethernet Pkts Sent a Number of Layer 2 Ethernet Messages transm...

Page 77: ...col is a master client you may set the LED to represent either all slaves servers configured in the gateway or a slave server device To select a slave server device 1 Select the protocol in the left d...

Page 78: ...her device into the 460 gateway whenever it is in Configuration Mode Upon clicking the Choose File button you will be prompted to select a location from which to load the saved file Once the location...

Page 79: ...tered an error while trying to load the saved configuration the gateway will indicate the first error it found and a brief description about it under the Load Configuration button Contact RTA Support...

Page 80: ...y you wish to copy the configuration from 2 Power up the gateway you wish to copy the configuration to DO NOT INSERT SD CARD YET 3 Navigate to the webpage inside the unit 4 Navigate to the dropdown Ot...

Page 81: ...rdware 1 On the front of the gateway below the Power LED there is a small pinhole Using a paperclip press the button through this pinhole and hold the button for at least 5 seconds 2 After 5 seconds t...

Page 82: ...tored in the Flash File System within the gateway Identify your device by clicking the Start Flashing LEDs button By clicking this button the two diagnostic LEDs will flash red and green Once you have...

Reviews: